Emerson Dixell XRi77CX Скачать руководство пользователя страница 5

 

1592020670 XRi77CX-CH GB r1.1 15.10.2019

 

XRi77CX-CH

 

5/9

 

ALL 

Minimum temperature alarm:

  

If ALC=Ab: [-100°C to ALU; -148 to ALU];  
If ALC=rE: [0.0 to 50.0°C or 0 to 90°F] when this temperature is reached the alarm is 
enabled, after the Ald delay time. 

AFH 

Differential for temperature alarm recovery:

 (0.1 to 25.5°C; 1 to 45°F) intervention 

differential for recovery of temperature alarm. 

ALd    Temperature alarm delay:

 (0 to 255 min) time interval between the detection of an 

alarm condition and alarm signalling. 

dAo 

Temperature alarm delay after power-on:

 (0.0 to 24h00min, res. 10min) time interval 

between the detection of the temperature alarm condition after instrument power on 
and alarm signalling. 

CONDENSER TEMPERATURE ALARM 

AP2 

Second temperature alarm probe selection

: (nP; P1; P2; P3; P4)  

nP = no probe; P1 = thermostat probe; P2 = evaporator probe; P3 = configurable probe; 

P4 = Probe on Hot Key plug. 

AL2 

Second low temperature alarm (absolute value): 

(-100 to 150°C; -148 to 302°F) 

when this temperature is reached the LA2 alarm is signalled, possibly after the Ad2 
delay. 

Au2 

Second high temperature alarm (absolute value): 

(-100 to 150°C; -148 to 302°F) 

when this temperature is reached the HA2 alarm is signalled, possibly after the Ad2 
delay. 

AH2 

Differential for second temperature alarm recovery:

 0.1 to 25.5°C; 1 to 45°F 

Ad2 

Second temperature alarm delay:

 (0 to 255 min) time interval between the detection 

of the condenser alarm condition and alarm signalling. 

dA2 

Second temperature alarm activation delay after power-on

: 0.0 to 24h00min, res. 

10min. 

bLL 

Compressor off due to second low temperature alarm:

 (n; Y) n = compressor keeps 

on  working;  Y  =  compressor  is  switched  off  till  the  alarm  is  present,  in  any  case 
regulation restarts after AC time at minimum. 

AC2 

Compressor  off  due  to  second  high  temperature  alarm: 

(n;  Y)  n  =  compressor 

keeps on working; Y = compressor is switched off till the alarm is present, in any case 
regulation restarts after AC time at minimum. 

SAF 

Differential for anti-freezing control: 

(0.0 to 25.5°C; 1 to 45°F) low level threshold to 

stop regulation. 

CONFIGURABLE RELAYS 

oA1 

Relay oA1 configuration

 

(7-8):

 (dEF; Fan; Alr; LiG; AUS; onF; db; CP2; dEF2; HES; 

Het; inV, CMP, nu) dEF = defrost; Fan = do not select it; Alr = alarm; LiG = light; AUS 
= Auxiliary relay; onF = always on with instrument on; db = neutral zone; CP2 = second 
compressor output; dF2 = do not select it; HES = night blind; Het = heater output;  inV 
= inverter compressor; CMP = ONOFF compressor; nu=not used. 

oA2 

Relay oA2 configuration (4-5-6):

 (dEF; Fan; Alr; LiG; AUS; onF; db; CP2; dEF2; HES; 

Het; inV, CMP, nu) dEF = defrost; Fan = do not select it; Alr = alarm; LiG = light; AUS 
= Auxiliary relay; onF = always on with instrument on; db = neutral zone; CP2 = second 
compressor output; dF2 = do not select it; HES = night blind; Het = heater output;  inV 
= inverter compressor; CMP = ONOFF compressor; nu=not used. 

oA3 

Relay oA3 configuration (8-9):

 (dEF; Fan; Alr; LiG; AUS; onF; db; CP2; dEF2; HES; 

Het; inV, CMP, nu) dEF = defrost; Fan = do not select it; Alr = alarm; LiG = light; AUS 

= Auxiliary relay; onF = always on with instrument on; db = neutral zone; CP2 = second 
compressor output; dF2 = do not select it; HES = night blind; Het = heater output;  inV 
= inverter compressor; CMP = ONOFF compressor; nu=not used. 

oA4 

Relay oA4 configuration (10-11-12):

 (dEF; Fan; Alr; LiG; AUS; onF; db; CP2; dEF2; 

HES; Het; inV, CMP, nu) dEF = defrost; Fan = do not select it; Alr = alarm; LiG = light; 
AUS = Auxiliary relay; onF = always on with instrument on; db = neutral zone; CP2 = 
second compressor  output;  dF2 =  do not select it;  HES =  night blind;  Het = heater 
output;  inV = inverter compressor; CMP = ONOFF compressor; nu=not used. 

oAn 

Analogue output configuration:

 (n;Y) n = 5-pin port is used for HOT-KEY; Y = 5-pin 

port is used as frequency output. 

AoP 

Alarm relay polarity: 

(oP; CL) oP = the relay is activated by opening the contact; CL 

= the relay is activated by closing the contact. 

 

DIGITAL INPUTS 

i1P 

Digital input 1 polarity: 

(oP; CL) oP = the digital input is activated by opening the 

contact; CL = the digital input is activated by closing the contact. 

i1F 

Digital input 1 configuration:

 (EAL; bAL; dor; dEF; ES; AUS; Htr; HdF; onF; nt) EAL 

= external alarm: “EA” message is displayed; bAL

 

= serious alarm “CA” message is 

displayed; dor = door switch function; dEF = activation of a defrost cycle; ES = energy 
saving; AUS = auxiliary relay activation with oAx=AUS; Htr = type of inverting action 
(cooling or heating); HdF =do not set it; onF = to switch the controller off; nt = to change 
parameter map 

i2P 

Digital input 2 input polarity:

 (oP; CL) oP = the digital input is activated by opening 

the contact; CL = the digital input is activated by closing the contact. 

i2F   

Digital input 2 configuration: 

(EAL; bAL; dor; dEF; ES; AUS; Htr; HdF; onF; nt) EAL 

= external alarm: “EA” message is displayed; bAL

 

= serious alarm “CA” message is 

displayed; dor = door switch function; dEF = activation of a defrost cycle; ES = energy 
saving; AUS = auxiliary relay activation with oAx=AUS; Htr = type of inverting action 
(cooling or heating); HdF =do not set it; onF = to switch the controller off; nt = to change 
parameter map 

did 

Digital input 1 alarm delay:  

(0 to 255 min) delay between the detection of the external 

alarm condition and its signalling. 
When i1F= PAL, it is the interval of time to calculate the number of pressure switch 
activation. 

d2d 

Digital input 2 alarm delay: 

 (0 to 255 min) delay between the detection of the external 

alarm condition and its signalling. 
When i1F= PAL, it is the interval of time to calculate the number of pressure switch 
activation. 

nPS 

Number of pressure alarm events before stopping the regulation (Lock alarm): 

(1 to 15) after nPS activations of the ixF=BAL digital input the regulation will be stopped. 

odC 

Compressor and fan status after door opening: 

(no; Fan; CPr; F_C)  no = normal;  

Fan = normal; CPr = compressor OFF, F_C = compressor OFF. 

rrd 

Regulation  restart  after  open  door  alarm: 

(n;  Y)  n  =  outputs  follow  the  odC 

parameter. Y = outputs restart with a door open alarm.  

HES 

Differential  for  energy  saving  mode:

  (-30.0  to  30.0°C;  -54  to  54°F)  it  sets  the 

increasing value of the set point [SET+HES] during the Energy Saving cycle. 

LdE 

Energy  saving  mode  controls  the  lights  (lights  off  when  energy  saving  goes 
active): 

(n, Y) n= lights are independent from energy saving; Y = lights are turned OFF 

when energy saving mode is activated

 

CURRENT TIME AND WEEKLY HOLIDAYS (ONLY FOR MODELS WITH RTC) 

Hur 

Hours:

 0 to 23h 

Min 

Minutes:

 0 to 59min 

dAY 

Day of the week: 

Sun to Sat 

dYM 

Day of the month: 

1 to 31 

Mon 

Month:

 1 to 12 

YAr 

Year:

 0 to 99 

Hd1 

First day of weekend

: (Sun to Sat; nu) set the first day of the week which follows the 

holiday times. 

