background image

 

1592020680 XRi60CH EN r2.0 2021.07.14

 

XRi60CH

 

2/9

 

-

 

FCC = o_n: 

fans will run even if the compressor is off, and not run during defrost 

-

 

FCC = C_Y: 

fans will switch ON and OFF with the compressor and 

run

 during defrost 

-

 

FCC = o_Y: 

fans will run continuously also during defrost 

 

The par. 

FAC

 is used to select which temperature probe will be used from the condenser fan regulator. 

This regulator uses a specific setpoint (par. 

St2

) and differential (par. 

HY2

) to activate and deactivate 

the condenser fans:  

-

 

If 

T>St2+HY2

 the condenser fans are activated 

-

 

If 

T<St2

 the condenser fans are deactivated 

 

The par. 

FCo

 can be used to keep the ventilators active for a period after compressor OFF. 

6.

 

AUXILIARY REGULATOR 

The auxiliary regulator can be be linked to a digital output (relay) for ONOFF regulation. 

The parameters used to configure the auxiliary regulators are the following: 

 

ACH 

Kind of action for auxiliary regulator 

SAA 

Set point for auxiliary regulator 

SHY 

Differential for auxiliary regulator 

ArP 

Probe selection for auxiliary regulator 

Sdd 

Auxiliary regulator disabled during any defrost 

7.

 

DUAL MAP FEATURE 

The controller is programmed with 2 different parameter maps. In this way, it is possible to choose the 

right map to meet both LT and NT applications. There are two different way to do this: 

-

 

If 

i1F=nt

, it will be possible to change the working map by using the digital input. 

-

 

By using button if it is linked to the map changing function (for example: 

d2n=Lnt

). 

8.

 

VARIABLE SPEED COMPRESSOR CONTROL 

8.1

 

FREQUENCY MODE 

The  controller  can  drive  variable  speed  compressors  with  frequency  control  input.  The  frequency 

output port can issue a frequency signal from 30 to 200Hz, duty cycle=50%. A special cable must be 

used to connect the frequency output of the controller to the frequency input of the specific inverter. 

-

 

CAB/EM1: cable 

DD900002 20

 for Embraco models 

-

 

CAB/SE1: cable 

DD900002 22

 for SECOP NLV models 

 

NOTE:

  

-

 

An inverter compressor can be completely controlled from the frequency output only. 

-

 

Only one compressor can be connected when frequency mode is used 

1.1

 

PARAMETERS 

The regulation band is from 

SET

 to 

SET+HY+HY1

. When the regulation is running, the compressor 

speed is continuously calculated and updated by the PI regulator. 

In case of regulation probe error, the compressor speed will be set to the value of par. 

SPi

It is possible to enable a cyclic or a continuous mode operation both during normal mode and energy 

saving mode: 

-

 

CMn, CME = Y

: after reaching the SETPOINT the VSC will keep on running 

-

 

CMn, CME = n

: after reaching the SETPOINT the VSC will be stopped 

1.2

 

HOT GAS DEFROST 

If hot gas defrost is selected, it will be possible to set the compressor speed by using par. 

Aod

1.3

 

PULL DOWN 

An automatic function named PULL DOWN is implemented. This function forces the controller to work 

at 

FMA

 until reaching a specific SETPOINT (par. 

CCS

) for a maximum interval of time (par. 

CCt

). The 

PULL-DOWN function is activated: 

-

 

At  start-up  if  the  temperature  measured  from  the  regulation  probe  is  higher  than  the 

SET+HY+HY1

 

-

 

After any defrost 

-

 

If the temperature measured from regulation probe go over the 

SET+HY+HY1+oHt

 value. 

If one of the above conditions happens, the controller will maintain the maximum compressor speed 

(

FMA

) until reaching the 

CCS

 setpoint. The maximum interval of time for any PULL DOWN is defined 

from par. 

CCt

8.2

 

OIL MIGRATION CONTROL (VALID ONLY FOR VSC) 

To  avoid  oil  migration  during  variable  speed  compressor  operation,  a  lubrication  control  is 

implemented. If the compressor works with a speed lower than the 

MnP

 threshold for 

tMi

 time, then 

the compressor speed will be increased to 

FMA

 for 

tMA

 time. 

NOTES: 

-

 

MnP= FMi to FMA, nu, OFF 

-

 

If 

MnP=nu

, then this function is disabled 

-

 

If 

MnP=oFF

, then the compressor will be stopped for 

tMA

 if it works continuously for 

tMi

8.3

 

PI ALGORITHM 

The VSC regulator implements a PI (Proportional-Integral) algorithm to guarantee temperature stability 

always  near  the  setpoint.  Here  below  there  are  some  advises  for  parameter  settings  in  some 

applications.  

 

 

Low Temperature Applications 

Normal Temperature Applications 

HY 

0.3 

HY1 

0.7 

tSt 

1 to 3 min 

1 to 3 min 

iSt 

10 to 20 min 

5 to 10 min 

rSr 

20 to 60 

90 to 180 

Str 

40 to 80 sec 

10 to 20 sec 

voS 

1 to 3 

3 to 5 

vo2 

3 to 7 

5 to 10 

vo3 

5 to 10 

5 to 10 

tHv 

90 to 120 sec 

20 to 30 sec 

tLv 

30 to 60 sec 

5 to 10 sec 

dPt 

2 to 4 

1 or 2 

SAt 

5 to 10 min 

1 to 3 min 

 

NOTE: 

-

 

Every application needs specific tuning tests to find the optimal values. 

-

 

Use 

HY

 

<

 

HY1

 (better if 

2*HY <= HY1

) in Low Temp Applications 

-

 

Use 

HY > HY1

 (better if 

HY >= 2*HY1

) in Normal Temp Applications 

9.

 

FRONT PANEL AND COMMANDS 

 

 

 

 

To display target set point; in programming mode it selects a parameter or confirm 

an operation. 

 

(

DEF

) To start a manual defrost. 

 

(

UP

) To see the used parameter map. When in programming mode, it browses the 

parameter codes or increases the displayed value. 

 

(

DOWN

) To see the used parameter map. When in programming mode, it browses 

the parameter codes or decreases the displayed value. 

Keep it pressed 5 sec to change parameter map from “nt” to “Lt” and vice

-versa 

(valid when button properly configured). 

 

To switch the instrument on and off (when 

onF=oFF

).  

 

To switch on and off the light (when 

oAx=LiG

). 

 

KEY COMBINATIONS: 
 

 

+

 

 

To lock & unlock the keyboard 

 +

 

 

To enter in programming mode 

 +

 

 

To exit the programming mode 

9.1

 

USE OF LEDS 

Icon functions are described in the following table: 

LED 

MODE  FUNCTION 

 

ON 

Compressor enabled 

Flashing  Anti-short cycle delay enabled 

 

ON 

Defrost enabled 

Flashing  Drip time in progress 

 

ON 

Fans enabled 

Flashing  Fans delay activation (for example after any defrost) 

 

ON 

An alarm is occurring 

 

ON 

A PULL DOWN is running 

 

 

ON 

Energy saving enabled 

 

ON 

Light on 

 

ON 

Auxiliary relay on 

,

 

ON 

Measurement unit 

Flashing  Programming phase 

10.

 

MAX & MIN TEMPERATURE MEMORIZATION 

10.1

 

HOW TO SEE THE MIN TEMPERATURE 

1.

 

Press and release the 

DOWN 

button (if properly configurated). 

2.

 

The “

Lo

” message will be displayed followed by the minimum temperature recorded.

 

3.

 

By pressing the 

DOWN

 button again or waiting for 5 sec the normal display will be restored. 

10.2

 

HOW TO SEE THE MAX TEMPERATURE 

1.

 

Press and release the 

UP 

button (if properly configurated). 

2.

 

The “

Hi

” message will be displayed followed by the maximum temperature recorded.

 

3.

 

By pressing the 

UP 

button again or waiting for 5 sec the normal display will be restored. 

10.3

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 

1.

 

Keep 

SET 

button pressed for more than 3 sec while the max or min temperature is displayed. 

(

rSt

 message will be displayed) 

2.

 

After  confirming  the  operation, 

the  “

rSt

”  message 

will  start  blinking  and  then  the  normal 

temperature will be displayed. 

Содержание Dixell XRi60CH

Страница 1: ...porator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 2 1 PRE DEFROST The par dAF enable a pre defrost phase During this interval the regulation setpoint will be moved to the value SET 1 C or SET 1 F The defrost phase starts as soon as the regulation temperature reach the pre defrost setpoint or when the...

Страница 2: ...the maximum compressor speed FMA until reaching the CCS setpoint The maximum interval of time for any PULL DOWN is defined from par CCt 8 2 OIL MIGRATION CONTROL VALID ONLY FOR VSC To avoid oil migration during variable speed compressor operation a lubrication control is implemented If the compressor works with a speed lower than the MnP threshold for tMi time then the compressor speed will be inc...

Страница 3: ...T HY1 Variable Speed Compressor Differential in normal mode 0 1 to 25 5 C 1 to 45 F odS Output activation delay at start up 0 to 255 min this function is enabled after the instrument power on and delays the output activations AC Anti short cycle delay 0 to 999 sec minimum interval between a compressor stop and the following restart AC1 Anti short cycle delay 2nd compressor 0 to 999 sec delay befor...

Страница 4: ...ating CL cooling SAA Set Point for auxiliary regulator 100 0 to 150 0 C 148 to 302 F it defines the room temperature set point to switch auxiliary relay SHY Auxiliary regulator differential 0 1 to 25 5 C 1 to 45 F differential for auxiliary output set point ACH CL AUX Cut in is SAA SHY AUX Cut out is SAA ACH Ht AUX Cut in is SAA SHY AUX Cut out is SAA ArP Probe selection for auxiliary regulator nP...

Страница 5: ...lease for internal use Ptb Parameter table code readable only 13 DIGITAL INPUTS The first digital input terminals 18 20 is enabled with P3P n The free voltage digital inputs are programmable by the i1F parameter 13 1 GENERIC ALARM i1F EAL As soon as the digital input is activated the unit will wait for did time delay before signalling the EAL alarm message The outputs status doesn t change The ala...

Страница 6: ...l operation Check connections before replacing the probe Temperature alarms HA and LA automatically stop as soon as the temperature returns to normal values Alarms EA and CA with ixF bAL PAL recover as soon as the digital input is disabled 18 3 OTHER MESSAGES Pon Keyboard unlocked PoF Keyboard locked noP In programming mode no parameter in Pr1 On the display or in dP2 dP3 dP4 the selected probe is...

Страница 7: ...tor fan controlled during defrost no no Pr2 Fon Evaporator fan ON time in normal mode with compressor OFF 0 0 Pr2 min FoF Evaporator fan OFF time in normal mode with compressor OFF 0 0 Pr2 min FAC Probe selection for condenser fan nP nP Pr2 St2 Set Point 2 Regulation for condenser fan 0 0 15 0 Pr2 C Hy2 Set Point 2 differential for condenser fan 1 0 10 0 Pr2 C FCC Condenser fan operating mode O_n ...

Страница 8: ...0 Pr2 hh mm Adr Serial address 1 1 Pr2 bAU Baudrate 9 6 9 6 Pr2 onC ONOFF button configuration left upper side nU nU Pr2 on2 ONOFF button timed 3sec configuration left upper side oFF oFF Pr2 LGC Light button configuration left upper side LiG LiG Pr2 LG2 Light button timed 3sec configuration left upper side nU nU Pr2 dFC DEF button configuration left upper side Pb2 Pb2 Pr2 dF2 DEF button timed 3sec...

Страница 9: ...50T150 C resolution 0 1 C or 1 C selectable Accuracy 0 7 C 1 digit and relative to the full scale Inputs 4 NTC PTC or PT1000 configurable 1 voltage free contacts I O port HOT KEY MAX voltage allowed is 5 VDC DO NOT CONNECT ANY EXTERNAL POWER SUPPLY Buzzer Optional Serial Outputs TTL standard available on 5 pin port HOT KEY connector Maximum cable length 2m Relay Outputs standard Ref Nominal UL IEC...

Отзывы: