background image

 

1592002510 XT11S GB-IT r1 0 05 05 2015  

XT11S 

1/1 

XT11S 

Electronic Digital Thermometer with 

maximum / minimum temperature log 

1.

 

GENERAL WARNING 

 PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and shall be kept near the 

device for easy and quick reference. 

 

Check the application limits before proceeding. 

 

Dixell Srl reserves the right to change the composition of its 

products, even without notice, ensuring the same and unchanged 

functionality. 

SAFETY PRECAUTIONS 

 

WARNING: this equipment should be installed, adjusted and 

serviced by qualified electrical maintenance personnel familiar 

with the construction and operation of the equipment and the 

hazards involved. Failure to observe this precaution could result 

in bodily injuries. 

 

Dixell is not responsible for any impairment or damage 

caused by the product if used in a not specified manner.  

 

Always ensure that the probe is connected to the instrument 

before the power supply is connected and turned ON. 

 

Check the supply voltage is correct before connecting the 

instrument. 

 

The probe is under NO extra low safety voltage for models 

with 230V or 110V power supply. 

 

For the model at 230V or 110V a double insulation probe has to 

be used, NOT SUPPLIED. 

 

Use insulated quick connector terminals for voltage and probe. 

 

The instrument is designed for panel mounting and electrical 

connections must be positioned inside a properly protected 

board/panel. 

 

Do not expose to water or moisture: use the instrument only within 

the operating limits avoiding sudden temperature changes with 

high atmospheric humidity to prevent condense formation. 

 

Warning: disconnect all electrical connections before any kind of 

maintenance. 

 

The instrument shall never be opened. 

 

In case of failure or faulty operation send the instrument back to 

the retailer or to “Dixell S.r.l.” (see address) with a detailed 

description of the fault. 

 

Assure that the wires for probes and for power supply are 

separated and far enough from each other, without crossings and 

spirals. 

 

To see the max and minimum recorded temperatures, use a S1 

Class II approved push button, normally open, connected as 

indicated in par. 5. 

2.

 

GENERAL DESCRIPTION 

The XT11S is a new electronic digital thermometer which displays 

the current temperature and also logs the maximum and minimum 

temperatures experienced. 

These max. / min. temperatures can be displayed at the touch of a 

button and reset if required. 

3.

 

INSTALLATION - 230V OR 115V VERSION  (FIG.1) 

The instrument is equipped with fast-on type spade terminals with 

probe connections separated from the power supply connections. To 

install the instrument proceed as follow

  Use insulated quick connector terminals for voltage and 

probe. 

Probe

input

Power Supply

Line

(N)

 (L)

(N)                  (L)

P1

N

T

C

 

Fig.1 

 

1.

 

Make a 59x25,5 mm (1.01x2.32 inch) hole in a panel with a 

thickness between 0.8mm and 2.7mm. 

2.

 

Take the instrument from the box and place it in the hole until 

the side flaps click, which means they are locked. 

3.

 

 Disconnect the power supply from the board by 

means of a panel switch, not supplied, (P1 in Fig.1).  

4.

 

 A Class II and certified according to IEC 60947-1 and 

60947-3 approved  panel switch has to be used. 

5.

 

 Fit the panel switch near the XT11S, in a place easy to 

reach, to make the power supply disconnection easy. 

6.

 

Place the probe where it has to measure the temperature. 

7.

 

Connect the probe terminals to the 2.8mm. fast-on as 

indicated. 

8.

 

For supply use double insulation cables, with at least 0.75 mm² 

as diameter.( AWG minus or equal to 20.) 

9.

 

To protect the instrument against over current a 63mA 

external fuse has to be used. 

10.

 

Connect the power supply cables to the 6.3mm. fast-on. 

11.

 

If possible, the manufacturer suggests connecting the phase 

(L) to the fast-on on the right and neutral (N) to the fast-on on 

the left as indicated. 

12.

 

At this stage the board can be connected to the power supply 

once more. 

4.

 

DISPLAY OFFSET ADJUSTMENT 

1.

 

It’s possible to adjust the display visualisation in the range –

10÷10°C, in case of wrong read-out of the probe. 

2.

 

To do it, use a 3mm screwdriver to rotate the potentiometer 

till the thermometer display the right temperature.  

5.

 

DISCONNECTION AND PROBE SUBSTITUTION      

(FIG.1) 

1.

 

 Disconnect the power supply on the board where the 

instrument is positioned, by means of the panel switch (P1 

in Fig.1) 

2.

 

Remove the power supply fast-ons.

 

3.

 

Disconnect the instrument and the probe.

 

6.

 

EXTERNAL PUSH-BUTTON CONNECTION (FIG.2) 

In order to display the maximum and minimum values on the 

instrument, use the S1 Class II approved type push button, normally 

open. Button has to be rated for the maximum main supply voltage.  

(NOT SUPPLIED). 
1.

 

 Disconnect the power supply on the board where the 

instrument is positioned, by means of the panel switch (P1 

in Fig.1) 

2.

 

Connect the push button in parallel with the probe as shown in 

Fig.2. 

Probe

input

Power Supply

N

T

C

S1

0

 -

+10°C

+17°F

-10°C

-17°F

S1: external
push button

Probe

 

 

 

 

 

 

Fig.2 

 

3.

 

Place the probe where it has to measure the temperature. 

