Quick ad-hoc network tests to isolate issues
You can use the Trex unit to connect to various connection points on the fieldbus segment
to isolate an issue. For example, if the device fails to power due to a low-voltage at its
terminals, use the Fieldbus Diagnostics application to measure the voltage at all cable
connection points between the power supply and the device. These measurements can
help you identify the section of cable or junction box where the voltage drop occurs.
Long-term tests to catch sporadic issues
If a device has issues for only part of the day, you can take measurements over a period of
time to capture the time/date the issue occurs. For example, if you notice sporadic
increases in noise, you can take a measurement for multiple hours to determine when the
issue is occurring. This can help you relate the noise with another event, such as a variable-
frequency drive starting and stopping throughout the day.
Periodic tests to help you track your network and create trends
You can take measurements every few months to create an overall trend/report for the
fieldbus segment. For example, you can create one set of measurements when a device is
installed, and another set of measurements a year later for comparison. This can help you
track any slow degradation of the fieldbus segment.
The Fieldbus Diagnostics application has a logging feature that lets you save one or more
sets of measurements to a comma-separated values (.csv) log file. The files can then be
transferred to a PC for further review and analysis in a spreadsheet program.
5.1
Open or close the Fieldbus Diagnostics
application
1.
To open Fieldbus Diagnostics, tap the Fieldbus Diagnostics icon on the Trex
Home
screen.
2.
To close Fieldbus Diagnostics, tap
Exit
.
5.2
Fieldbus Diagnostics Overview screen
The Fieldbus Diagnostics Overview screen is the home screen for the application. The
screen displays the status of the measurements and lets you configure the application.
Note
The
Power supply
option is not displayed if the Trex unit has the Device Communicator
communication module. The Device Communicator Plus communication module and FOUNDATION
fieldbus Power Plug are required to power a FOUNDATION fieldbus device.
Fieldbus Diagnostics application
150
User Guide
Содержание AMS Trex
Страница 1: ...User Guide Rev 3 August 2017 AMS Trex Device Communicator User Guide ...
Страница 8: ...Contents vi User Guide ...
Страница 130: ...Field Communicator application 122 User Guide ...
Страница 186: ...Fieldbus Diagnostics application 178 User Guide ...
Страница 198: ...Technical specifications 190 User Guide ...
Страница 206: ...Glossary 198 User Guide ...