background image

 

 

1592020010 XR10CX GB m&M r1.1 27.03.2015 

XR10CX 

1/4 

Digital controller with cooling or heating action

 

XR10CX 

 

CONTENTS 

1.

 

GENERAL WARNING ___________________________________________________ 1

 

2.

 

GENERAL DESCRIPTION  _______________________________________________ 1

 

3.

 

CONTROLLING LOADS _________________________________________________ 1

 

4.

 

FRONT PANEL COMMANDS _____________________________________________ 1

 

5.

 

MAX & MIN TEMPERATURE MEMORIZATION _______________________________ 1

 

6.

 

MAIN FUNCTIONS _____________________________________________________ 2

 

7.

 

PARAMETERS  ________________________________________________________ 2

 

8.

 

DIGITAL INPUT (ENABLED WITH P3P = N)  _________________________________ 3

 

9.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS ___________________________ 3

 

10.

 

X-REP OUTPUT – OPTIONAL ____________________________________________ 3

 

11.

 

INSTALLATION AND MOUNTING  _________________________________________ 3

 

12.

 

ELECTRICAL CONNECTIONS ____________________________________________ 3

 

13.

 

HOW TO USE THE HOT KEY _____________________________________________ 3

 

14.

 

ALARM SIGNALS ______________________________________________________ 3

 

15.

 

TECHNICAL DATA _____________________________________________________ 3

 

16.

 

CONNECTIONS  _______________________________________________________ 4

 

17.

 

DEFAULT SETTING VALUES _____________________________________________ 4

 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy and 
quick reference. 

 

The instrument shall not be used for purposes different from those described hereunder. 
It cannot be used as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell  Srl  reserves  the  right  to  change  the  composition  of  its  products,  even  without 
notice, ensuring the same and unchanged functionality. 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do  not  expose  to  water  or  moisture:  use  the  controller  only  within  the  operating  limits 
avoiding  sudden  temperature  changes  with  high  atmospheric  humidity  to  prevent  
formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit  the  probe  where  it  is  not  accessible  by the  End  User.  The  instrument  must  not  be 
opened. 

 

In  case  of  failure  or  faulty  operation  send  the  instrument  back  to  the  distributor  or  to 
“Dixell S.r.l.” (see address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure  that  the  wires  for  probes,  loads  and  the  power  supply  are  separated  and  far 
enough from each other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) 
in parallel with inductive loads could be useful. 

2.

 

GENERAL DESCRIPTION 

Model 

XR10C

, format 32 x 74 mm format is a single stage temperature controller suitable for 

applications    in  the  field  of  refrigeration  or  heating.  It  provides  a  relay  output  to  drive  the 
compressor.  It is also provided with 2 NTC or PTC probe inputs, the first one for temperature 
control,  the  second  one,  optional,  to  connect  to  the  HOT  KEY  terminals  to  signal  the 
condenser  temperature  alarm  or  to  display  a  temperature.  The  digital  input  can  operate  as 
third temperature probe. 
The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX,  
to  a  network  line 

ModBUS-RTU

  compatible  such  as  the  Dixell  monitoring  units    of  X-WEB 

family. It allows to program the controller by means the HOT KEY programming  keyboard.  
The  instrument  is  fully  configurable  through  special  parameters  that  can  be  easily 
programmed through the keyboard. 

3.

 

CONTROLLING LOADS 

3.1

 

THE REGULATION OUTPUT 

The regulation is performed according to the temperature measured by the probe. 
The instruments are provided with the 

CH 

programmable parameter which enables the user to 

set the regulation both for heating or cooling applications:

 

· 

 CH = CL: cooling applications

  

· 

 

CH = Ht: heating applications

 

3.2

 

CH = CL: COOLING APPLICATIONS. 

The  Hy  value  is  automatically  set  above  the  Set  Point.  If  the  temperature  increases  and 
reaches  set  point  plus  differential  the  compressor  is  started  and  then  turned  off  when  the 
temperature reaches the set point value again.  
 

Time

Temper.

Compr.

SET

ON

 

 

3.3

 

CH = HT: HEATING APPLICATION.  

The  Hy  value  is  automatically  set  under  the  Set  Point.  If  the  temperature  decreases  and 
reaches set point minus differential the regulation output is activated and then turned off when 
the temperature reaches the set point value again. 
 

Time

Temper.

Heating

ON

SET

SET- HY

Time

 

4.

 

FRONT PANEL COMMANDS 

 

 

 

: To display target set point; in programming mode it  selects a parameter  or confirm 

an operation. 

  (DEF) 

Not enabled 

 

  (

UP)

:  To  see  the  max.  stored  temperature;  in  programming  mode  it  browses  the 

parameter codes or increases the displayed value. 

  (

DOWN

)  To  see  the  min  stored  temperature;  in  programming  mode  it  browses  the 

parameter codes or decreases the displayed value. 

 

To switch the instrument off, if onF = oFF.  

 

Not enabled 

KEY COMBINATIONS: 

  

 



To lock & unlock the keyboard

.

 

 

+

  

 

To enter in programming mode. 

  

+

  

 

To return to the room temperature display. 

4.1

 

USE OF LEDS 

Each LED function is described in the following table. 

LED 

MODE 

FUNCTION 

 

ON 

Compressor enabled 

 

Flashing 

Anti-short cycle delay enabled 

  ON 

An alarm is occurring 

  ON 

Energy saving enabled 

°C/°F 

ON 

Measurement unit 

°C/°F 

Flashing 

Programming phase 

5.

 

MAX & MIN TEMPERATURE MEMORIZATION 

5.1

 

HOW TO SEE THE MIN TEMPERATURE 

1. 

 

Press and release the 

n

 key. 

2. 

 

The “Lo” message will be displayed followed by the minimum temperature recorded. 

3. 

 

By pressing the 

n

 key again or by waiting 5s the normal display will be restored. 

5.2

 

HOW TO SEE THE MAX TEMPERATURE 

1. 

 

Press and release the 

o

 key. 

2. 

 

The “Hi” message will be displayed followed by the maximum  temperature recorded. 

3. 

 

By pressing the 

o

 key again or by waiting 5s the normal display will be restored. 

5.3

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 

1.

 

Hold  press  the  SET  key  for  more  than  3s,  while  the  max.  or  min  temperature  is 
displayed. (rSt message will be displayed) 

2.

 

To confirm the operation the “rSt” message starts blinking and the normal temperature 
will be displayed. 

Содержание Dixell XR10CX

Страница 1: ...ut to drive the compressor It is also provided with 2 NTC or PTC probe inputs the first one for temperature control the second one optional to connect to the HOT KEY terminals to signal the condenser temperature alarm or to display a temperature The digital input can operate as third temperature probe The HOT KEY output allows to connect the unit by means of the external module XJ485 CX to a netwo...

Страница 2: ...With COn 0 compressor is always OFF COF Compressor OFF time with faulty probe 0 255 min time during which the compressor is OFF in case of faulty thermostat probe With COF 0 compressor is always active CH Type of action CL cooling Ht heating DISPLAY CF Temperature measurement unit C Celsius F Fahrenheit WARNING When the measurement unit is changed the SET point and the values of the parameters Hy ...

Страница 3: ...able external relay 12 1 PROBE CONNECTION The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature Place the defrost termination probe among the evaporator fins in the coldest place where most ice is formed far from heaters or from th...

Страница 4: ... cL Pr1 CF Temperature measurement unit C F C Pr2 rES Resolution in integer dE dec point dE Pr1 dLy Display temperature delay 0 20 0 min 10 sec 0 Pr2 ALc Temperat alarms configuration rE related to set Ab absolute Ab Pr2 ALU MAXIMUM temperature alarm Set 110 0 C Set 230 F 110 Pr1 ALL Minimum temperature alarm 50 0 C Set 58 F Set 50 0 Pr1 AFH Differential for temperat alarm recovery 0 1 C 25 5 C 1 ...

Отзывы: