XR06CH

 

1/3

 

 

DIGITAL CONTROLLER WITH DEFROST AND 

FANS MANAGEMENT 

XR06CH BMB 

1

 

General warnings ............................................................................................................................................. 1

 

2

 

General description .......................................................................................................................................... 1

 

3

 

Regulation ........................................................................................................................................................ 1

 

4

 

Defrost .............................................................................................................................................................. 1

 

5

 

Fans .................................................................................................................................................................. 1

 

6

 

Front panel commands .................................................................................................................................... 1

 

7

 

Parameters ....................................................................................................................................................... 2

 

8

 

Digital inputs (ONLY XR03CX) ........................................................................................................................ 2

 

9

 

Installation and mounting ................................................................................................................................. 2

 

10

 

Electrical connections ...................................................................................................................................... 2

 

11

 

How to use the hot key .................................................................................................................................... 2

 

12

 

Alarm signalling ................................................................................................................................................ 2

 

13

 

Technical data .................................................................................................................................................. 3

 

14

 

Connections ..................................................................................................................................................... 3

 

15

 

Default setting values....................................................................................................................................... 3

 

 

1

 

GENERAL WARNINGS 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This  manual  is  part  of  the  product  and  should  be  kept  near  the  instrument  for  easy  and  quick 
reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot be 
used as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell Srl reserves  the right to change the composition of its products, even without  notice,  ensuring 
the same and unchanged functionality. 

1.2

 

SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not  expose to water or  moisture: use  the controller only within the operating limits avoiding sudden 
temperature changes with high atmospheric humidity to prevent  formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.p.A.” (see 
address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from each 
other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with 
inductive loads could be useful. 

 

Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring the 
same and unchanged functionality. 

2

 

GENERAL DESCRIPTION 

The XR06CHformat 32 x 74 x 60 mm, is microprocessor based controller, suitable for applications 
on  medium  or  low  temperature  ventilated  refrigerating  units.  It  has  three  relay  outputs  to  control 
compressor, fan, and defrost which can be either electrical or reverse cycle (hot gas).  The device is 
also provided with 2 NTC probe inputs, the first one for temperature control and the second one to be 
located  onto  the  evaporator,  to  control  the  defrost  termination  temperature  and  to  managed  the  fan 
and  it’s  provided  with  a  configurable  digital  input.  With  the  HOTKEY  it’s  possible  to  program  the 
instrument in a quick and easy way. 

3

 

REGULATION 

The  regulation  is  performed  according  to 
the  temperature  measured  by  the 
thermostat 

probe 

with 

positive 

differential  from  the  set  point:  if  the 
temperature  increases  and  reaches  set 
point  plus  differential  the  compressor  is 
started  and  then  turned  off  when  the 
temperature  reaches  the  set  point  value 
again. 

 

In  case  of  fault  in  the  thermostat  probe  the  start  and  stop  of  the  compressor  are  timed  through 
parameters “Cy” and “Cn”. 

4

 

DEFROST 

Two defrost modes are available through the “td” parameter: 

 

td=EL 

 defrost through electrical heater (compressor OFF) 

 

td=in 

 hot gas  defrost (compressor ON).  

Other  parameters  are  used  to  control  the  interval  between  defrost  cycles  (id)  ),  its  maximum length 
(Md)  and  two  defrost  modes:  timed  or  controlled  by  the  evaporator’s  probe.  At  the  end  of  defrost 
dripping time is started, its length is set in the dt parameter. With dt=0 the dripping time is disabled. 

5

 

FANS 

With FC parameter it can be selected the fans functioning: 

 

FC=cn 

 will switch ON and OFF with the compressor and not run during defrost 

 

FC=on 

 fans will run even if the compressor is off, and not run during defrost 

 
After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fd” parameter. 
 

 

FC=cy 

 fans will switch ON and OFF with the compressor and run during defrost 

 

FC=oY 

 fans will run continuously also during defrost. 

 

An additional parameter  “FS”  provides the setting of temperature, detected by the  evaporator  probe, 
above  which  the  fans  are  always  OFF.  This  is  used  to  make  sure  circulation  of  air  only  if  his 
temperature is lower than set in “FS” 

5.1

 

FANS AND DIGITAL INPUT 

When the digital input is configured as door switch iF=do, fans and compressor status depends on the 
dC parameter value:  

 

dC=no 

 normal regulation; 

 

dC=Fn 

 fans OFF; 

 

dC=cP 

 compressor OFF;  

 

dC=Fc 

 compressor and fans OFF. 

When  rd=y, the regulation restart with door open alarm. 

6

 

FRONT PANEL COMMANDS 

 

  

To  display  target  set  point,  in 
programming  mode  it  selects  a 
parameter 

or 

confirm 

an 

operation 

 

To start a manual defrost  

 

In  programming  mode  it  browses 
the parameter codes or increases 
the displayed value 

 

In  programming  mode  it  browses 
the 

parameter 

codes 

or 

decreases the displayed value 

 

KEYS COMBINATION 

 

+

 

 

To lock or unlock the keyboard

 

 

+

 

 

To enter in programming mode 

 

+

 

 

To return to room temperature display

 

 

LED 

MODE 

SIGNIFICATO 

 

On 

Compressor enabled 

Flashing 

Anti short cycle delay enabled (AC parameter) 

 

On 

Defrost in progress 

Flashing 

Dripping in progress 

 

On 

Fans output enabled 

Flashing 

Fans delay after defrost 

 

On 

Measurement unit  

Flashing 

Programming mode 

 

On 

Measurement unit 

Flashing 

Programming mode 

6.1

 

HOW TO SEE THE SET POINT 

1.

 

Push and immediately release the SET key, the set point will be showed; 

2.

 

Push and immediately release the SET key or wait about 5s to return to normal visualisation. 

6.2

 

HOW TO CHANGE THE SETPOINT 

1.

 

Push the SET key for more than 2 seconds to change the Set point value; 

2.

 

The value of the set point will be displayed and the “°C” or “°F” LED starts blinking; 

3.

 

To change the Set value push the 

 or 

 arrows. 

4.

 

To memorise the new set point value push the SET key again or wait 10s. 

6.3

 

HOW TO START A MANUAL DEFROST 

 

Push the DEF 

 key for more than 2 seconds and a manual defrost will start 

6.4

 

HOW TO CHANGE A PARAMETER VALUE 

 

To change the parameter’s value operate as follows:  
1.

 

Enter  the  Programming  mode  by  pressing  the  SET

  keys  for  3s  (“°C”  or  “°F”  LED  starts 

blinking). 

2.

 

Select the required parameter. Press the “SET” key to display its value 

3.

 

Use 

 or 

 to change its value. 

4.

 

Press “SET” to store the new value and move to the following parameter. 

To exit: Press SET

 or wait 15s without pressing a key. 

NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

6.5

 

HIDDEN MENU 

The hidden menu includes all the parameters of the instrument. 

HOW TO ENTER THE HIDDEN MENU 

1.

 

Enter  the  Programming  mode  by  pressing  the  SET

  keys  for  3s  (“°C”  or  “°F”  LED  starts 

blinking). 

2.

 

Released  the  keys,  then  push  again  the  SET

  keys  for  more  than  7s.  The  L2  label  will  be 

displayed immediately followed from the Hy parameter.  
NOW YOU ARE IN THE HIDDEN MENU. 

3.

 

Select the required parameter. 

4.

 

Press the “SET” key to display its value 

5.

 

Use 

 or 

 to change its value. 

6.

 

Press “SET” to store the new value and move to the following parameter. 

To exit: Press SET

 or wait 15s without pressing a key. 

NOTE1:  if there  aren’t  any  parameter  in  L1,  after  3s  the  “nP”  message  is  displayed.  Keep  the  keys 
pushed till the L2 message is displayed.  
NOTE2: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

HOW  TO  MOVE  A  PARAMETER  FROM  THE  HIDDEN  MENU  TO  THE  FIRST 
LEVEL AND VICEVERSA. 

Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” (user 
level) by pressing SET

. In HIDDEN MENU when a parameter is present in First Level the decimal 

point is on. 