Instruction Manual
D200149X012
3610J and 3620J Positioners
September 2017
62
Loop Schematics
Figure 31. CSA Loop Schematic for Fisher 3622 (Installation Drawing GE28591)
GE28591
NOTES:
1. BARRIERS MUST BE CSA CERTIFIED WITH ENTITY PARAMETERS
AND ARE TO BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURER'S I.S. INSTALLATION INSTRUCTIONS.
2. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE
CANADIAN ELECTRICAL CODE, PART I.
3. FOR ENTITY INSTALLATION (I.S. AND N.I.): Vmax > Voc, Imax > Isc,
Ci + Ccable < Ca, Li + Lcable < La.