Actuator Configuration
Section 6: Actuator Configuration
6.2.11
Configuration of the Torque Limiting Device in Opening
Opening torque limits are 50%, 75% and 100% of the nominal torque. The nominal torque
corresponding to 100% is set in-house and is stated on the nameplate.
•
Enter setup configuration: move switch SW3 to position ON (configuration function)
•
Move SW4 switch to position 7
•
Move switch SW6 to positions 2,5 or 9 for the requested torque value
(in percentage) in opening
•
Push ENTER pushbutton SW5 to confirm
•
When pushing SW5, the red LED switches on for confirmation
•
The setting of the torque limiting device in opening is now complete
•
Exit setup configuration (move switch SW3 to position 1) or proceed to the
next parameter
NOTICE
Consult the valve manufacturer torque specifications for correct limit torque configuration.
WARNING
Installation, configuration, commissioning, maintenance, and repairs must be performed
by approved and qualified personnel only.
6.2.12
Reverse Mode Configuration
•
Enter setup configuration: move switch SW3 to position ON (configuration function)
•
Move switch SW4 to position 8
•
Move switch SW6 to position:
—
1 counter-clockwise (CCW) ON
—
0 counter-clockwise (CCW) OFF
•
Push ENTER pushbutton SW5 to confirm
•
When pushing SW5, the red LED switches on for confirmation
•
Reverse mode (CCW) set is now completed
•
Exit setup configuration (move switch SW3 to position 1) or proceed to the
next parameter