Digital controller for CDU management

    

XC10CX and XC30CX  

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This  manual  is  part  of  the  product  and  should  be  kept  near  the  instrument for easy and quick 
reference. 

 

The  instrument  shall  not  be  used  for  purposes  different  from  those  described  hereunder.  It 
cannot be used as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell  Srl  reserves  the  right  to  change  the  composition  of  its  products,  even  without  notice, 
ensuring the same and unchanged functionality. 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits avoiding 
sudden  temperature  changes  with  high  atmospheric  humidity  to  prevent    formation  of 
condensation 

 

Warning:

 disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.” 
(see address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from 
each other, without crossing or intertwining. 

 

In  case  of  applications  in  industrial  environments,  the  use  of  mains  filters  (our  mod.  FT1)  in 
parallel with inductive loads could be useful. 

2.

 

GENERAL DESCRIPTION 

Model 

XC30CX

, format 32x74mm, is a digital thermostat for condensing unit applications. It provides 

three digital (relay) outputs, one for the compressor and the other ones to control the fans. It is also 
provided with 2 NTC or ratiometric probe inputs, to be used on the suction and condenser line. Several 
digital  inputs  can  operate  to  manage  the  condensing  unit  safeties.  The 

HOT-KEY

  output  allows  to 

program the controller by means the 

HOT-KEY

 programming key. The instrument is fully configurable 

through special parameters that can be easily programmed through the keyboard. 
 
Model 

XC10CX

 differs from the 

XC30CX

 on the digital output number. In fact, the 

XC10CX

 has only 

one digital output, which is used to control the compressor. 

3.

 

CONTROLLING LOADS 

3.1

 

COMPRESSOR 

The regulation is performed according to 
the  pressure  measured  by  the  suction 
probe P1. 
The compressor cut in is give by the 

Cin 

parameter. 
The  compressor  cut  out  is  give  by  the 

Cou 

parameter. 

Time

Press.

Compr.

COU

ON

 

In  case  of  fault  in  the  regulation  probe  the  start  and  stop  of  the  compressor  are  timed  through 
parameters 

Con

 and 

CoF

3.2

 

FAN MANAGEMENT (ONLY FOR XC30CX) 

The 

XC30CX

 is able to control 1 or 2 condenser fans. 

A direct regulation is performed (cooling). It depends on the parameters: 
 

SF1

 

Set point for fan1

 (with NTC probe: -40°C to SF2 or 40°F to SF2;  with pressure probe: 

P2i to SF2 bar/PSI/kPA) 

HF1 

Differential for fan 1 

(0.1 to 10.0°C/bar; 1 to 100°F/PSI)

 

SF2 

Set point for fan2

 (with NTC probe: SF1 to 110°C or SF1 to 230°F;  

with pressure probe: SF1 to P2E bar/PSI/kPA)

 

HF2 

Differential for fan 2 

(0.1 to 10.0°C/bar; 1 to 100°F/PSI/kPA)

 

 
A fan is switched on when the temperature (pressure) is higher than 

SF1+HF1

 and switched off when 

it comes back to 

SF1

, as explained in the following picture 

 

F1

F2

Sf2

Sf2+HF2

ZIC

Sf1 + Hf1

Sf1

 

 

3.3

 

FAN CYCLING (ONLY FOR XC30CX) 

To share the running hours between the 2 fans, the XC30CX will record the operating hours of each 
fan. The controller will rotate the fan activation and de-activation to share the operating hours between 
the 2 fans.  

 
Note

: with only one fan, it will be activated with 

T>SF1+HF1

 and switched off with 

T<SF1

4.

 

FRONT PANEL COMMANDS 

 

 

 

To display target set point; in programming mode it selects a parameter or confirm 
an operation. 

 

(RESTART) 

It depends on the 

rSC

 parameter;

 with rSC=rSt

 it allows a manual 

restart and a “dead band reset”; with 

rSC=nP

 only the dead band reset is allowed. 

 

(UP)

 To see the condenser temperature for 5 sec; in programming mode it browses 

the parameter codes or increases the displayed value. 

 

(DOWN)

 To see the 

dLt

 temperature; in programming mode it browses the 

parameter codes or decreases the displayed value. 

 

(SERVICE) 

To enter the service menu. 

 

(Alarm menu) 

To enter the Alarm menu. 

KEY COMBINATIONS: 

  

 

 

 

To lock & unlock the keyboard. 

 

+

  

 

To enter in programming mode. 

  

+

  

 

To return to the suction pressure display. 

 

4.1

 

USE OF LEDS 

Each LED function is described in the following table. 

LED 

MODE 

FUNCTION 

 

ON 

Compressor enabled 

Flashing  Anti-short cycle delay enabled 

ON 

Fan1 enabled (only for XC30CX) 

ON 

Fans enabled (only for XC30CX) 

kPA 

ON 

kPA  display 

Flashing  Programming mode 

bar 

ON 

bar display 

Flashing  Programming mode 

PSI 

ON 

PSI display 

Flashing  Programming mode 

 

ON 

You’re browsing the service menu 

 

Flashing  A new alarm happened 

ON 

You’re browsing the alarm menu 

 

ON 

An alarm is occurring 

5.

 

OTHER FUNCTIONS 

5.1

 

PRESSURE PROBE ERROR BY-PASS AT START UP 

If a pressure probe error occurs at start-up, it will be by-passed for the 

P1d

 time, and the compressor 

will be switched on when the following conditions are satisfied: 

-

 

odS

, regulation delay at start up, is expired. 

-

 

With 

di1=Y

, the thermostat digital input 14-17 is enabled. 

-

 

The

 HP

 digital input or the 

dLt

 temperature is not locking the regulation. 

In this period the controller displays the flashing label 

P1E

If during the 

P1d

 time the pressure probe error recovers, the standard regulation will start, otherwise, 

when 

P1d

 expires the pressure probe error P1 will be signaled and the compressor will be switched on 

and off cyclically with 

Con

 and 

CoF

 period. 

5.2

 

PRESSURE PROBE ERROR BY-PASS WHEN THE COMPRESSOR IS NOT 

WORKING 

When  the  compressor  is  switched  off  the  pressure  probe  error  is  not  signalled.  In  this  case  if  the 
pressure  raises  and  exceeds  the  pressure  probe  range,  the  controller  will  display  the  last  value 
flashing. 
In this situation the compressor will restart when: 

a.

 

With 

di1=Y

: the thermostat digital input (14-17) is enabled. 

b.

 

With 

di1=n

: as soon as the delays for the compressor restart are expired. 

c.

 

If the compressor was switched off because of 

HP

 safety digital input or because of a 

too high 

dLt

 temperature, it will be able to restart as soon as these conditions are 

removed.  

5.3

 

RESET DEAD BAND 

If the pressure value is in the range [

Cou

 to 

Cin

] and the compressor relay is off, it’s possible to force 

it  keeping  the 

RESTART 

key  pressed  for  2  sec.  The  compressor  will  run  till  the 

Cou

  threshold  is 

reached. 

Содержание dixell XC10CX

Страница 1: ...r fan 2 0 1 to 10 0 C bar 1 to 100 F PSI kPA A fan is switched on when the temperature pressure is higher than SF1 HF1 and switched off when it comes back to SF1 as explained in the following picture F1 F2 Sf2 Sf2 HF2 ZIC Sf1 Hf1 Sf1 3 3 FAN CYCLING ONLY FOR XC30CX To share the running hours between the 2 fans the XC30CX will record the operating hours of each fan The controller will rotate the fa...

Страница 2: ... higher than doF value the following actions will be performed a The compressor will be shut down b The display will show the dLt message alternated with suction probe c The dLt alarm counter will be increased 5 7 2 Automatic restart When the temperature detected by the dLT probe is lower than the don value the compressor will be able to restart only when both dLF and AC timers will expire If the ...

Страница 3: ... C don to 392 F don DLT temperature for compressor restart 30 0 C to doF 22 F to doF ALd Stop compressor delay 0 to 255 sec nPS Number of activation of DLT alarm in a hour to lock compressor 0 to 15 0 always automatic restart dLF Minimum time of compressor off with dLL alarm 0 to 15 min HIGH CONDENSER TEMPERATURE AU2 Condenser Temperature Pressure threshold for high alarm P2C ntC AH2 to 110 0 C AH...

Страница 4: ...be 40 to 110 C 40 to 230 F PTC 990ohm probe 50 to 150 C 58 to 302 F Resolution 0 1 C or 1 C or 1 F selectable Accuracy ambient temp 25 C 0 7 C 1 digit 16 DEFAULT SETTING VALUES LABEL RANGE XC10CX XC30CX Value Level Value Level Cin CoU to US bar PSI kPA 3 3 Pr1 3 3 Pr1 CoU LS to Cin bar PSI kPA 2 6 Pr1 2 6 Pr1 LS P1i to Cou bar PSI kPA 0 5 Pr2 0 5 Pr2 US Cin to P1E bar PSI kPA 7 0 Pr2 7 0 Pr2 odS 0...

Отзывы: