Higher voltage of the jump window.
Min.
Sup.Min.Lim.1
Max.
Sup.Min.Lim.2
Def. 30%
(this parameter is visualized only if “Suppress.1” is ON)
The functions “
Suppress.2
” and “
Suppress.3
” with corresponding limits operate alike the “
Suppress 1
” and are
prioritary functions on any operating cycle.
15.3
RELAY
SETTINGS
Enables the internal relay based on the following settings:
Default (Def.)
: enabled relay in a condition of regular operating, disabled
relay in emergency case (see Diagnosis on page 24).
Manual
: enabled relay above the value
Max.Lim.Rel.1
and disable under the
value
Min.lim.rel.1
.
Clock
[OPTIONAL]:
Enabled relay between the intervals of the clock timer
Value of pressure/temperature under which the relay is disabled.
This parameter is visualized only when “
Relay1
” is set on “
Manual
”.
Value of pressure/temperature above which the relay is enabled.
This parameter is visualized only when “
Relay1
” is set on “
Manual
”
[WITH S1 CARD]
The functions “
Relay 2
” and “
Relay 3
” with the corresponding limits operate alike the “
Relay 1
”. With manual
operation ON the relays exchange with reference to the signal of the priority probe except when the setting
“PRIORITY IN. [BS] = independent” is ON. In this case the Relay 1 makes reference to the analogical input 1and the
Relays 2 and 3 to the analogical input 2.
15.4
MODBUS
SETTINGS
Defines the ModbusRTU address of the adjuster. It can go from 1 to 247.
Def. 1
1
MB ADDRESS
[MB]
25
MAX.LIM.REL. 1
[IR]
bar
20
MIN.LIM.REL. 1
[IR]
bar
default
RELAY 1
[IR]
*
30
SUP.MAX.LIM.1
[IM]
%