Type 846 and Model 3311
Instruction Manual
Form 5739
February 2002
3–2
Table 3-1 Type 846 and Model 3311 I/P Rangeability Matrix
Input
Output Pressure Range (psi) (Performance Code)
Input
Range
Common Ranges
Misc.
Std. Split
High Range Splits
3–15
(S,M)
.5–30
(M)
3–27
(M)
6–30
(M)
5–25
(M)
0.5–6
(S,M)
.5–18
(S,M)
3–9
(S,M)
9–15
(S,M)
.5–15
(S,M)
15–30
(M)
15–27
(M)
6–18
(S,M)
18–30
(M)
5–15
(S,M)
15–25
(M)
4–20
n
n
n
n
n
D
n
D
D
n
U
U
n
U
n
U
4–12
12–20
n
n
n
n
J
n
J
n
J
D
D
n
J
D
D
D
D
n
J
U
n
U
n
n
n
U
n
n
n
U
n
4–8
8–12
12–16
16–20
n
n
J
J
n
n
J
J
n
n
J
J
n
n
n
J
n
n
J
J
n
n
J
J
10–50
Consult I/P Marketing
S=Standard Performance Unit
M=Multirange Performance Unit
n
=Available in Direct or Reverse Action
D=Available in Direct Action Only
J=Available, but if the desired calibration cannot be achieved by adjusting the zero/span screws, unit may require Hi/Lo jumper to be moved. The jumper is located on the circuit board
assembly, and is usually in the Hi position. Disengaging the master module and moving the jumper to the Lo position will allow calibration to the desired range.
U=Special Build Required.
Assembly in Section 6 for an explanation of how to
engage the module final assembly.
5. Connect the air supply to the air supply port.
6. Connect a precision output indicator to the output
signal port.
7. Make sure that the output gauge port has an
output gauge or a threaded plug installed. A
threaded plug is provided for units shipped without
output gauges.
8. Remove the terminal compartment cover.
9. Connect the current source (or voltage source)
positive lead (+) to the terminal block positive (+)
and the current source (250-ohm resistor lead)
negative lead (–) to the terminal block negative (–).
Refer to figure 3-1.
CAUTION
Excessive current can damage the
transducer. Do not connect an input
current of more than 100 mA to the
transducer.
10. Apply a 4.0 mA (V
m
= 1.0 V) signal, and adjust
the zero screw to achieve a 0.2 bar (3.0 psi) output.
The output increases with clockwise rotation of the
zero screw.
11. Apply a 20.0 mA (V
m
= 5.0 V) signal, and adjust
the span screw to achieve a 1.0 bar (15.0 psi)
output. The output increases with clockwise rotation
of the span screw.
12. Repeat Steps 10 and 11 to verify and complete
the calibration.
Multirange Performance: Full Range
Input,
(2)
Direct Action
Use the following procedure with a multirange
performance unit to achieve the desired direct action
output span for a 4 to 20 mA input signal:
1. Perform steps 1 through 9 of the calibration
procedure for Standard Performance: Full Range
Input, Direct Action.
2. Apply a 4.0 mA (V
m
= 1.0 V) signal, and adjust
the zero screw to achieve the desired lower limit of
the output range. The lower limit must be between
0.03 and 0.6 bar (0.5 and 9.0 psi). The output
increases with clockwise rotation of the zero screw.
3. Apply a 20.0 mA (V
m
= 5.0 V) signal, and adjust
the span screw to achieve the desired upper limit of
the output range. The span must be at least 0.4 bar
(6.0 psi). The maximum upper limit is 2.0 bar (30.0
psi). The output increases with clockwise rotation of
the span screw.
4. Repeat steps 2 and 3 to verify and complete the
calibration.
2. Consult factory for calibration of multirange performance units with split range
input.
Содержание Fisher 3311
Страница 8: ...Type 846 and Model 3311 Instruction Manual Form 5739 February 2002 1 8 ...
Страница 22: ...Type 846 and Model 3311 Instruction Manual Form 5739 February 2002 3 6 ...
Страница 41: ...Parts List Instruction Manual Form 5739 February 2002 7 3 Figure 7 1 Exploded Parts Drawing continued B2468 IL ...
Страница 44: ...Type 846 and Model 3311 Instruction Manual Form 5739 February 2002 8 2 FM Schematics 13B8780 C doc ...
Страница 47: ......