DLC3010 Digital Level Controller
Principle of Operation
May 2018
103
Figure A‐6. Digital Level Controller Analog Output Signal
2
4
6
8
10
12
14
16
18
20
22
24
-20%
0%
20%
40%
60%
80%
100%
120%
Output during Alarm with
Alarm Jumper in Hi Position
Output Saturated
(3.8 mA)
(22.5 mA)
Output during Alarm with
Alarm Jumper in Lo
Position
(3.7 mA)
Output Saturated
(20.5 mA)
Normal Operation
Output (mA)
PV Range
E0379
Note
The upper alarm value is compliant with NAMUR NE 43, but the lower alarm value is not.
If using in a system with NAMUR NE 43 compatibility, the high alarm value may be an appropriate choice.
Other circuits in the digital level controller provide reverse polarity protection, transient power surge protection, and