Emerson FB3000 RTU Instruction Manual
D301851X012
May 2022
Service and Troubleshooting
77
Figure 5-13: Firmware Update Dialog Box
8.
Select the checkbox in the Selected column to choose the firmware. If you are
downloading the same version that is already installed on the device, select
Download selected packages even if they are unchanged. If you want to update
the RTU’s clock so that it agrees with your PC clock, click Time Sync device after
the download.
9.
Click Start to begin the firmware download. Allow the download to proceed to
completion. If you choose to cancel the firmware download before it completes,
the system restores the current version already in the device. The firmware
upgrade results in a warm start of the running application.
5.9
Backing Up Historical Data and Your
Configuration
DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-
hazardous. Performing this operation in a hazardous area could result in an explosion.
Important
While this procedure includes instructions to back up historical data to a PC, there is no
mechanism for restoring the historical data to the RTU. The backup is so you can
preserve the data for auditing or other purposes.
Содержание FB3000
Страница 7: ...FB3000 CSA Approval Information CD9411L Issued March 11 2021 CSA 5 ...
Страница 8: ......
Страница 12: ......
Страница 46: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 34 Installation ...
Страница 68: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 56 I O Configuration and Wiring ...
Страница 72: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 60 Operation ...
Страница 94: ......