background image

 

 

© 2017 Emerson Climate Technologies, Inc.

 

AE4-1372 R4 

Operating Envelope 

Figure

 

at  the  end  of  this  bulletin  shows  the  CO

2

 

cascade operating envelope in relation to R-410A and R-
404A. 

 

Charging Procedure 

 

Do  not  operate  compressor  without  enough  system 
charge  to  maintain  at  least  87  PSIG  (6  Bar)  suction 
pressure.  

 

Do not operate with a restricted suction.  

 

Do not operate with the low-pressure cut-out bridged. 

 
Vapor initial charge should be 145 PSIG (10 Bar). Do 
not allow a pressure under 87 PSIG (6 Bar), otherwise 
it might cause CO

2

 solidification and blocked valves or 

pipes and consequently, the scrolls may overheat and 
cause early drive bearing damage. 
 
Do not use the compressor to test the opening set point 
of the high-pressure cut-out. Bearings are susceptible to 
damage before they have had several hours of normal 
running in. Ensure charging equipment is approved for 
at least 1300 PSIG (89.6 Bar).  
 
The  system  should  be  charged  through  the  liquid-
receiver  shut-off  valve  or  through  a  valve  in  the  liquid 
line. 

The  use of  a filter  drier in the charging line is 

highly recommended. 

 
Because there may be several valves in the system it is 
recommended to charge on both the high and low sides 
simultaneously to ensure a positive refrigerant pressure 
is present in the compressor before it runs. The majority 
of the charge should be placed in the high side of the 
system  to  prevent  bearing  washout  during  first-time 
start. 
 

Deep Vacuum Operation 

Copeland Scroll compressors should never be used to 
evacuate a refrigeration or air-conditioning system. The 
scroll compressor can be used to pump down refrigerant 
in  a  unit  as  long  as  the  pressures  remain  within  the 
operating envelope. Low suction pressures will result in 
overheating of the scrolls and permanent damage to the 
compressor  drive  bearing.  ZO  scrolls  incorporate 
internal low vacuum protection, the floating seal unloads 
when the pressure ratio exceeds approximately 10:1. 

Shell Temperature 

 

The  top  shell  and  discharge  line  can  briefly  but 
repeatedly reach temperatures above 350°F (176.7 °C)  
if  the  compressor  cycles  on  its  internal  protection 
devices.  This  only  happens  under  rare  circumstances 
and can be caused by the failure of system components 
such  as  the  condenser  or  evaporator  fan  or  loss  of 
charge and depends upon the type of expansion control. 
Care  must  be  taken  to  ensure  that  wiring  or  other 
materials that could be damaged by these temperatures 
do not come in contact with the shell. 
 

Pump Down Cycle and Parallel Rack Application 

A pump down cycle  for control of refrigerant migration 
may  be  used  in  conjunction  with  a  crankcase  heater 
when the compressor is located so that cold air blowing 
over  the  compressor  makes  the  crankcase  heater 
ineffective. 
 
If a pump down cycle is used on a parallel rack system, 
a  separate  external  check  valve  must  be  added.  The 
scroll  discharge  check  valve  is  designed  to  stop 
extended  reverse  rotation  and  prevent  high-pressure 
gas  from  leaking  rapidly  into  the  low  side  after  shut-
down.  The  check  valve  will  in  some  cases  leak  more 
than  reciprocating  compressor  discharge  reeds, 
normally  used  with  pump  down,  causing  the  scroll 
compressor to recycle more frequently. Repeated short-
cycling of this nature can result in a low oil situation and 
consequent  damage  to  the  compressor.  The  low-
pressure  control  differential  must  be  reviewed  since  a 
relatively  large  volume  of  gas  will  re-expand  from  the 
high  side  of  the  compressor  into  the  low  side  on 
shutdown. 
 

Low Pressure Safety Control  

Never set the low-pressure control to shut off outside of 
the operating envelope. To prevent the compressor from 
running  into  problems  during  such  faults  as  loss  of 
charge or partial blockage, the control should not be set 
lower than -60°F (-51.1°C) equivalent suction pressure 
(80 PSIG, 5.51 bar) below the lowest design operating 
point. 

 

Minimum Run Time 

Emerson recommends a maximum of 10 starts per hour. 
There  is  no  minimum  off  time  because  scroll 
compressors  start  unloaded,  even  if  the  system  has 
unbalanced  pressures.  The  most  critical  consideration 
is  the  minimum  run  time  required  to  return  oil  to  the 
compressor after start-up. To establish the minimum run 
time, obtain a sample compressor equipped with a sight 

Содержание Copeland Scroll ZO104KCE

Страница 1: ...pecially designed rubber grommets Kit 527 0157 00 12 Figure 3 Oil Management Control OMC CO2 12 Figure 4 Suction Side Pressure Relief Valve Requirements 13 Figure 5 Three Phase Power Circuit 14 Figure 6 ZO Compressor Operating Envelope 14 Figure 7 Compressor Electrical Connection 14 Revision Tracking R4 Pg 2 New Pressure Safety Icon added Pg 4 Caution tag added to superheat requirement Pg 4 Notes ...

Страница 2: ...e safety instructions Safety Icon Explanation DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE is used to ...

Страница 3: ...and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be used Failure to follow these warning...

Страница 4: ... with R 410A air conditioning compressors which operate at similar pressure levels as CO2 compressors CO2 FOR LOW TEMPERATURE APPLICATIONS SUB CRITICAL DX SYSTEM Figure 1 at the end of this bulletin shows a cascade system diagram with HFC refrigerant for the high side and sub critical CO2 for the low stage refrigerant Nomenclature The model designation contains the following technical information ...

Страница 5: ... port on the suction Rotalock valve This port is open to the compressor sump no matter what position the valve stem is located The relief valve itself can be remotely located as long as the path from compressor suction sump and the valve is always open 2 This flow path cannot be shut off in any way by a valve Figure 4 represents the correct a and incorrect b way to apply the pressure relief valve ...

Страница 6: ...r to Figure 5 for details The terminal box is IP21 for all models from ZO21K to ZO104K The ZO Scroll compressors have three phase induction motors connected in star Copeland Scroll compressors like several other types of compressors will only compress in one rotational direction Three phase compressors will rotate in either direction depending upon phasing of the power Since there is a 50 chance o...

Страница 7: ...eatedly reach temperatures above 350 F 176 7 C if the compressor cycles on its internal protection devices This only happens under rare circumstances and can be caused by the failure of system components such as the condenser or evaporator fan or loss of charge and depends upon the type of expansion control Care must be taken to ensure that wiring or other materials that could be damaged by these ...

Страница 8: ...l or refrigerant may damage the compressor resulting in failure New Installations The copper coated steel suction tube on scroll compressors can be brazed in approximately the same manner as any copper tube Recommended brazing materials Any SIL FOS material is recommended preferably with a minimum of 5 silver However 0 silver is acceptable Be sure suction tube fitting I D and suction tube O D are ...

Страница 9: ...r may be indicated A current imbalance exceeding 20 of the average on the three phases of a three phase compressor should be investigated further A more comprehensive trouble shooting sequence for compressors and systems can be found in Section H of the Electrical Handbook Form No 6400 8 Before replacing or returning a compressor be certain that the compressor is actually defective As a minimum re...

Страница 10: ...40V 70W 32 Lead Length 995 0018 00 018 0095 04 240V 70W 48 Lead Length 918 0043 00 018 0095 05 480V 70W 48 Lead Length 918 0043 01 018 0095 06 575V 70W 48 Lead Length 918 0043 02 018 0095 07 120V 70W 48 Lead Length 918 0043 07 018 0095 08 400V 70W 48 Lead Length 018 0095 09 277V 70W 21 Lead Length Table 1 ZO Family Models Model Nominal Horse power Displacement CFH Capacity BTU HR EER Weight LB kg ...

Страница 11: ...ime Delay for Low Level Signal 10 seconds Time Delay After Setpoint Recovery 5 seconds Alarm Delay Time Including Alarm Contact 120 seconds Alar Switch SPDT Alarm Contact Rating 10A 120VAC 50 60Hz 5A 250VAC 50 60 Hz 3A 30 VDC Refrigerant Temperature 40 to 180 F 40 C to 82 2 C Maximum Ambient Temperature Storage 40 to 120 F 40 C to 48 9 C Maximum Ambient Temperature Intermittent Duty 40 to 120 F 40...

Страница 12: ... 2017 Emerson Climate Technologies Inc 12 AE4 1372 R4 Figure 3 Oil Management Control OMC CO2 Figure 2 Specially designed rubber grommets Kit 527 0157 00 ...

Страница 13: ... 2017 Emerson Climate Technologies Inc 13 AE4 1372 R4 Figure 4 Suction Side Pressure Relief Valve Requirements ...

Страница 14: ... or services described herein or their use or applicability Emerson Climate Technologies Inc and or its affiliates collectively Emerson as applicable reserve the right to modify the design or specifications of such products at any time without notice Emerson does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of...

Отзывы: