background image

Warning

Attempts to adjust and/or repair this product 
by unauthorized or unqualified persons void the 
product warranty and may cause damage to 
equipment and serious injury or death to persons.

This product is a safety related component 
intended for use in critical applications. The 
improper application, installation or maintenance 
of the valve or the use of parts or components not 
manufactured by Emerson may result in a failure 
of the valve.

anderson greenWood

 Safety Selector valveS (Spool Style)

InstallatIon and operatIonal safety InstructIons

installation

Many valves are damaged when first placed 
in service because of failure to clean the 
connection properly when installed. Before 
installation, all flange faces or threaded 
connections on both the SSv and the 
connecting components (vessel, pipe or 
pressure relief valve) must be thoroughly 
cleaned of all dirt and foreign material.

Because foreign materials that pass into and 
through the SSv can damage the seat, the 
systems on which the valves are tested and 
finally installed must also be inspected and 
cleaned. New systems in particular are prone 
to contain foreign objects that inadvertently get 
trapped during construction and will destroy 
the seating surface when the valve flows. the 
system should be thoroughly cleaned before 
the SSv is installed.

general

the intent of these instructions is to acquaint 
the user with the storage, installation and 
operation of this product.

this Safety Selector valve (SSv) should only 
be used in accordance with the applicable 
operating instructions and within the application 
specifications of the purchase order.

storage and handling

Because cleanliness is essential to the 
satisfactory operation and tightness of an SSv, 
precautions should be taken during storage to 
keep out all foreign materials. Inlet and outlet 
protectors should remain in place until the 
valve is ready to be installed in the system. It is 
recommended that the valve be stored indoors 
in the original shipping container away from dirt 
and other forms of contamination.

the SSv should be handled with care and not 
subjected to heavy shocks.

Before installation these instructions must be fully read and understood

© 2017 emerson. all rights reserved.

emerson.com/FinalControl

VCosi-01063-en 17/12

the gaskets used must be dimensionally correct 
for the specific flanges. the inside diameters 
must fully clear the valve inlet and outlet 
openings so that the gasket does not restrict flow.

for flanged valves, draw down all connection 
studs or bolts evenly to avoid possible distortion 
of the valve body.

the SSv ‘s are shipped from the factory with 
one side completely “isolated” and one side 
“active”. the position indicator points to the 
“active” side. check that the “active” side is 
correct for the initial installation and start-
up operation. See operatIoN below for 
instructions to change.
the SSv is designed to minimize inlet pressure 
loss to a pressure relief valve. to assure this is 
accomplished follow these guidelines:
1.  connect the SSv as direct and close as 

possible to the vessel being protected.

2.  the SSv should be mounted vertically in an 

upright position either directly on a nozzle 
from the pressure vessel or on a short 
connection fitting that provides a direct, 
unobstructed flow between the vessel and 
the valve.

3.  the SSv should never be installed on a 

fitting having a smaller inside diameter 
than the inlet connection of the SSv.

the discharge piping should be carried by a 
separate support and be properly braced to 
withstand reactive thrust forces when the 
pressure relief valve relieves. the SSv should 
also be supported to withstand any swaying or 
system vibrations.

Any installation, maintenance, adjustment, repair 
or test, performed on the safety selector valve 
must be done in accordance with the requirements 
of all applicable Emerson Procedures and 
Instructions as well as applicable National and 
International Codes and Standards.

The information, specifications and technical data 
(the “Specifications”) contained in this document 
are subject to change without notice. Emerson 
does not warrant that the Specifications are 
current and assumes no responsibility for the 
use or misuse thereof. The Purchaser should 
verify that there have been no changes to the 
Specifications prior to use.