XR44CX 

1/4 

Digital controller with defrost and fan management

 

XR44CX  

1.

 

GENERAL WARNING ........................................................................................................... 1

 

2.

 

GENERAL DESCRIPTION .................................................................................................... 1

 

3.

 

CONTROLLING LOADS ....................................................................................................... 1

 

4.

 

FRONT PANEL COMMANDS ............................................................................................... 1

 

5.

 

MAX & MIN TEMPERATURE MEMORIZATION .................................................................... 1

 

6.

 

MAIN FUNCTIONS ............................................................................................................... 2

 

7.

 

PARAMETERS ..................................................................................................................... 2

 

8.

 

DIGITAL INPUTS .................................................................................................................. 3

 

9.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS ............................................................. 3

 

10.

 

INSTALLATION AND MOUNTING ......................................................................................... 3

 

11.

 

ELECTRICAL CONNECTIONS.............................................................................................. 3

 

12.

 

USE THE HOT KEY.............................................................................................................. 3

 

13.

 

ALARM SIGNALS ................................................................................................................. 3

 

14.

 

TECHNICAL DATA ............................................................................................................... 4

 

15.

 

CONNECTIONS ................................................................................................................... 4

 

16.

 

DEFAULT SETTING VALUES ............................................................................................... 4

 

 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This  manual  is  part of the product and should be kept near the instrument for easy and quick 
reference. 

 

The  instrument  shall  not  be  used  for  purposes  different  from  those  described  hereunder.  It 
cannot be used as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell  Srl  reserves  the  right  to  change  the  composition  of  its  products,  even  without  notice, 
ensuring the same and unchanged functionality. 

1.2

 

SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do  not expose to water or moisture: use the controller only within the operating limits avoiding 
sudden  temperature  changes  with  high  atmospheric  humidity  to  prevent    formation  of 
condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.” 
(see address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure  that  the  wires  for  probes,  loads  and  the  power  supply  are  separated  and  far  enough 
from each other, without crossing or intertwining. 

 

In  case  of  applications  in  industrial  environments,  the  use  of  mains  filters  (our  mod.  FT1)  in 
parallel with inductive loads could be useful. 

2.

 

GENERAL DESCRIPTION 

Model XR44CX, format 32 x 74 mm, is microprocessor based controller, suitable for applications on 
low temperature refrigerating units. It has four relay outputs to control compressor 1 and 2, defrost 1 
and  2,  which  can  be  either  electrical  or  reverse  cycle  (hot  gas).  It  is  also  provided with up to three 
NTC  or  PTC  probe  inputs,  the  first  one  for  temperature  control,  the  second  and  third  one,  to  be 
located onto the evaporator, to control the defrost termination temperature on the evaporator 1 and 2.   
It allows to program the controller by means the HOT KEY programming keyboard. 

3.

 

CONTROLLING LOADS 

3.1

 

COMPRESSOR 

The regulation is performed according to 
the  temperature  measured  by  the 
thermostat  probe  with  a  positive 
differential  from  the  set  point:  if  the 
temperature  increases  and  reaches  set 
point  plus  differential  the  compressor  is 
started  and  then  turned  off  when  the 
temperature  reaches  the set point value 
again. 

Time

Temper.

Compr.

SET

ON

 

In  case  of  fault  in  the  thermostat  probe  the  start  and  stop  of  the  compressor  are  timed  through 
parameters Con and CoF

3.2

 

SECOND COMPRESSOR MANAGEMENT  

The relay of the second compressor is activated in parallel with the relay of the first compressor, with 
a possible delay set in the AC1 parameter. Both the compressors are switched off at the same time. 

3.3

 

DEFROST  

Two  defrost  modes  are  available  through  the  tdF  parameter:  defrost  through  electrical  heater 
(tdF=EL) and hot gas defrost (tdF=in).  
Other  parameters  are  used  to control the interval between defrost cycles (idF), its maximum length 
(MdF) and two defrost modes: timed or controlled by the evaporator’s probe (P2P).  
At the end of defrost dripping time is started, its length is set in the Fdt parameter. With Fdt=0 the 
dripping time is disabled. 

3.4

 

CONTROL OF EVAPORATOR FANS 

The fan control mode is selected by means of the FnC parameter: 
FnC=C_n, fans will switch ON and OFF with the compressor and not run during defrost. 
FnC=o_n, fans will run even if the compressor is off, and not run during defrost. 
 
After defrost, there is a timed fan delay allowing for drip time, set by means of the Fnd parameter. 

FnC=C_Y, fans will switch ON and OFF with the compressor and run during defrost. 
FnC=o_Y, fans will run continuously also during defrost. 

 

An additional parameter FSt provides the setting of temperature, detected by the evaporator probe, 
above  which  the  fans  are  always  OFF.  This  is  used  to  make  sure  circulation  of  air  only  if  his 
temperature is lower than set in FSt

3.4.1  Forced activation of fans 

This  function  managed  by  the  FCt  parameter  is  designed  to  avoid  short  cycles  of  fans,  that  could 
happen when the controller is switched on or after a defrost, when the room air warms the evaporator. 
How it works: if the temperature difference between evaporator probe and room probe is higher than 
the FCt parameter value, fans will be switched on. With FCt=0 the function is disabled. 

3.4.2  Cyclical activation of the fans with compressor off. 

When FnC=C-n or C-Y (fans working in parallel with the compressor), by means of the Fon and FoF 
parameters the fans can carry out on and off cycles even if the compressor is switched off. When the 
compressor is stopped the fans go on working for the Fon time. With Fon=0 the fans remain always 
off, also when the compressor is off.  

4.

 

FRONT PANEL COMMANDS 

 

 
 

 

To display target set point; in programming mode it selects a parameter or confirm 
an operation. 

 

(DEF) To start a manual defrost. 

 

(UP) To see the max stored temperature; in programming mode it browses the 
parameter codes or increases the displayed value. 

 

(DOWN) To see the min stored temperature; in programming mode it browses the 
parameter codes or decreases the displayed value. 

 

To switch the instrument on and off (when onF=oFF).  

 

To switch on and off the light output (if present). 

 

KEY COMBINATIONS: 

  

 

 

To lock & unlock the keyboard. 

 

+

  

 

To enter in programming mode. 

  

+

  

 

To return to the room temperature display. 

4.1

 

USE OF LEDS 

Each LED function is described in the following table. 

LED 

MODE  FUNCTION 

 

ON 

Compressor enabled 

Flashing  Anti-short cycle delay enabled 

 

ON 

Defrost enabled 

Flashing  Drip time in progress 

 

ON 

An alarm is occurring 

 

ON 

Continuous cycle is running 

°C/°F 

ON 

Measurement unit 

Flashing  Programming phase 

5.

 

MAX & MIN TEMPERATURE MEMORIZATION 

5.1

 

HOW TO: SEE THE MIN TEMPERATURE 

1. 

 

Press and release the DOWN key. 

2. 

 

The “Lo” message will be displayed followed by the minimum temperature recorded. 

3. 

 

By pressing the DOWN key again or by waiting 5 sec the normal display will be restored. 

5.2

 

HOW TO: SEE THE MAX TEMPERATURE 

1. 

 

Press and release the UP key. 

2. 

 

The “Hi” message will be displayed followed by the maximum temperature recorded. 

3. 

 

By pressing the UP key again or by waiting 5 sec the normal display will be restored. 

5.3

 

HOW TO: RESET THE MAX AND MIN TEMPERATURE RECORDED 

1.

 

Keep  the  SET  key  pressed  more  than  3  sec,  while  the  max  or  min  temperature  is displayed. 
(“rSt” message will be displayed) 

2.

 

To confirm the operation the “rSt” message will start blinking and the normal temperature will be 
displayed. 

Содержание Dixell XR44CX

Страница 1: ...heater tdF EL and hot gas defrost tdF in Other parameters are used to control the interval between defrost cycles idF its maximum length MdF and two defrost modes timed or controlled by the evaporator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 4 CONTROL OF EVAPORATOR FANS The fan control mode is selec...

Страница 2: ...Y n not present the terminals operate as digital input Y present the terminals operate as third probe o3 Second evaporator probe calibration P3 12 0 to 12 0 C 21 to 21 F allows to adjust possible offset of the third probe odS Outputs activation delay at start up 0 to 255min this function is enabled at the initial start up of the instrument and inhibits any output activation for the period of time ...

Страница 3: ... DOR It signals the door status and the corresponding relay output status through the odC parameter no normal any change FAn Fan OFF CPr Compressor OFF F_C Compressor and fan OFF Since the door is opened after the delay time set through parameter doA the door alarm is enabled the display shows the message dA and the regulation restarts is rtr YES The alarm stops as soon as the external digital inp...

Страница 4: ...min 15 Pr2 CoF Compressor OFF time with faulty probe 0 to 255 min 15 Pr2 CF Temperature measurement unit C F C Pr2 rES Resolution dE in dE Pr1 Lod Probe displayed P1 P2 P3 P4 SEt dtr P1 Pr2 tdF Defrost type EL in EL Pr2 Label Name Range Value Level dtE First defrost termination temperature 55 to 50 0 C 67 to 122 F 8 Pr1 dtS Second defrost termination temperature 55 to 50 0 C 67 to 122 F 8 Pr1 idF ...