Emerson Fisher 67D Series Скачать руководство пользователя страница 1

www.fisherregulators.com

D103151XUS2

Installation Guide

English – May 2010

67D Series

Installation

!

Warning

Only qualified personnel should install 

or service a regulator.  Regulators 

should be installed, operated, and 

maintained in accordance with 

international and applicable codes and 

regulations, and Emerson Process 

Management Regulator Technologies, 

Inc. instructions.
If the regulator vents fluid or a leak 

develops in the system, it indicates that 

service is required.  Failure to take the 

regulator out of service immediately may 

create a hazardous condition.
Personal injury, equipment damage, or 

leakage due to escaping fluid or bursting 

of pressure-containing parts may result 

if this regulator is overpressured or 

is installed where service conditions 

could exceed the limits given in the 

Specifications section, or where 

conditions exceed any ratings of the 

adjacent piping or piping connections.
To avoid such injury or damage, provide 

pressure-relieving or pressure-limiting 

devices (as required by the appropriate 

code, regulation, or standard) to prevent 

service conditions from exceeding limits.
Additionally, physical damage to the 

regulator could result in personal injury 

and property damage due to escaping 

fluid.  To avoid such injury and damage, 

install the regulator in a safe location.
The internal relief valve in the 

67DFSR Series regulators do not 

provide full overpressure protection.  

The internal relief valve is designed 

for minor seat leakage only.

Clean out all pipelines before installation of the 

regulator and check to be sure the regulator has not 

been damaged or has collected foreign material during 

shipping.  For NPT bodies, apply pipe compound to the 

external pipe threads.  For flanged bodies, use suitable 

line gaskets and approved piping and bolting practices.  

Install the regulator in any position desired, unless 

otherwise specified, but be sure flow through the body 

is in the direction indicated by the arrow on the body.

Introduction

This installation guide provides instructions for 

installation, startup, and adjustment.  To receive a copy 

of the instruction manual, contact your local Sales 

Office or view a copy at www.fisherregulators.com.  

For further information refer to: 67D Series Instruction 

Manual, form 5858, D103151X012.

P.E.D. Category

This product may be used as a safety accessory 

with pressure equipment in the following Pressure 

Equipment Directive 97/23/EC categories.  It may 

also be used outside of the Pressure Equipment 

Directive using sound engineering practice (SEP) 

per table below.

PRODUCT SIZE

CATEGORIES

FLUID TYPE

1/2 NPT

SEP

1

Specifications

Body Size and End Connection Style

1/2 NPT

Maximum Inlet Pressure (Body Rating)

(1)

 

Filtered models: 

17,2 bar (250 psig)

Unfiltered models: 

27,6 bar (400 psig)

Maximum Outlet Pressure

(1) 

10,3 bar (150 psig) over outlet pressure setting 

up to a maximum of 17,2 bar (250 psig) 

Proof Test Pressure

All Pressure Retaining Components have been 

proof tested per Directive 97/23/EC - Annex 1, 

Section 7.4

Outlet Pressure Ranges

(1)

0 to 1,4 bar (0 to 20 psig)

0 to 2,4 bar (0 to 35 psig)

0 to 4,1 bar (0 to 60 psig)

0 to 8,6 bar (0 to 125 psig)

0 to 10,3 bar (0 to 150 psig)

Temperature Capabilities

(1)

       With Nitrile (NBR)

 

 

Standard Bolting: 

-29° to 82°C (-20° to 180°F) 

 

Stainless Steel Bolting:

 -40° to 82°C (-40° to 180°F)

 

 With Fluorocarbon (FKM):

 

 

Polyethylene Filter 

(Standard)

 

-18° to 82°C (0° to 180°F)

 

Polyvinylidene (PVDF), Stainless Steel, or Glass Filter  

        (Optional):

 -18° to 149°C (0° to 300°F)

       

With Silicone (VMQ) Diaphragm, Low Temperature 

 

Nitrile (NBR) O-rings, and Low Temperature 

 

Bolting:

 -51° to 82°C (-60° to 180°F)

 

With Gauges:

 -29° to 82°C (-20° to 180°F)

 

With Automatic Drain:

 4° to 79°C (40° to 175°F)

  1.  The pressure/temperature limits in this Installation Guide and any applicable standard or  

       code limitation should not be exceeded.

Содержание Fisher 67D Series

Страница 1: ...g practices Install the regulator in any position desired unless otherwise specified but be sure flow through the body is in the direction indicated by the arrow on the body Introduction This installation guide provides instructions for installation startup and adjustment To receive a copy of the instruction manual contact your local Sales Office or view a copy at www fisherregulators com For furt...

Страница 2: ...sted slowly open the upstream and downstream shut off valves Adjustment To change the outlet pressure remove the closing cap or loosen the locknut and turn the adjusting screw clockwise to increase outlet pressure or counterclockwise to decrease pressure Monitor the outlet pressure with a test gauge during the adjustment Replace the closing cap or tighten the locknut to maintain the desired settin...

Страница 3: ...1 Types 67DFS and 67DFSR Assembly 33 18 20 17 3 16 1 15 4 12 2 6 9 2 19 7 45 50 11 58 57 3 66 49 48 5 65 18 19 31 GE31805 Figure 2 Types 67DS and 67DSR Assembly 33 18 19 20 45 16 15 11 49 12 48 14 57 58 1 50 3 17 7 GE31806 ...

Страница 4: ...agement product remains solely with the purchaser Emerson Process Management Regulator Technologies Inc 2010 All Rights Reserved Industrial Regulators Emerson Process Management Regulator Technologies Inc USA Headquarters McKinney Texas 75069 1872 USA Tel 1 800 558 5853 Outside U S 1 972 548 3574 Asia Pacific Shanghai China 201206 Tel 86 21 2892 9000 Europe Bologna Italy 40013 Tel 39 051 4190611 M...

Отзывы: