Instruction Manual
D200354X012
4200 Transmitters
March 2011
20
Table 8. Transmitter and Position Switch Conditions (also see figure 7)
FOR ROTARY ACTUATORS
Type
Transmitter
Action
Actuator Style
Actuator Stem Travel
Input Potentiometer
Rotation
(1)
Transmitter
Current Output,
Milliampere
Set Position Switch
4210
Direct
A,D
Down
CW
20
Hi
Up
CCW
4
Lo
B,C
Up
CW
20
Hi
Down
CCW
4
Lo
Reverse
A,D
Up
CCW
20
Hi
Down
CW
4
Lo
B,C
Down
CCW
20
Hi
Up
CW
4
Lo
4212
Direct
A,D
Down
CW
N/A
Hi
Up
CCW
Lo
B,C
Up
CW
Hi
Down
CCW
Lo
Reverse
Not available for position switches without transmitter
4215
Direct
A,D
Down
CW
20
Hi
Up
CCW
4
Lo
B,C
Up
CW
20
Hi
Down
CCW
4
Lo
Reverse
A,D
Down
CW
4
Hi
Up
CCW
20
Lo
B,C
Up
CW
4
Hi
Down
CCW
20
Lo
4211
Not required for transmitter without position switches
FOR SLIDING‐STEM ACTUATORS
4210
4220
Direct
- - -
Down
CW
20
Hi
Up
CCW
4
Lo
Reverse
- - -
Up
CCW
20
Hi
Down
CW
4
Lo
4212
4222
Direct
- - -
Down
CW
N/A
Hi
Up
CCW
N/A
Lo
Reverse
Not available for position switches without transmitter
4215
Direct
- - -
Down
CW
20
Hi
Up
CCW
4
Lo
Reverse
- - -
Down
CW
20
Hi
Up
CCW
4
Lo
4211,4221
Not required for transmitter without position switches
1. Viewed from the potentiometer shaft end.
Test Equipment Required
The following test equipment is used in the calibration and maintenance of the instrument:
D
Digital voltmeter (DVM) that measures voltages in the range of 0 to 30 volts DC with an accuracy of
±
0.25 percent.
D
Power supply capable of supplying 20 to 30 volts DC at 100 mA.
D
Resistor, 250 ohms, 0.1%, 0.5 watt or greater.