AGL_Stream_ST_4MTL_4MSL_E_Rev01
5
2.4 Application range
2.4.1 Qualified refrigerant and oil
Stream CO
2
compressors are delivered with POE oil. Large models (4MTL-35 to 4MTL-50) can
alternatively be delivered on request with PAG oil.
Oil recharge values can be taken from Copeland
™ brand products Select software available at
Qualified refrigerant
R744 (CO
2
)
Copeland brand
products standard oils
Emkarate RL 68 HB (POE 68)
Zerol RFL 68 EP (PAG 68)*
Qualified servicing oils
Emkarate RL 68 HB (POE 68)
Zerol RFL 68 EP (PAG 68)*
Factory oil charge
(litres)
Medium
temp
Low
temp
Medium
temp
Low
temp
Medium
temp
4MTL-05
4MTL-07
4MTL-09
4MSL-03
4MSL-04
4MSL-06
4MTL-12
4MTL-15
4MTL-30
4MSL-08
4MSL-12
4MSL-15
4MTL-35
4MTL-40
4MTL-50
1.3
1.8
2.5
* Optional and for large models only
Table 3: Qualified refrigerant and oils & factory oil charges
To recharge:
▪
When the compressor is completely empty of oil, the amount of oil to be "recharged" is typically
0.12 litre less than the original oil charge (oil will already be present in the system).
To top up:
▪
During commissioning, planned maintenance or servicing, add oil so that the compressor oil level
is between min ¼ and max ¾ of side sight glasses and full in the housing cover sight glass.
▪
Recommended quality for carbon dioxide purity class: 4.0 [(
≥ 99.99 %) H
2
O ≤ 10 ppm,
O
2
≤ 10 ppm, N
2
≤ 50 ppm] or higher.
2.4.2 Application limits
WARNING
Oil dilution due to low superheat! Compressor breakdown!
Low suction
superheat leads to oil dilution. Always operate the system with adequate
superheat to avoid oil viscosity decrease. Additional measures in system
design might help to avoid inacceptable lubrication conditions.
The operating envelopes of transcritical and subcritical StreamCO
2
compressors are shown below.
Figure 3: Operating envelopes for transcritical applications with R744
– Models 4MTL-05 to 4MTL-15