1.5 Power Supply/Sequencer Module (PSSM)
Note:
If you need redundant power supply capabilities, you can install
a Redundant Power Supply/Sequencer Module (RPSSM)
instead
of
the PSSM. For details on the RPSSM, see
Appendix P
.
The Power Supply/Sequencer module (PSSM) takes power from an
external bulk DC power supply and then provides power through the
ControlWave housing/backplane to all installed modules.
The PSSM operates from +22.2 to +30V (dc) and ships from the factory
with a nominal input supply configuration of 24V.
The PSSM includes:
ON/OFF system power switch
Pluggable terminal block to connect the external power supply
Watchdog output connector to signal a watchdog failure to an
external device
Status LEDs
Chapter 2
includes instructions for installing and configuring the PSSM.
1.6 I/O Modules
The ControlWave supports analog input, analog output, digital input,
digital output, universal digital input, isolated RTD, and isolated low
level analog input modules for either local or remote field device wiring
termination.
Refer to
Chapter 3
for information on specific I/O modules.
shows a typical I/O module housing.
Terminations are pluggable and accept a maximum wire size of #14
AWG. All I/O modules have surge protection that meets either C37.90-
1978 or 472-1978 IEEE specifications.
Each I/O module connects to the backplane using a 110-pin male
connector and to its associated terminal block assembly using a 44 pin
header.