4.

 

Connect the probe terminals to the 2.8mm. fast-ons as 

indicated. 

5.

 

For supply use double insulation cables, with at least 0.75 

mm² as diameter (AWG minus or equal to 20). 

6.

 

Connect the power supply cables to the 6.3mm. fast-ons. 

7.

 

If possible, the manufacturer suggests connecting the phase 

(L) to the fast-on on the right and neutral (N) to the fast-on on 

the left as indicated. 

8.

 

At this stage the board can be connected to the power supply 

once more. 

7.

 

DISPLAY OF MIN. AND MAX. TEMPERATURES 

LOGGED 

Once the button for min & max temperatures has been 

connected, proceed as follows: 
Maximum temperature display:  

1.  Press and hold the push button (S1) till the display reads “HI”. 

2.  Release S1 and the highest temperature recorded since the 

last reset will be displayed for 3 seconds. 

Minimum temperature display

1.  Press and hold the push button (S1) till the display reads “LO”. 

2.  Release S1 and the lowest temperature recorded since the last 

reset will be displayed for 3 seconds. 

Probe offset value display

1.  Press and hold the push button (S1) till the display reads “PO”. 

2.  Release S1 and the probe offset value will be displayed for 3 

seconds. 

Maximum /minimum temperature reset

: 

 

1.

 

Press and hold the push button (S1) till the display reads “rE”. 

2.

 

Release S1 and the display will flash “rE” for 5 seconds. 

3.

 

While the display is flashing press the push button and the 

max&min temperature will be erased. 

 

 

Power on and power failure warning:  

When the power supply is turned on and after any power failure, 

when the max. and min. set values are visualised, the display 

flashes. This is to warn the user that there has been an interruption 

to the power supply.  

To restore normal operation, follow the same procedure that is used 

for re-setting the maximum/minimum memory. (see Maximum 

/minimum temperature reset). 

8.

 

MAINTENANCE AND CLEANING 

Instruments do not require particular maintenance. To clean frontal, 

just use a soft moist cloth and avoid using any strong detergent or 

solvent. 

9.

 

TECHNICAL DATA 

Case: 64x31mm, depth: 19.5mm; self extinguishing polycarbonate. 

Mounting: only for panel mounting; 25,5x59mm panel cut out          

(1.01x2.32inc.). 

Frontal protection: IP20. 

Electrical connections:  fast-on type spade terminals with probe 

connections (2.8mm) separated from power supply 

connections (6.3mm). 

Power supply: 230Vac ±10% 50/60Hz VDE approved 

 

or 110Vac ±10% 50/60Hz, or 12Vac/dc, or 24Vac/dc. 

Absorbed current: 40mA. 

Probe: NTC with double isolation for 230Vac or 110Vac version. 

Display and measurement units:  

 

- 50.0÷99.9 °C => 100 to110°C; -40÷230 °F 

 

NTC standard probe: -30÷105°C (-22÷220°F). 

Display update delay times (optional) when the  temperature 

increases:  fixed at 1 or 3 minutes depending on model 

specified at time of order. 

Operating temperature: T60°C/32÷140°F. 

Storage temperature: -30÷75°C/-22÷167°F.  

Relative humidity: 20÷85% (no condensing). 

Maximum working height: 2000m a. s. l. 

Installation category III; Transitory over-voltage: 4000V

Pollution degree: 2 according to IEC 664

Offset:  ±10°C (±17°F). 

Accuracy: from -30 to -10°C (-22÷14°F): 1°C (2 °F) ±1 digit. 

from -10 to 110°C (14÷230°F): 0,5°C (1 °F) ±1 digit. 

 

 

 

 

 

           

 

 

 

 

 

Only for 230V 

model 

Содержание Dixell XT11S

Страница 1: ...wer supply For the model at 230V or 110V a double insulation probe has to be used NOT SUPPLIED Use insulated quick connector terminals for voltage and probe The instrument is designed for panel mounting and electrical connections must be positioned inside a properly protected board panel Do not expose to water or moisture use the instrument only within the operating limits avoiding sudden temperat...

Страница 2: ...where it has to measure the temperature 7 Connect the probe terminals to the 2 8mm fast on as indicated 8 For supply use double insulation cables with at least 0 75 mm as diameter AWG minus or equal to 20 9 To protect the instrument against over current a 63mA external fuse has to be used 10 Connect the power supply cables to the 6 3mm fast on 11 If possible the manufacturer suggests connecting th...

Страница 3: ...he fast on on the right and neutral N to the fast on on the left as indicated 8 At this stage the board can be connected to the power supply once more 7 DISPLAY OF MIN AND MAX TEMPERATURES LOGGED Once the button for min max temperatures has been connected proceed as follows Maximum temperature display 1 Press and hold the push button S1 till the display reads HI 2 Release S1 and the highest temper...

Страница 4: ...tection IP20 Electrical connections fast on type spade terminals with probe connections 2 8mm separated from power supply connections 6 3mm Power supply 230Vac 10 50 60Hz VDE approved or 110Vac 10 50 60Hz or 12Vac dc or 24Vac dc Absorbed current 40mA Probe NTC with double isolation for 230Vac or 110Vac version Display and measurement units 50 0 99 9 C 100 to110 C 40 230 F NTC standard probe 30 105...

Отзывы: