22 • XR35CX I&O Manual
17 E2 MODBUS Network Wiring
• Connect the MODBUS Network to the RS485 Connector on the E2 PIB board (Belden 8641 recommended).
• Note to wire the RS485 +/- polarity at the E2 in the
reverse
of the XR35CX devices.
• Position the three termination jumpers to the UP (terminated) position to provide RS485 termination at the E2.
• Do not connect the shield of the MODBUS network to the E2 PIB center terminal. Instead, use a 100 ohm 1/2 watt
resistor to connect the MODBUS cable shield to earth ground.
• At each XR35CX device, wire the MODBUS cable to the RS485 +/- terminals and connect the MODBUS shield to
the pin
18
terminal.
• Terminate the end of the MODBUS network at the last XR35CX device on the daisy chain with the MODBUS
termination block (
P/N 535-2711
), or by connecting a 150 ohm resistor between the /- terminals.
Appendix A - Alternate MODBUS COM Wiring Method for E2, XR, XM, and XEV Devices
(Technical Bulletin P/N 026-4148).
Figure 17-1
- XR35CX to E2 MODBUS Network Wiring
100 ohm
½ Watt
Shield
Shield
Sh
ie
ld
EARTH GROUND CONNECTION
MODBUS TERMINATION
BLOCK 535-2711 150 ohm
Terminate last device only
REVERSE POLARITY OF +/- ON RS-485
CABLE FROM E2 TO DEVICE
*Note that for E2 Enhanced PIB
boards, the RS-485 connection
can be wired on COM 2, COM 4,
or COM 6 port.
Содержание Dixell XR35CX - 110VAC
Страница 2: ......
Страница 4: ......
Страница 27: ...Other Messages Connections 21 16 Connections The X REP output is optional Figure 16 1 XR35CX Connections ...
Страница 38: ...32 XR35CX I O Manual 026 1203 Rev 3 03 FEB 2015 Figure A 1 MODBUS Com Wiring Diagram ...