C6.1.10/0118-0318/E
15
2.11.6 Entering programming level 2 "Pr2"
To enter the Pr2 programming menu:
▪
Press
simultaneously for 3 seconds. The first parameter label will be displayed.
▪
Press
till the
T18
label is displayed, then press the
key;
▪
The blinking
PaS
label will be displayed; wait for a few seconds;
▪
The display will show "
0 - -
" with blinking 0: insert the password [
321
] using the
and
keys and confirming with the
key.
2.11.7 Fast access menu
This menu contains the list of probes and some values that are automatically evaluated by the
board such as the superheat and the percentage of valve opening.
nP
or
noP
stands for "probe
not present" or "value not evaluated",
Err
means "value out of range", "probe damaged, not
connected or incorrectly configured".
Entering fast access
menu
Press and release the
UP
arrow. The duration of the
menu in case of inactivity is 3 minutes.
The values that will be displayed depend on the
configuration of the board.
Use the
or
arrow to select
an entry, then
press
to see the value
or to go on with
another value.
▪
P1P: Pressure value of the P1 probe (suction pressure)
▪
P2t: Temperature value of the P2 probe (not valid)
▪
P2P: Pressure value of the P2 probe (discharge pressure)
▪
P3t: Temperature value of the P3 probe (discharge line
temperature)
▪
P4t: Temperature value of the P4 probe (not applicable)
▪
P5t: Temperature value of the P5 probe (not applicable)
▪
P6t: Temperature value of the P6 probe (ambient temperature)
▪
P7t: Temperature value of the P7 probe (free)
▪
SH: Value of superheat. nA = not available
▪
oPP: Percentage of step valve opening.
▪
SEtd: Value of the dynamic setpoint (condenser fan SET). This
information is available only if the dynamic setpoint function is
enabled.
▪
AOO: Percentage of the analog output (0-10V or TRIAC PWM
Mod.). This information is available only if the 0-10V or TRIAC PWM
Mod. is enabled.
▪
dStO: Percentage of the PWM output driving the valve of the Digital
Scroll compressor.
▪
L°t: Minimum room temperature.
▪
H°t: Maximum room temperature.
▪
HM: Menu.
▪
tU1: Voltage reading V1 (not valid in standard configuration)
▪
tU2: Voltage reading V2 (not valid in standard configuration)
▪
tU3: Voltage reading V3 (not valid in standard configuration)
▪
tA1: Current reading I1
▪
tA2: Current reading I2
Exit
Press simultaneously or wait for the timeout of about
60 seconds
Table 15: Fast access menu
2.12 Controller keyboard
2.12.1 How to lock the keyboard
Keep the
and
keys pressed simultaneously for more than 3 seconds. The
"PoF"
message
will be displayed and the keyboard will be locked. At this point it is only possible to see the setpoint
or the maximum or minimum temperatures stored. If a key is pressed for more than 3 seconds,
the
"PoF"
message will be displayed.
S
afet
y
inst
ru
ctio
n
s
P
ro
d
u
ct
d
es
cr
ipt
ion
Inst
all
atio
n
S
tar
ting
up
&
o
p
er
atio
n
Ma
int
enan
c
e &
repai
r
Cer
tif
ica
tion
&
a
pp
ro
va
l
Dismant
ling
&
d
ispo
sa
l
Содержание Copeland EazyCool ZXDI Series
Страница 1: ...Copeland EazyCool Indoor Condensing Units ZXDI Range Application Guidelines ...
Страница 5: ......