Section 6: Actuator Configuration
6.2.14
Blinker / Local Selector Configuration
The default configuration for Blinker / Local Selector relay is off (always Open). In Blinker
configuration the relay changes its status every 500msec (Motor Running function) as the
actuator is moving. In Local Selector configuration (with Local Interface OM3 installed), the
relay is CLOSED when OM3 switch is on REMOTE and the relay is OPEN when OM3 switch is
on LOCAL.
To configure Blinker or Local Selector monitoring function (when OM3 is present):
•
Enter setup configuration: move switch SW3 to position ON (configuration function)
•
Move switch SW4 to position 4
•
Move switch SW6 to position 1 (Blinker) or 2 (Local Selector)
•
Confirm by pushing ENTER pushbutton SW5
•
When pushing SW5, the red LED switches on for confirmation
•
Exit setup configuration (move switchSW3 to position 1) or proceed to the
next parameter
6.2.15
Three-Wires (3-Wires) / Two-Wires (2-Wires)
Remote Control Configuration
The SCE300 default remote control configuration is a Three-Wires (3-Wires)
Remote Control
3-Wires configuration operation
•
Command on terminal 35 to OPEN,
•
Command on terminal 36 to CLOSE
2-Wires configuration operation
•
Command present on terminal 35 to OPEN,
•
Command absent on terminal 35 to CLOSE;
•
Terminal 36 not used
To configure Remote Control parameter:
•
Enter set up configuration: move switch SW3 to position ON (configuration function)
•
Move switch SW4 to position 9
•
Move switch SW6 to position 5 (3-WIRES) or 6 (2-WIRES)
•
Confirm by pushing ENTER pushbutton SW5
•
When pushing SW5, the red LED switches on for confirmation
•
Exit set up configuration (move switch SW
3 to position 1) or proceed with the
next parameter