1592039020 XLH210 GB r1.0 Gas Leak Detector 2016.04.26.doc 

                           

XLH210 

2/2

 

7.

 

THE DISPLAY 

 

 

 

 

7.1

 

TO ENTER IN PARAMETER CONFIGURATION 

1)

 

Enter the “Pr1” level where the parameters are visible; press ” SET + DOWN “ for more than 3 seconds. 

2)

 

Enter the “Pr2” level; Select “Pr2” (PAS) with 

n

 key and press “ SET ”. 

3)

 

On the display will appear “0 - -” with a flashing zero. 

4)

 

Use 

o

 or 

n

 to input the security code in the flashing digit; confirm the figure by pressing “ SET ”.  

The security code is “321“. 

7.2

 

TO CHANGE PARAMETER VALUES   

1.

 

Enter the Programming mode. 

2.

 

Select the required parameter. 

3.

 

Press the “ SET ” key to display its value (that start blinking). 

4.

 

Use 

o

 or 

n

 to change its value. 

5.

 

Press “ SET ” to store the new value and move to the following parameter. 

To exit: Press ” SET and then UP “ or wait 15s without pressing a key. 

NOTE: the new values are saved even if the Programming Mode will exit by time-out. 

7.3

 

HOW TO LOCK / UNLOCK THE KEYBOARD  

 + 

 

Keep the 

o

 and 

n

 keys pressed together for more than 3s until appear: 

-

 

“POF”= keyboard is locked 

-

 

“Pon”= keyboard is unlocked 

7.4

 

ON/OFF 

 

By pushing the ON/OFF key, the instrument shows “OFF” for 5 sec. and the ON/OFF LED is 

switched ON.  

To put the instrument in ON mode press another time the key. 

 

8.

 

MEANING OF THE LABELS  

Message 

Meaning 

on 

The controller is on and it is working correctly 

oFF (label or led) 

The controller is OFF (stand-by); no leakages recognized. 

PAL  

The pre-Alarm is active (the AHL threshold has been reached) 

ALL 

The Alarm is active (the AHu threshold has been reached) 

AHL 

Value of the Pre-Alarm threshold (modifiable with SET button) 

AHu 

Value of the Alarm threshold (modifiable with SET button) 

PoF 

The keyboard is locked 

Pon 

The keyboard is unlocked 

Err 

SEnS 

The gas sensor is not connected or broken 

 

The alarm message is displayed until the alarm condition recoveries.  All the alarm messages are showed 

alternating with the room temperature except for the “P1” which is flashing. To reset the “EE” alarm and restart 

the normal functioning press any key, the “rSt” message is displayed for about 3s. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9.

 

KIND OF SENSORS 

 

GAS: any model with 4÷20mA signal; maximum consumption not greater than 4V/A. 

 

Note: 

 

The sensors can be provided by Dixell with a different P/N (the P/N depend on the gas type). Please 

check with our sales department. 

The sensors can recognize the following gas: R134A, R410A, R407C, R404A, R507A, R407A, R407F 

R744, R290. 

The sensor can be IP41 or IP66. Please check with our sales department. 

 

There is a 5-minute power-up delay to allow the sensor to stabilise. 

The green LED will flash at 1 second intervals during the warm-up. 

 

In an alarm condition: 

o

 

green LED stays on and the red LED is on 

o

 

audible alarm operates (if not disabled and after delay, if set). 

o

 

relay output activates (after a delay, if set) 

o

 

I output changes proportionally with gas concentration. 

In a fault condition: 

o

 

green LED will be off and the red LED will be on 

o

 

current fault output will activate: 2mA on the 4-20mA output 

 

10.

 

TECHNICAL DATA 

Housing: self extinguishing ABS  

Case: frontal 210x230 mm; depth 87mm  

Mounting: See par. 3  

Protection: IP65 

Connections: Screw terminal block 

 2,5mm

2

 wiring 

Power supply: 230Vac 50/60Hz 

±

 10% 

Power absorption: 7VA max 

Display:3 digits, red LED; 3 digits, yellow LED low 

Inputs:  4÷20mA input 

Digital inputs: door switch, free voltage  

Relay outputs:   Alarm (oA2): 16A 250V 

Light (oA1): 16A 250Vac 

Pre-Alarm (0A4): 8A 250Vac 

Other outputs:   Buzzer (Standard) 

 

   

Direct RS485 (optional) 

Data storing: on the non-volatile memory (EEPROM) 

Kind of action: 1B 

Pollution grade: normal 

Software class: A 

Operating temperature: 0÷60°C 

Storage temperature: -25÷60°C  

Relative humidity: 20

÷

85% (no condensing) 

Resolution: 1% or 0.1% (selectable) 

 

 

11.

 

DEFAULT SETTING VALUES 

Label  Description 

Range 

Value  Menù 

rEH  Resolution for gas sensor 

in ÷ Hd 

Hd 

Pr2 

tib  Timeout inhibition buzzer 

0 ÷ 250 min 

Pr1 

AHL  Threshold gas pre-alarm 

0% ÷ AHu  

50.0 

Pr1 

AHu  Threshold gas alarm 

AHL ÷ 100% 

80.0 

Pr1 

AHH  Gas alarm recovery differential 

0.5 ÷ 25 % 

10.0 

Pr1 

AHd  Gas alarm delay 

0 ÷ 250 min 

Pr1 

dHo  Delay of gas alarm at start-up 

0.0 ÷ 23.5 hours 

0.0. 

Pr1 

o3  Gas sensor calibration 

-10 ÷ 10 % 

0.0 

Pr2 

P3P  Gas sensor presence

 

n = not present; Y = present 

Pr2 

Lci  Readout with 4 mA 

-999% ÷ uci 

Pr2 

uci  Readout with 20 mA 

LCi ÷ 999% 

100 

Pr2 

i2P  Door switch digital input polarity

 

cL =open / oP = close

 

oP 

Pr1 

AS  Alarm relay polarity 

cL =open / oP = close 

oP 

Pr1 

Adr  RS485 serial address 

1÷247 

Pr1 

Ptb  Parameter table 

read only 

Pr2 

rEL  Software release 

read only 

Pr1 

Pr2  Access to the protected parameter list

 

321 

Pr1 

 

 

 

 

 

 

 

 

 

 

Display with the 

status of the 

controller 

(see 

section 8) 

Value (%) 

measured by the 

sensor; within the 

values between 

the parameters 

“Lci” and “uci”  