36
February 2020
Installation and Maintenance Instructions
MAN-02-04-99-0712-EN Rev. 1
Actuator Configuration
Section 6: Actuator Configuration
6.2.9
Stroking Time Selection in Opening
•
Enter setup configuration: move switch SW3 to position ON (configuration function)
•
Move switch SW4 to position 5
•
Move switch SW6 to positions 4, 6, 8 for the requested stroking time according to
the table below
•
Push ENTER pushbutton SW5 to confirm
•
When pushing SW5, the red LED switches on for confirmation
•
The selected stroking time in opening is now set
•
Exit setup configuration (move switch SW3 to position 1) or proceed to the
next parameter
Table 6.
Operating Times
Model
Nominal torque
(Nm / lb.ft)
Operating time (secs 90°) at selected step
8
6
4
063/E006
63/46
15
28
48
125/E013
125/92
15
28
48
250/E025
250/184
15
28
48
500/E051
500/369
15
28
48
1000/E091
1000/738
24
45
80
2000/E171
2000/1475
53
100
180
NOTE:
Time is guaranteed with +/- 10% tolerance on 90° stroke
6.2.10
Setting of the Torque-Limiting Device in Closing
Closing torque limits are 50%, 75% and 100% of the nominal torque. The nominal torque
corresponding to 100% is set in-house and is stated on the nameplate.
•
Enter setup configuration: move switch SW3 to position ON (configuration function)
•
Move switch SW4 to position 6
•
Move switch SW6 to positions 2, 5 or 9 for the requested torque value
(in percentage) in closing
•
Push ENTER pushbutton SW5 to confirm
•
When pushing SW5, the red LED switches on for confirmation
•
The setting of the torque limiting device in closing stroke is now complete
•
Exit setup configuration (move switch SW3 to position 1) or proceed to the
next parameter
NOTICE
Consult the valve manufacturer torque specifications for correct limit torque configuration.
WARNING
Installation, configuration, commissioning, maintenance, and repairs must be performed
by approved and qualified personnel only.