Hd2 

Second day  of  weekend

:  (Sun  to  Sat;  nu)  set  the  second  day  of  the  week  which 

follows the holiday times. 

 

N.B.   Hd1, Hd2 

can be set also as

 

“nu” 

value (Not Used).

  

ENERGY SAVING TIMES (ONLY FOR MODELS WITH RTC) 

iLE 

Working  days  Energy  saving  starting  time:

  (0  to  23h50min)  during  the  Energy 

Saving cycle the set point is increased by the value in HES so that the operation set 
point is SET+HES. 

dLE 

Working  days  Energy  saving  duration:

  (0  to  24h00min)  sets  the  duration  of  the 

Energy Saving cycle on workdays. 

iSE 

Holyday Energy saving starting time:

 0 to 23h50min. 

dSE 

Holyday Energy saving duration:

 0 to 24h00min. 

DEFROST TIMES (ONLY FOR MODELS WITH RTC) 

dd1…dd6

 

Daily defrost:

 (n; Y) to enable the 

Ld1…Ld6

 defrost operations for all the days 

of the week. 

Ld1…Ld6

 

Defrost starting time: 

(0 to 23h50min) these parameters set the beginning of 

the  6  programmable  defrost  cycles  during  workdays.  Ex:  when  Ld2=12.4  the 
second defrost starts every Monday at 12.40. 

 

N.B.: 

To disable a defrost cycle set it to “nu”(not used). 

 

Ex: 

if

 Ld6=nu

;

 

the sixth defrost cycle will 

be disabled. 

OTHER 

Adr 

Serial  address:

  (1  to  247)  identifies  the  instrument  address  when  connected  to  a 

ModBUS compatible monitoring system. 

onC 

ONOFF button configuration: 

(nu; oFF; ES) nu=not used; oFF=to switch OFF and 

ON the controller; ES=to enable and disable enersy saving mode 

on2 

ONOFF  button  timed  (3sec)  configuration: 

(nu;  oFF;  ES)  nu=not  used;  oFF=to 

switch OFF and ON the controller; ES=to enable and disable enersy saving mode

 

LG2 

Light  button  timed  (3sec)  configuration  (left  upper  side):

  (nu;  LiG;  AUS;  Lnt) 

nu=not  used;  LiG=  to  activate  and  deactivate  light  output;  AUS=to  activate  and 
deactivate the auxiliary output; Lnt=to change parameter map

 

dn2 

Down  button  timed  (3sec)  configuration

:  (nu;  Std;  Lnt;  Pnd)  nu=not  used; 

Std=standard use; Lnt= to change parameter map; Pdn=to activate a Pull Down cycle. 

dP1 

Probe P1 value visualization:

 read only 

dP2 

Probe P2 value visualization:

 read only 

dP3 

Probe P3 value visualization:

 read only

 

dP4 

Probe P4 value visualization:

 read only

 

SPd 

Instantaneous Variable Speed Drive speed (in percentage):

 read only 

rSE 

Real set point

: it shows the set point used during the energy saving cycle or during 

the continuous cycle. 

rEL 

Firmware release

 for internal use. 

Ptb 

Parameter table code

: readable only. 

14.

 

DIGITAL INPUTS  

The first digital input (terminals 18-20) is enabled with 

P3P=n

With 

P3P=n

 and 

i1F=i2F

 the second digital input is disabled. 

The free voltage digital inputs are programmable by the 

i1F

 and 

i2F

 parameters. 

14.1

 

GENERIC ALARM (IXF = EAL) 

As soon as the digital input is activated the unit will wait for 

did

 

time delay before signalling the “

EAL

” 

alarm message. The outputs status does

n’t change. The alarm stops just after the digital input is de

-

activated. 

14.2

 

SERIOUS ALARM MODE (IXF = BAL) 

When the  digital input is activated,  the  unit  will wait for 

did

 delay 

before signalling the  “

CA

”  alarm 

message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated. 

14.3

 

DOOR SWITCH INPUT (IXF = DOR) 

It signals the door status and the corresponding relay output status through the 

odC

 parameter:  

no

 = normal (any change); 

FAn

 = Fan OFF; 

CPr

 = Compressor OFF; 

F_C

 = Compressor and fan OFF. 

