System Installation
Centellis 2000 Shelf Release 3.0 Installation and Use (6806800L99F
)
58
Procedure
To install a system into a standard 19" ANSI rack, proceed as follows:
1. Insert the system into a standard 19" ANSI rack.
2. Fasten the system to the rack via the integrated chassis mounting flanges using two
bolts or screws (minimum 6 mm (0.24 inch) in diameter) on the left side and two
on the right side of the system.
3. Make sure that the system has been placed in a location at room temperature for at
least 24 hours before powering it up.
The following clearances are required when installing the system into an at least 600 mm
(23.62 inch) deep rack. The physical dimensions in the figure below are in millimeters. Make
sure that 60% of the rack's rear is open.
Figure 3-1
Rack Mounting Dimensions
Содержание Centellis 2000 Shelf Release 3.0
Страница 8: ...Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 8 ...
Страница 10: ...Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 10 List of Tables ...
Страница 12: ...Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 12 List of Figures ...
Страница 20: ...Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F About this Manual 20 About this Manual ...
Страница 40: ...System Overview Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 40 ...
Страница 52: ...Site Preparation Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 52 ...
Страница 87: ...FRU Installation Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 87 ...
Страница 106: ...Non Field Replaceable Units Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 106 ...
Страница 108: ...Cooling Subsystem Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 108 ...
Страница 116: ...Power Subsystem Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 116 ...
Страница 146: ...Redundancy Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 146 ...
Страница 154: ...Software Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 154 ...
Страница 158: ...Troubleshooting Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 158 ...
Страница 174: ...Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F Safety Notes 174 ...
Страница 188: ...Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F Sicherheitshinweise 188 ...
Страница 192: ...Index Centellis 2000 Shelf Release 3 0 Installation and Use 6806800L99F 192 ...
Страница 193: ......