C6.1.9/0219/E
39
Appendix 1: Parameter list level 1 (Pr1)
Code
Description
Range
MT
LT
C07
Refrigerant selection for
regulation
R404A(0-404) - R507(1-507) - R134A(2-134) - R22(3-R22) -
R407C(4-07C) - R407A(5-07A) - R407F(6-07F) -
R448A(48A) - R449A(8-49A) - R410A(9-410)
8-R449A
8-R449A
C16
Digital compressor setpoint
C03 to C04
3.0
1.0
C17
Proportional band for
compressor regulation
0.1 to 9.9 bar; 0.1 to 99.9 PSI;
0.1°C to 25.5°C
2.0
1.0
C21
Cycle time for digital
compressor
10 to 40 sec
10
10
C24
Minimum capacity for digital
compressor
0 to C25
10
10
C27
Time with DGS at PMi
before switching off another
load
0 to 255 sec
10
5
D29
Low-pressure alarm value
A02 to A03
0.8
0.3
E66
Delta temperature
condenser floating setpoint
0.0°C to 25.5°C
8.0
8.0
N01
Current minute
0 to 59
N02
Current hour
0 to 23
N03
Day of month
1 to 31
N04
Month
1 to 12
N05
Year
0 to 99
T18
Access to Pr2 level
[0÷999]
3 2 1
3 2 1
Table 22: Parameters level 1