Option
Description
Power Positioner with other mA value
Power a positioner with a specified mA
value.
4.
Tap
OK
.
5.
To change the current being supplied by the Trex unit, do one of the following:
•
Tap a quick current button.
•
Tap the up or down arrow keys to slowly increase or decrease the current. The
default increment is 0.1 mA.
•
Tap the pencil icon to set a mA value.
6.
Wait for the valve to move.
7.
Repeat steps 5 and 6 until the valve moves through all the required positions.
8.
To stop powering the device, do one of the following:
•
Tap
Trex Unit Power
to set the option to
OFF
. You are prompted to select a power
option to set the position of the valve.
•
Tap
Exit
. You are prompted to select a power option to set the position of the
valve.
•
Remove the lead set from the Trex unit. You are
not
prompted to select a power
option to set the position of the valve.
4.10
Settings for controlling current
4.10.1
Change the values for the quick buttons
The Loop Diagnostics screen has five buttons that have default values of 4 mA, 8 mA, 12
mA, 16 mA, and 20 mA. These buttons let you quickly change the current. You can change
the value for each button.
Loop Diagnostics application
User Guide
141