background image

2000 and 2500 Series

2

Specifications

The Specifications section lists the specifications for the 2000 and 2500 Series. Specification is stamped on the 

nameplate attached to the emergency relief vent. Refer to Product Identification and Marking section for the 

nameplate details.

Connection Sizes Available

  See Table 1

Pressure Ranges

(1)(2)

2000 Series:

2.0 to 32.0 oz./sq. in.  

(0.5 oz./sq. in. increments)  

3.5 to 55.0 in. w.c. 

(1.0 in. w.c. increments) 

8.6 to 138 mbar 

(2.2 mbar increments)

2500 Series:

4.0. to 16.0 oz./sq. in.  

(0.5 oz./sq. in. increments) 

7.0 to 27.0 in. w.c. 

(0.5 in. w.c. increments) 

17.4 to 67.2 mbar 

(2.2 mbar increments)

Vacuum Pressure Ranges

(1)

 (2500 Series)

0.5, 0.75, 1 and 2 oz./sq. in.

Construction Materials

2000 Series

Base and Arm:

 Carbon Steel, 304 Stainless steel 

and 316 Stainless steel

Disk and Seal Support:

 Aluminum,  

304 Stainless steel and 316 Stainless steel

Seal:

 Buna-N, FEP Teflon

®

 and Viton

®

2500 Series

Base, Arm and Hood:

 Carbon steel,  

304 Stainless steel and 316 Stainless steel

Disk and Seal Support

: Aluminum and 

316 Stainless steel 

Seal:

 FEP Teflon

®

, Viton

®

 and Buna-N

Vacuum Spring:

 302 Stainless steel

Vacuum Pallet and Vacuum Seat:

 Polyphenylene 

Sulfide and 316 Stainless steel

1. The pressure limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.

Figure 4. 

Product Identification and Marking

Teflon

®

 and Viton

®

 are marks owned by E. I. du Pont de Nemours and Company.

SERIES

MODEL

CONNECTION SIZE

ANSI

API

2000 Series

Emergency Pressure Relief -  

For Pressure Relief Only

2004

4 in.

- - - -

2008

8 in.

8 in.

2012

12 in.

- - - -

2016

16 in.

- - - -

2018

18 in.

- - - -

2020

20 in.

20 in.

2024

24 in.

24 in.

2500 Series

Emergency Pressure Relief Vent  

with Vacuum -

For Pressure and Vacuum Relief

2516

16 in.

- - - - 

2520

20 in.

20 in.

2524

24 in.

24 in.

Table 1. 

Connection sizes and Model Number

HAZARDOUS LOCATION

OUTER HOUSING OF UNCOATED ALUMINUM 

II 2 G c T6

OUTER HOUSING OF STAINLESS STEEL, 

CARBON STEEL OR COATED ALUMINUM 

II 1 G c T6

SMART WIRELESS ID MARKING 

(2000 SERIES MODELS ONLY)

  II 1 G c T5

Ex ia IIC T5 Ga

Содержание Enardo 2000 Series

Страница 1: ...and Emerson Process Management Regulator Technologies Tulsa LLC EmersonTM instructions Failure to correct trouble could result in a hazardous condition Call a qualified service person to service the unit Installation operation and maintenance procedures performed by unqualified person may result in improper adjustment and unsafe operation Either condition may result in equipment damage or personal...

Страница 2: ... Base Arm and Hood Carbon steel 304 Stainless steel and 316 Stainless steel Disk and Seal Support Aluminum and 316 Stainless steel Seal FEP Teflon Viton and Buna N Vacuum Spring 302 Stainless steel Vacuum Pallet and Vacuum Seat Polyphenylene Sulfide and 316 Stainless steel 1 The pressure limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded Figure ...

Страница 3: ...eplate attached to the relief valve Model number Flange size and rating Serial number Tag number Notified body number Category number year certificate number pressure setting and flow rate and vacuum setting and flow rate Teflon and Viton are marks owned by E I du Pont de Nemours and Company Figure 5 Emergency Pressure Relief Vent Model Number 2500 Series 2 5 Connection Size 16 20 and 24 in Base A...

Страница 4: ...y lifts breaking the seal between the seat and seal portion of the lid assembly This allows vapors to pass through the vent orifice and relieve pressure build up The vent reseals upon relief and remains sealed It is important to note that relieving vapors near the set pressure in a continuous manner may cause the lid assembly to flutter or oscillate This is a common occurrence in products of this ...

Страница 5: ...r networking technology is based on the Highly Addressable Remote Transducer HART protocol It is the most widely used wireless networking standard used today and for this reason the 2000 Series has been designed to integrate with it As long as the wireless gateway is WirelessHART it will receive the Open or Closed signal from the device The WirelessHART gateway will then send the information to a ...

Страница 6: ... with bolt pattern of the vent The attachment flange base should be at level surface 2 Carefully remove the 2000 and 2500 Series from its crate The seal portion of the vents is delicate protect this surface while handling the unit 3 Place the appropriate gasket on the level attachment flange and center the vent into place 4 Insert the appropriate number of bolts and make sure the vent is fastened ...

Страница 7: ...rom the vent if opened under pressure Follow the instruction below for the preventive maintenance of the 2000 and 2500 Series 2 Inspect and clear away any debris or buildup that may cause the vent to become lodged or impede air flow through the unit Do not adjust the height of the installed spring Clean the internal components with a suitable solvent and non abrasive cloth 4 Clear away any debris ...

Страница 8: ...ement Regulator Technologies Tulsa LLC 9932 East 58th Street Tulsa OK 74146 6411 Tel 1 918 662 6161 Fax 1 918 662 0004 For further information visit www enardo com Remote Monitoring Maintenance 1 Maintain Smart Wireless Model 2000 EPRV s in the same way as all standard EPRV s 2 Take certain precautions when cleaning the transmitter The surface resistivity of the antenna assembly is greater than 1 ...