Since the door is opened, after the delay time set through parameter 

doA

, the door alarm is enabled, 

the display shows the message 

dA

 and the regulation restarts is

 rtr=Y

. The alarm stops as soon as 

the external digital input is disabled again. With the door open, the high and low temperature alarms 
are disabled. 

14.4

 

START DEFROST (IXF = DEF) 

It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will 
restart only if the digital input is disabled otherwise the instrument will wait until the 

MdF

 safety time is 

expired. 

Содержание Dixell XRi77CX

Страница 1: ...t RTC EdF rtC the defrost is real time controlled depending on the hours set in the parameters Ld1 Ld6 for workdays Other parameters are used to control defrosting cycles the maximum length MdF and defrosting modes timed or controlled by the evaporator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 2 1 PR...

Страница 2: ... to set the regulation HY1 Differential for proportional regulation 0 1 to 25 5 C 1 to 45 F Fr0 Frequency output value with compressor stopped 0 to 50Hz frequency output signal when compressor stopped PMi Minimum compressor speed in percentage 0 to PMA PMA Maximum compressor speed in percentage PMi to 100 voS Signal output variation increment when temperature is increasing if vdC FrE then 1 to 100...

Страница 3: ...g mode by pressing the SET DOWN buttons for 3 sec the C or F LED will start blinking 2 Browse to the required parameter and then press the SET button to display its current value 3 Use UP or DOWN buttons to change its value 4 Press SET button to store the new value and move to the following parameter To exit press SET UP buttons or wait for 15 sec without pressing any key NOTE the set value is sto...

Страница 4: ... idF is expired tdF Defrost type EL in EL electrical heater in hot gas dFP Probe selection for defrost control nP P1 P2 P3 P4 nP no probe P1 thermostat probe P2 evaporator probe P3 configurable probe P4 Probe on Hot Key plug dtE Defrost end temperature 55 to 50 C 67 to 122 F enabled only when EdF Pb sets the temperature measured by the evaporator probe which causes the end of defrost idF Interval ...

Страница 5: ... condition and its signalling When i1F PAL it is the interval of time to calculate the number of pressure switch activation d2d Digital input 2 alarm delay 0 to 255 min delay between the detection of the external alarm condition and its signalling When i1F PAL it is the interval of time to calculate the number of pressure switch activation nPS Number of pressure alarm events before stopping the re...

Страница 6: ... and then turn the Controller ON 3 The parameter list of the HOT KEY will be automatically downloaded into the Controller memory The doL message will blink followed a by a flashing End label 4 After 10 seconds the instrument will restart working with the new parameters 5 Remove the HOT KEY NOTE the message Err is displayed for failed programming In this case turn the unit off and then on if you wa...

Страница 7: ...ion for defrost control P2 Pr2 dtE Defrost termination temperature 4 0 Pr2 idF Interval between two consecutives defrost cycles 24 Pr2 MdF Maximum length for defrost 45 Pr2 dSd Start defrost delay 0 Pr2 StC Compressor stop time before starting any defrost 5 Pr2 dFd Displaying during defrost it Pr1 dAd Delay for display temperature update after any defrost 20 Pr1 Fdt Draining time 5 Pr2 Hon Drain h...

Страница 8: ...in percentage 100 Pr2 voS_nt Compressor speed variation increment when temperature is increasing 1 Pr2 vo2_nt Compressor speed variation decrement when temperature is decreasing 2 Pr2 vo3_nt Compressor speed variation decrement after any Pull Down 5 Pr2 PdP_nt Compressor speed during any Pull Down 100 Pr2 t1F_nt Time with compressor speed at PMI before stopping the compressor 1 Pr2 SPi_nt Compress...

Страница 9: ...arity CL Pr2 i2F_nt Digital input 2 configuration EAL Pr2 did_nt Digital inputs 1 alarm delay 1 Pr1 d2d_nt Digital inputs 2 alarm delay 1 Pr2 nPS_nt Number of pressure alarm switch before stopping the regulation Lock alarm 15 Pr1 OdC_nt Compressor and fan status after door opening F C Pr1 rrd_nt Regulation restart after open door alarm yes Pr1 HES_nt Differential for energy saving mode 0 Pr1 LdE_n...

Отзывы: