background image

 

TI_Unit_CO2_Stream_04_EN_Rev00 

Ident number 3293976 (P/N 900-0010-00/Rev00) 

1/3

 

Date of last update: Aug-22 

 

Ref: TI_Unit_CO2_Stream_04_EN_Rev00 

 

 

Application Engineering Europe 

C

OPELAND

 

CO

2

 

R

EFRIGERATION 

U

NITS

 

C

HANGEOVER 

V

ALVE 

S

ERVICE 

K

IT

 

 

This  technical  information  provides  instructions  for  the  replacement  of  the  changeover  valve  on  Copeland  CO

2

 

refrigeration units. These instructions are valid only for Copeland CO

2

 refrigeration units with M24x1.5 thread on the 

PRV’s connected to the liquid receiver through the changeover valve. If the pressure relief valves (PRV’s) cannot be 
disassembled  from  the  changeover  valve,  it  is  necessary  to replace  the  complete  assembly  (changeover  valve  + 
PRV

’s). The PRV version with metric thread M24x1.5 cannot be used anymore. The PRV on the high-pressure side 

is not affected by this change. 

The service kit N°3290262 includes the components shown in the table below. 

Components 

Description 

Quantity 

Ident & Part 

number 

Valve-Change-Over 1/2"NPT 

Changeover valve 

3290262 

510-1018-00 

Valve-Safety assm 90 bar 

Pressure relief valve (PRV) 

3288776 

(510-0902-01) 

User manual - CV Kit 

Instruction 

3293976 

(900-0010-00) 

Table 1: BOM of changeover valve service kit 

 
When replacing 

the changeover valve including PRV’s, the instructions in this technical information must be carefully 

followed. Use the recommended torque at each step. 

Only qualified and authorized HVAC or  refrigeration personnel are permitted to conduct the changes described in 
this technical information. All appropriate safety measures must be considered. 

Replacement of changeover valve: 

  Release all the pressure/refrigerant from the unit 

(Figure 1)

  Disassemble the changeover valve from the liquid receiver 

(Figure 2)

  Connect a nitrogen hose to the liquid receiver so that no thread debris can fall into it 

(Figure 3)

  Clean the liquid receiver thread 

(Figure 3)

  

  

 

Figure 1   

                Figure 2   

 

 

 

     

    Figure 3

 

 

 