Electrical Field Connections
Liebert
®
CW
™
System Design Manual
68
Figure 6-2 Electrical field connections (Ethernet), downflow, CW026 – CW084
Top Entrance
Electric Box Bottom
Coil Support Frame
Unit Bottom
Bottom Entrance
Remove knockouts.
Low Voltage Communication Wiring
CAT5E Ethernet connections – field installed
Avoid routing near high voltage wiring.
Secure wiring to prevent damage and
use bushing or edge guard to avoid sharp edges.
Remove knockouts
to access control board.
To display
P64
1. To provide unit to unit (U2U) networking, unplug the cable
from P64 on the iCOM board and from ETH-1 on the touch
screen display. Remove the cable. The first customer
connection point will be to ETH-1 on the display.
The second customer connection point will be P64 at the iCOM
control board. Alternatively, the cable can be unplug at P64
on the iCOM control board, and plug into a straight-thru
Ethernet coupler (Not provided). The first customer connection
will be on the other side of the coupler. The second connection
will be at P64 on the iCOM control Board.
Notes:
1
1
NOTE: Refer to specification sheet for full load amp and wire size amp ratings.
MONITORING
PANEL
Front of Unit
Right side of Unit
DPN003198
Pg. 2 Rev. 1
Содержание CW089
Страница 2: ......
Страница 8: ...Liebert CW System Design Manual vi ...
Страница 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Страница 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Страница 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Страница 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Страница 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...
Страница 114: ...Optional Liebert Air Economizer for Liebert CW Liebert CW System Design Manual 104 Page intentionally left blank ...