2.11.7 Fast access menu
The f ast access menu contains the list of probes and some values that are automatically evaluated
by the board such as the superheat and the percentage of valve opening.
"nP"
or
"noP"
stands f or "Probe not present" or "Value not evaluated".
"Err"
means "Value out of
range" or "Probe damaged, not connected or incorrectly configured".
Entering the fast
access menu
Press and release the
UP
arrow. In case of inactivity the
menu remains displayed for 3 minutes.
The values that will be displayed depend on the
conf iguration of the board.
Use the
or
arrow to select
an entry, then
press
to see the value
or to go on with
another value.
▪
P1P: Pressure value of the P1 probe (suction pressure)
▪
P2t: Temperature value of the P2 probe (not valid)
▪
P2P: Pressure value of the P2 probe (discharge pressure)
▪
P3t: Temperature value of the P3 probe (discharge line
temperature)
▪
P4t: Temperature value of the P4 probe = not available
▪
P5t: Temperature value of the P5 probe = not available
▪
P6t: Temperature value of the P6 probe (ambient temperature)
▪
P7t: Temperature value of the P7 probe (free)
▪
SH: Value of superheat. nA = not available
▪
oPP: Percentage of step valve opening = not available
▪
LInJ: Status of the liquid line solenoid (
"
On
"
–
"
Off
"
). This information
is available only if one relay is set as
"
Liquid Line Solenoid
"
.
▪
SEtd: Value of the dynamic setpoint (condenser f an SET). This
inf ormation is available only if the dynamic setpoint f unction is
enabled.
▪
AOO: Percentage of the analogue output (0-10 V or TRIAC PWM
Mod.). This inf ormation is available only if the 0-10 V or TRIAC PWM
Mod. is enabled.
▪
dSO: Percentage of the PWM output driving the valve of the digital
scroll compressor
▪
L°t: Minimum room temperature
▪
H°t: Maximum room temperature
▪
HM: Menu
▪
tU1: Voltage reading V1
▪
tU2: Voltage reading V2
▪
tU3: Voltage reading V3
▪
tA1: Current reading I1
▪
tA2: Current reading I2
Exit
Press simultaneously or wait for the timeout of about
60 seconds
Table 16: Fast access menu
2.12 Controller keyboard
2.12.1 How to lock the keyboard
Keep the
and
keys pressed simultaneously for more than 3 seconds. The
"PoF"
message
will be displayed and the keyboard will be locked. At this point it is only possible to see the setpoint
or the maximum or minimum temperatures stored. If a key is pressed for more than 3 seconds, the
"PoF"
message will be displayed.
2.12.2 How to unlock the keyboard
Keep the
and
keys pressed simultaneously for more than 3 seconds, till the
"Pon"
message
is displayed.