background image

 

xxxxxxxxxxxxxxxxxx XR44CH ISA GB r1.6 21.11.2016 

XR44CH 

3/5 

7.5.2  HOW  TO:  MOVE  A  PARAMETER  FROM  THE  HIDDEN  MENU  TO  THE 
FIRST LEVEL AND VICEVERSA. 

Each parameter present in the hidden menu (Pr2) can be moved into the user level (Pr1) by pressing 
SET+DOWN buttons. If a parameter is part of the user level, when showed in the hidden menu the 
decimal point will be lit. 

7.6

 

HOW TO: LOCK THE KEYBOARD 

1. 

 

Keep both UP and DOWN buttons pressed for more than 3 sec. 

2. 

 

The  “PoF”  message  will  be  displayed  and  the  keyboard  will  be  locked.  At  this  point  it  will  be 
possible only to see the set point or the MAX o Min temperature stored 

3. 

 

If a button is pressed more than 3 sec the “PoF” message will be displayed 

7.7

 

HOW TO: UNLOCK THE KEYBOARD 

Keep pressed together for more than 3 sec the UP

 and DOWN keys till the “Pon” message will be 

displayed. 

7.8

 

THE CONTINUOUS CYCLE 

When defrost is not in progress, it can be activated by holding the UP key pressed for about 3 sec. 
The compressor operates to maintain the CCS set point for the time set through the CCt parameter. 
The cycle can be terminated before the end of the set time using the same activation key UP for 3 sec. 

7.9

 

THE ON/OFF FUNCTION 

 

With “onF = oFF”, pushing the ON/OFF key, the instrument is switched off. The “OFF” 
message is displayed. In this configuration, the regulation is disabled. 
To switch the instrument on, push again the ON/OFF key. 

WARNING: Loads connected to the normally closed contacts of the relays are always supplied 
and under voltage, even if the instrument is in stand by mode.  

7.10

 

SECOND DIGITAL INPUT OR PROBE 4. 

The input normally used as fourth probe can be used as second digital input according to the setting of 
the parameter P4C. 
With P4C = Pb the input works as probe. 
With P4C = i2F the input works as second digital input (par. i2F) 

8.

 

PARAMETERS 

REGULATION 

HY 

Differential: (0.1 to 25.5°C; 1 to 45°F) intervention differential for set point. Compressor 
Cut IN is Set Point + differential (HY). Compressor Cut OUT is when the temperature 
reaches the set point. 

LS   

Minimum set point: (-100°C to SET; -148°F to SET) sets the minimum value for the 
set point. 

US 

Maximum  set  point:  (SET  to  150°C;  SET  to  302°F)  set  the  maximum  value  for  set 
point. 

ot   

Thermostat probe calibration: (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible 
offset of the thermostat probe. 

P2P 

First evaporator probe presence: (n; Y) n = not present, the defrost stops by time;  
Y = present, the defrost stops by temperature. 

oE 

First  evaporator  probe  calibration:  (-12.0  to  12.0°C;  -21  to  21°F)  allows  to  adjust 
possible offset of the evaporator probe. 

P3P 

Second evaporator probe presence (P3): (n; Y) n = not present, the terminals operate 
as digital input; Y = present, the terminals operate as third probe. 

o3 

Second  evaporator  probe  calibration (P3): (-12.0 to 12.0°C; -21 to 21°F) allows to 
adjust possible offset of the third probe. 

P4P 

Fourth probe presence (P4): (n; Y) n = not present, Y = present 

O4 

Fourth probe calibration (P4): (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible 
offset of the fourth probe. 

P4C 

Probe 4 setting (Pb = temperature probe: id4 = second digital input) 

odS 

Outputs activation delay at start up: (0 to 255min) this function is enabled at the initial 
start up of the instrument and inhibits any output activation for the period of time set in 
the parameter.  

AC   

Anti-short cycle delay for first compressor: (0 to 50 min) minimum interval between 
the compressor stop and the following restart. 

AC1    Anti-short  cycle  delay  for  second  compressor:  (0  to  50  min)  minimum  interval 

between the compressor stop and the following restart. 

Mon 

Maximum  time  single  compressor  on  :  (0÷255min;  with  0  function  not  enabled). 
When Mon is expired the second compressor is activated. 

2CC 

Dual compressor management: SEq = sequence – HAF= Dual  band 

rtr 

Percentage of the third and first probe for regulation (0÷100; 100 = P1, 0 = P3 ): it 
allows to set the regulation according to the percentage of the first and third probe, as 
for the following formula (rtr(P1-P3)/100 + P3) 

CCt 

Compressor ON time during continuous cycle: (0.0 to 24h00min, res. 10 min) allows 
to  set  the  length  of  the  continuous  cycle.  Compressor  stays  on  without  interruption 
during CCt time. This is useful, for instance, when the room is filled with new products. 

CCS 

Set point for continuous cycle: (-55 to 150°C; -67 to 302°F) it sets the set point used 
during the continuous cycle. 

Con 

Compressor  ON  time  with  faulty  probe:  (0  to  255min)  time  during  which  the 
compressor  is  active  in  case  of  faulty  thermostat  probe.  With  Con=0  compressor  is 
always OFF. 

CoF 

Compressor  OFF  time  with  faulty  probe:  (0  to  255min)  time  during  which  the 
compressor  is  OFF  in  case  of  faulty  thermostat  probe.  With  CoF=0  compressor  is 
always active. 

DISPLAY 

CF 

Temperature measurement unit: (°C; °F) °C = Celsius; °F = Fahrenheit.  
WARNING: When the measurement unit is changed the SET point and the values of the 
parameters  HY,  LS,  US,  ot,  ALU  and  ALL  have  to  be  checked  and  modified  (if 
necessary). 

rES 

Resolution (for °C): (in=1°C; dE=0.1°C) allows decimal point display. 

Lod 

Instrument display: (P1; P2, P3, P4, SET, dtr) it selects which probe is displayed by the 
instrument. P1 = Thermostat probe; P2 = Evaporator probe; P3 = Third probe (only for 
model with this option enabled); P4 = Fourth probe, SET = set point; dtr = percentage of 
visualization. 

rEd 

X-  REP  display  (optional):  (P1;  P2,  P3,  P4,    SET,  dtr):  it  selects  which  probe  is 
displayed  by  X-  REP:  P1  =  Thermostat  probe;  P2  =  Evaporator  probe;  P3  =  Third 
probe(only for model with this option enabled); P4 = Fourth probe, SET = set point;  dtr = 
percentage of visualization. 

dLy 

Display  delay:  (0  ÷20.0m;  risul.  10s)  when  the  temperature  increases,  the  display  is 
updated of 1 °C/1°F after this time. 

dtr 

Percentage of the third and first probe for visualization when Lod = dtr (0÷100; 100 
= P1, 0 = P3 ): if Lod = dtr 
it allows to set the visualization according to the percentage 
of the first and third probe, as for the following formula (dtr(P1-P3)/100 + P3). 

DEFROST 

tdF 

Defrost type: (EL; in) EL = electrical heater; in = hot gas. 

dFP 

Probe selection for first defrost termination: (nP; P1; P2; P3; P4) nP = no probe;  
P1 =thermostat probe; P2 = second probe; P3 =configurable probe; P4 = Fourth probe. 

dSP 

Probe selection for second defrost termination: (nP; P1; P2; P3; P4) nP = no probe; 
P1 =thermostat probe; P2 = second probe; P3 =configurable probe; P4 = Fourth probe. 

dtE 

First defrost termination temperature: (-55 to 50°C; -67 to 122°F) (enabled only when 
EdF=Pb) sets the temperature measured by the evaporator probe, which causes the end 
of defrost. 

dtS 

Second  defrost  termination temperature: (-55 to 50°C; -67 to 122°F) (enabled only 
when EdF=Pb) sets the temperature measured by the evaporator probe, which causes 
the end of defrost. 

idF 

Interval  between  defrost  cycles:  (0  to  120  hours)  determines  the  interval  of  time 
between two defrost cycles. 

MdF 

(Maximum) length for first defrost: (0 to 255 min) when P2P=n, (not evaporator probe: 
timed  defrost)  it  sets  the  defrost  duration.  When  P2P=Y  (defrost  end  based  on 
temperature) it sets the maximum length for defrost. 

MdS 

(Maximum)  length  for  second defrost: (0 to 255 min) when P2P=n, (not evaporator 
probe:  timed  defrost)  it  sets  the  defrost  duration.  When  P2P=Y (defrost end based on 
temperature) it sets the maximum length for defrost. 

dSd 

Start  defrost  delay:  (0  to  99  min)  this is useful when different defrost start times are 
necessary to avoid overloading the plant.  

StC 

Compressor stop before defrost: (da 0 a 30 min) with hot gas defrost it sets 
compressor stop vefore defrost. 

dFd 

Temperature displayed during defrost: (rt; it; SEt; dEF) rt = real temperature;  
it = temperature at defrost start; SEt = set point; dEF = “dEF” label. 

dAd 

MAX display delay after defrost: (0 to 255 min) sets the maximum time between the 
end of defrost and the restarting of the real room temperature display. 

Fdt 

Drip time: (0 to 120 min) time interval between reaching defrost termination temperature 
and  the  restoring  of  the  control’s  normal  operation.  This  time allows the evaporator to 
eliminate water drops that might have formed due to defrost. 

dPo 

First defrost after start-up: (n; Y) n = after the idF time, Y = immediately. 

Hd1 

Pre-defrost cycle differential (-12.0÷12.0°C/-24÷24°F) 

Ht1 

Pre-defrost cycle duration (0÷120min) 

Hd2 

Post-defrost cycle differential (-12.0÷12.0°C/-24÷24°F) 

Ht2 

Post-defrost cycle duration (0÷120min) 

dAF 

Defrost  delay  after  continuous  cycle:  (0.0  to  24h00min,  res.  10min)  time  interval 
between the end of the fast freezing cycle and the following defrost related to it. 

FANS 

FnC 

Fans operating mode: (C-n; o-n; C-Y; o-Y) C-n = runs with the compressor, OFF during 
defrost; o-n = continuous mode, OFF during defrost;  C-Y = runs with the compressor, 
ON during defrost; o-Y = continuous mode, ON during defrost. 

Fnd 

Fans delay after defrost: (0 to 255min) interval between end of defrost and evaporator 
fans start. 

FCt 

Temperature  differential  to  avoid  fan  short  cycles:  (0  to  59°C;  0  to  90°F)  (N.B.:  if 
FCt=0 function disabled) if the difference of temperature between the evaporator and the 
room probes is higher than FCt value, the fans will be switched on. 

FSt 

Fans stop temperature: (-55 to 50°C; -67 to 122°F) setting of temperature, detected by 
evaporator probe, above which fans are always OFF. 

Fon 

Fan  ON  time:  (0÷15  min)  with  Fnc  =  C_n  or  C_y,  (fan  activated  in  parallel  with 
compressor).  it  sets  the  evaporator  fan  ON  cycling  time  when  the  compressor  is  off. 
With Fon =0 and FoF ≠ 0 the fan are always off, with Fon=0 and FoF =0 the fan are 
always off. 

FoF 

Fan  OFF  time:  (0÷15  min)  with  Fnc  =  C_n  or  C_y,  (fan  activated  in  parallel  with 
compressor). it sets the evaporator fan off cycling time when the compressor is off. With 
Fon =0 and FoF ≠ 0 the fan are always off, with Fon=0 and FoF =0 the fan are always 
off. 

FSU 

Kind of action of fan: 

Std = standard, according to the Fnc parameter 
Fon  =  with  i1F  =  FAn  and  Fnc  =  Cn  or  C-y,  by  means  of  digital input the fan works 
according to the Fnc parameter or are always on. 
FoF = with i1F = FAn by means of digital input the fan are enabled or switched off.

 

ALARMS 

ALU 

MAXIMUM temperature alarm:  

 

If ALC=Ab: [ALL to 150.0°C or ALL to 302°F] 

 

If ALC=rE: [0.0 to 50.0°C or 0 to 90°F] 

when this temperature is reached the alarm is enabled, after the ALd delay time. 

ALL 

Minimum temperature alarm:  

 

If ALC=Ab: [-100°C to ALU; -148 to ALU] 

 

If ALC=rE: [0.0 to 50.0°C or 0 to 90°F] 

when this temperature is reached the alarm is enabled, after the ALd delay time. 

AFH 

Differential  for  temperature  alarm  recovery:  (0.1  to  25.5°C;  1  to  45°F)  intervention 
differential for recovery of temperature alarm. 

ALd    Temperature  alarm  delay:  (0  to  255  min)  time  interval  between  the  detection  of  an 

alarm condition and alarm signalling. 

Содержание Dixell XR44CH

Страница 1: ...econd compressor is activated after a delay counter AC1 parameter Both compressor are switched off when the temperature set point is reached 3 2 2 Dual band activation With 2CC HAF the regulation is changed as follows a Activation of compressors The activation threshold of the first compressor is where T is temperature T SET Hy The activation threshold of the second compressor is where T is temper...

Страница 2: ... Press and release the UP key 2 The Hi message will be displayed followed by the maximum temperature recorded 3 By pressing the UP key again or by waiting 5 sec the normal display will be restored 5 3 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 1 Keep the SET key pressed more than 3 sec while the max or min temperature is displayed rSt message will be displayed 2 To confirm the operation the...

Страница 3: ...nly for model with this option enabled P4 Fourth probe SET set point dtr percentage of visualization rEd X REP display optional P1 P2 P3 P4 SET dtr it selects which probe is displayed by X REP P1 Thermostat probe P2 Evaporator probe P3 Third probe only for model with this option enabled P4 Fourth probe SET set point dtr percentage of visualization dLy Display delay 0 20 0m risul 10s when the tempe...

Страница 4: ...d the display shows the message dA and the regulation restarts is rtr YES The alarm stops as soon as the external digital input is disabled again With the door open the high and low temperature alarms are disabled 9 5 START DEFROST I1F DEF It starts a defrost if there are the right conditions After the defrost is finished the normal regulation will restart only if the digital input is disabled oth...

Страница 5: ... Defrost type EL 0 in 1 ALt 2 in Pr2 dFP Probe for first defrost nP 0 P1 1 P2 2 P3 3 P4 4 P2 Pr2 dSP Probe for second defrost nP 0 P1 1 P2 2 P3 3 P4 4 nP Pr2 dtE First defrost termination temperature 55 0 C 50 0 C 67 F 122 F 8 0 Pr2 dtS Second defrost termination temperature 55 0 C 50 0 C 67 F 122 F 8 0 Pr2 idF Interval between defrost cycles 0 120 hours 6 Pr2 MdF Maximum length for first defrost ...

Отзывы: