Appendix 6: Additional features for customization
Required setting for proper functionality
Setting needs to be adjusted according to application
Temperature sensor in case temperature
– System restart is required!
Parameters
Parameter description
Factory setting
Required setting
ZXDE
ZXDI
A19
P7C
Probe 7 configuration
nu = Not used
tnt = Thermostat temperature
C05
LS
Compressor regulation probe selection
SuP = Suction pressure
probe
CSt = Case temperature
G01
EcS
Case temperature probe selection
nu = Not used
tnt = Thermostat temperature
G02
SEt
Cut-out temperature
+2°C
Adjust to application requirements
G03
Hy
Positive differential defines upper cut-in temperature
1K
Adjust to application requirements
Unit On/Off
– System restart is required!
Parameters
Parameter description
Factory setting
Required setting
ZXDE
ZXDI
R07
i3F
Digital input 3 configuration
nu = Not used
OnF = On/Off
R08
i3P
Digital input 3 polarity
CL = Closed
Adjust to application requirements
Evaporator fan
– System restart is required!
Parameters
Parameter description
Factory setting
Required setting
ZXDE
ZXDI
G42
FnC
Fans operating mode
cn
cn = Switch on and off with the compressor, stop
during defrost
On = Always on, stop during defrost
cy = Switch on and off with the compressor, run
during defrost
Oy = Always on, run during defrost
S05
oA2
Relay output 2
nu = Not used
EPF = Evaporator fan
G45
Fon
Fan on time
1 min
Adjust to application requirements
G46
FoF
Fan off time
1 min
Adjust to application requirements
G55
Fnd
Fan delay after defrost
1 min
Adjust to application requirements