XWi70K

 

2/15 

 

NOTE: 

-

 

All configured fans must have a valid Modbus address 

-

 

The internal logic controls the available fans in parallel mode: all (configured) fans will receive 
the same speed command. 

-

 

Set 

S00=0

 to disable condenser fans controlled via Modbus 

6

 

EVAPORATOR FAN CONTROL 

The evaporator fan control mode is selected by means of the 

FnC

 parameter: 

FnC = C_n:

  fans will switch ON and OFF with the compressor and

 not run

 during defrost; 

FnC = o_n:

  fans will run even if the compressor is off, and not run during defrost; 

After defrost, there is a timed fan delay allowing for drip time, set by means of the 

Fnd

 parameter. 

FnC = C_Y:

   fans will switch ON and OFF with the compressor and 

run

 during defrost; 

FnC = o_Y:

  fans will run continuously also during defrost. 

 
The par. 

FAP

 is used to select which temperature probe will be used from the evaporator fan regulator. 

A specific setpoint (par. 

FSt

) provides the temperature value, detected by the evaporator probe, above 

which the fans are always OFF. This is used to make sure circulation of air only if his temperature is 

lower than set in 

FSt-HYF

6.1

 

FORCED ACTIVATION FOR EVAPORATOR FANS 

This function, managed by the 

FCt

  parameter, is designed to  avoid short cycles  of fans, that could 

happen when the controller is switched on or after a defrost, when the room air warms the evaporator.  
If the difference between the evaporator temperature and the room temperature is higher than the 

FCt

 

value, the controller will activate the fans. This function is disabled if 

FCt=0

6.2

 

CYCLIC ACTIVATION OF THE FANS WHEN THE COMPRESSOR IS OFF 

When 

FnC=C-n

 or 

C-Y

 (fans in parallel to the compressor), the fans will be able to carry out on and off 

cycles even if the compressor is switched off. The on and off interval of time follow the 

Fon

 and 

FoF

 

parameters. When the compressor is stopped, the fans will go on working for the 

Fon

 time. On the other 

side, with 

Fon=0

 the fans will stay always off when the compressor is off. 

7

 

CONDENSER FAN CONTROL 

The condenser fan control mode is selected by means of the 

FCC

 parameter: 

FCC = C_n:

  fans will switch ON and OFF with the compressor and

 not run

 during defrost; 

FCC = o_n:

  fans will run even if the compressor is off, and not run during defrost; 

FCC = C_Y:

  fans will switch ON and OFF with the compressor and 

run

 during defrost; 

FCC = o_Y:

  fans will run continuously also during defrost. 

 
The par. 

FAC

 is used to select which temperature probe will be used from the condenser fan regulator. 

This regulator uses a specific setpoint (par. 

St2

) and differential (par. 

HY2

) to activate and deactivate 

the condenser fans:  

-

 

If 

T>St2+HY2

 the condenser fans are activated 

-

 

If 

T<St2

 the condenser fans are deactivated. 

 

The par. 

FCo

 can be used to keep the ventilators active for a period after compressor OFF. 

7.1

 

MODBUS CONFIGURATION 

In case of fan controlled via Modbus, the following parameters need to be properly configured: 

CMi:

 minimum speed in percentage 

CMA:

 maximum speed in percentage 

CSS:

 safety speed in case of any communication od regulation error 

8

 

AUXILIARY REGULATORS 

Up to 2 auxiliary regulators can be used. Both can be linked: 

-

 

To a digital output (relay) for ONOFF regulation 

-

 

To an analogue output for proportional regulation 

 
The parameters used to configure the auxiliary regulators are the following: 
 

ACH 

Type of action for auxiliary regulator 

SAA 

Set point for auxiliary regulator 

SHY 

Differential for auxiliary regulator 

ArP 

Probe selection for auxiliary regulator 

Sdd 

Auxiliary regulator disabled during any defrost 

A2C 

Type of action for auxiliary regulator 2 

SA2 

Set point for auxiliary regulator 2 

SH2 

Differential for auxiliary regulator 2 

Ar2 

Probe selection for auxiliary regulator 2 

Sd2 

Auxiliary regulator 2 disabled during any defrost 

9

 

ANALOGUE OUTPUTS 

The  controller  is  equipped  with  2  configurable  analogue  outputs,  type  4-20mA  or  0-10Vdc  (both 
selectable). It is possible to use them for proportional regulation of: 

-

 

Evaporator fan speed 

-

 

Condenser fan speed 

Or as proportional output linked to the: 

-

 

Auxiliary regulator 1 (linked only to analogue output 1) 

-

 

Auxiliary regulator 2 (linked only to analogue output 2) 

The parameters used to configure the analogue outputs are the following: 
 

1An 

Type of analogue output 1 (4,20mA or 0-10Vdc) 

1oL 

Minimum value for analogue output 1 (in percentage) 

1oH 

Maximum value for analogue output 1 (in percentage) 

1At 

Start-up time with analogue output 1 at 100% 

2An 

Type of analogue 2 output (4,20mA or 0-10Vdc) 

2oL 

Minimum value for analogue output 2 (in percentage) 

2oH 

Maximum value for analogue output 2 (in percentage) 

2At 

Start-up time with analogue output 2 at 100% 

10

 

VARIABLE SPEED DRIVE CONTROL 

10.1

 

FREQUENCY MODE 

The controller can drive variable speed drives with frequency control input. The frequency output port 
can issue a frequency signal from 0 to 200Hz, duty cycle=50%. A special cable must be used to connect 
the frequency output of the controller to the frequency input of the specific inverter. 
 

-

 

CAB/EMB2: cable 

DD900002 20

 for Embraco models 

-

 

CAB/SE1: cable 

DD900002 21

 for SECOP NLV models 

 

NOTE:

  

-

 

An inverter compressor is totally controlled from the frequency output. 

-

 

Due to maximum current value of the frequency driver, 

only one compressor can be connected 

when frequency mode is used

10.1.1

 

CABLES FOR FREQUENCY MODE CONTROL 

EM

B

R

A

C

O

 

 

GRAY 

 GND (-) 

PINK 

  FREQ (+) 

SE

C

OP

 

 

R-  

 GND 

R+ 

 FREQ 

10.2

 

SERIAL MODE CONTROL 

The controller can drive variable speed compressors with serial control input. The speed command will 

use RPM’s (from 0 to 4500rpm) instead of values in Hertz. A

 special cable must be used to connect the 

serial port of the controller to the serial port of the relative inverter. 

-

 

CAB/EMB 1.5MT: cable 

DD190001 51

 for Embraco models 

-

 

CAB/SE2 1.5MT: cable 

DD190001 52

 for SECOP NLV models 

10.2.1

 

CABLES FOR SERIAL MODE CONTROL 

EM

B

R

A

C

O

 

 

SE

C

OP

 

 

10.3

 

PARAMETERS 

The regulation  band is from 

SET

 to 

SET+HY+HY1

. When the regulation is running, the compressor 

speed is continuously calculated and updated by the PI regulator. 
I case of regulation probe error, the compressor speed will be set to the value of par. 

SPi

It is possible to enable a cyclic or a continuous mode operation both during normal mode and energy 
saving mode: 

-

 

CMn, CME = Y

: after reaching the SETPOINT the VSC will keep on running 

-

 

CMn, CME = n

: after reaching the SETPOINT the VSC will be stopped 

10.4

 

HOT GAS DEFROST 

If hot-gas defrost is selected, it will be possible to set the compressor speed by using par. 

Aod

10.5

 

PULL DOWN 

An automatic function named PULL DOWN is implemented. This function forces the controller to work 
at 

FMA

 until reaching a specific SETPOINT (par. 

CCS

) for a maximum interval of time (par. 

CCt

). The 

PULL DOWN function is activated: 

-

 

At  start-up  if  the  temperature  measured  from  the  regulation  probe  is  higher  than  the 

SET+HY+HY1

 

-

 

After any defrost 

-

 

If the temperature measured from regulation probe go over the 

SET+HY+HY1+oHt

 value. 

If one of the above conditions happens, the controller will maintain the maximum compressor speed 
(

FMA

) until reaching the 

CCS

 setpoint. The maximum interval of time for any PULL DOWN is defined 

from par. 

CCt

. At the end of any PULL DOWN it is possible to set an interval of time (par. 

t1F

) with 

predefined compressor speed (

FMi

). 

10.6

 

OIL MIGRATION CONTROL (VALID ONLY FOR VSD) 

To avoid oil migration during variable speed compressor operation, a lubrication control is implemented. 
If the compressor works with a speed lower than the 

MnP

 threshold for 

tMi

 time, then the compressor 

speed will be increased to 

FMA

 for 

tMA

 time. 

NOTES: 

-

 

MnP= FMi to FMA, nu, OFF 

-

 

If 

MnP=nu

, then this function is disabled 

Содержание Dixell XWi70K

Страница 1: ... delay AC1 is always respected The second compressor is deactivated when T SET HY With parameter rCC it is possible to enable the compressor rotation function the activation of the first and the second compressor will be alternated to equalize the number of working hours of both of them In case of hot gas defrost operation it is possible to select if one or both compressors will be used 3 2 PULL D...

Страница 2: ... for auxiliary regulator 2 Sd2 Auxiliary regulator 2 disabled during any defrost 9 ANALOGUE OUTPUTS The controller is equipped with 2 configurable analogue outputs type 4 20mA or 0 10Vdc both selectable It is possible to use them for proportional regulation of Evaporator fan speed Condenser fan speed Or as proportional output linked to the Auxiliary regulator 1 linked only to analogue output 1 Aux...

Страница 3: ... manually by the user 11 7 DEAD BAND oAx db By setting oAx db the controller will perform a dead band regulation The heating element has to be connected to the correspondent relay If the temperature increases and reaches set point plus differential HY the compressor is started and then turned off when the temperature reaches the set point value again If the temperature decreases and reaches the se...

Страница 4: ...accessible parameters under a specific menu operate as follows 1 Enter the Programming mode by pressing the SET DOWN key for 3 seconds 2 The display will show the first menu available under Pr1 level 14 4 HOW TO ENTER PARAMETER PROGRAMMING MENU PR2 In the PR2 level there are all the parameters of the instrument 14 4 1 ENTERING THE PARAMETER PROGRAMMING MENU PR2 1 Enter the Programming mode by pres...

Страница 5: ... control ON in normal mode n Y Y VSC is never stopped during regulation CME Continuous control ON in energy saving mode n Y Y VSC is never stopped during regulation MnP Compressor speed threshold to activate lubrication valid for variable speed compressors only 0 disabled nu 1 to 100 OFF nu not used 1 to 100 select the percentage to activate function OFF compressor is stopped when the condition is...

Страница 6: ...tput value at the end of the scale 2At Interval of time with analogue output 2 maximum value 0 to 255 sec analogue output is forced at 100 after any activation for 2At seconds ALARM MENU ALr ALP Probe selection for temperature alarms nP P1 P2 P3 P4 nP no probe Px probe x Note P4 Probe on Hot Key plug ALC Temperature alarm configuration Ab rE Ab absolute rE relative ALU High temperature alarm when ...

Страница 7: ...mable defrost cycles during any ddx day Example when Ld2 12 4 the second defrost starts at 12 40 am during working days N B To disable a defrost cycle set it to nu not used Ex if Ld6 nu the sixth defrost cycle will be disabled SERIAL COMMUNICATION CoM Adr Serial address 1 to 247 device address for Modbus communication bAU Baudrate 9 6 19 2 select the correct baudrate for serial communication USER ...

Страница 8: ...automatically downloaded into the Controller memory The doL message will blink followed a by a flashing End label 4 After 10 seconds the instrument will restart working with the new parameters 5 Remove the HOT KEY NOTE the message Err is displayed for failed programming In this case turn the unit off and then on if you want to restart the download again or remove the HOT KEY to abort the operation...

Страница 9: ...t Maximum duration for Pull Down 04 00 Pr1 hour CCS Pull Down phase differential SET CCS or SET HES CCS 1 Pr1 F oHt Threshold for automatic activation of Pull Down in normal mode SET HY oHt 10 Pr1 F Con Compressor ON time with faulty probe 30 Pr1 min CoF Compressor OFF time with faulty probe 10 Pr1 min PbC Probe selection ntC Pr2 ot Probe P1 calibration 0 Pr1 F P2P Probe P2 presence yes Pr1 oE Pro...

Страница 10: ...r2 C ndE Number of connected controllers for random refrost Syd rnd 1 Pr2 FAP Probe selection for evaporator fan P3 Pr1 FSt Evaporator fan stop temperature 50 Pr1 F HyF Evaporator fan regulator differential 2 Pr1 F FnC Evaporator fan operating mode O_n Pr1 Fnd Evaporator fan delay after defrost cycle 4 Pr1 min FCt Differential temperature for cyclic activation of evaporator fans 0 disabled 0 Pr1 F...

Страница 11: ...ential in energy saving 1 Pr1 F ESt Energy saving timeout 24 Pr1 hour LdE Energy saving controls the lights lights OFF when energy saving goes active no Pr1 LHt Maximum duration for light output on 0 Pr1 min HUr Hours Pr1 Min Minutes Pr1 dAy Day of the week Pr1 dyM Day of the month Pr1 Mon Month Pr1 yAr Year Pr1 Hd1 First day of weekend nu Pr1 Hd2 2nd day of weekend nu Pr1 iLE Energy saving cycle ...

Страница 12: ...r max interval for output variation 30 Pr2 sec tLv_nt PI regulator min interval for output variation 10 Pr2 sec rSr_nt PI regulator range for output value calculation RPM 10 90 Pr2 RPM 10 Str_nt PI regulator delay before range drift 60 Pr2 sec dPt_nt PI regulator divisor for PI response time reduction acts on both par tSt and iSt 1 Pr2 CMn_nt Continuous control ON in normal mode yes Pr2 CME_nt Con...

Страница 13: ...Interval of time with analogue output 1 maximum value 5 Pr1 sec 2An_nt Type of analogue output 2 Vlt Pr1 2oL_nt Minimum value for analogue output 2 5 Pr1 2oH_nt Maximum value for analogue output 2 100 Pr1 2At_nt Interval of time with analogue output 2 maximum value 5 Pr1 sec ALP_nt Probe selection for temperature alarms nP Pr1 ALC_nt Temperature alarms configuration relative absolute Ab Pr1 ALU_nt...

Страница 14: ...no Pr1 dd7_nt Saturday defrost no Pr1 Ld1_nt 1st defrost starting time nu Pr1 hour Ld2_nt 2nd defrost starting time nu Pr1 hour Ld3_nt 3rd defrost starting time nu Pr1 hour Ld4_nt 4th defrost starting time nu Pr1 hour Ld5_nt 5th defrost starting time nu Pr1 hour Ld6_nt 6th defrost starting time 12 00 Pr1 hour Adr_nt Serial address 1 Pr1 bAU_nt Baudrate 9 6 Pr1 brd_nt Type of keyboard lock UnL Pr2 ...

Страница 15: ...ac 30K cycles Motor load 2HP 12FLA 72LRA 230Vac 30K cycles Motor load 1HP 16FLA 96LRA 110Vac 30K cycles Motor load 4 9FLA 29 4LRA 110 230Vac 30K cycles 14 8 A 230Vac 30K cycles oA2 SPST 16A 250VAC Resistive load 10A 230 Vac 30K cycles 14A NO 230Vac 50K cycles oA3 SPST 8A 250VAC Resistive load 10A 110 230Vac 30K cycles Motor load 1 2HP 230Vac 30K cycles Motor load 4 9FLA 29 4LRA NO 110 230Vac 30K c...