Table 4-5 Size 4 and larger input current, fuse and cable size ratings
Installation class (ref: IEC60364-5-52:2001)
B1 - Separate cables in conduit.
B2 - Multicore cable in conduit
C - Multicore cable in free air.
Cable sizes are from IEC60364-5-52:2001 table A.52.C with correction
factor for 40°C ambient of 0.87 (from table A52.14) for cable installation
method B2 (multicore cable in conduit).
Only PVC insulated cables should be used.
Cable size may be reduced if a different installation method is used, or if
the ambient temperature is lower.
The recommended cable sizes above are only a guide. The mounting
and grouping of cables affects their current-carrying capacity, in some
cases smaller cables may be acceptable but in other cases a larger
cable is required to avoid excessive temperature or voltage drop. Refer
to local wiring regulations for the correct size of cables.
N
The recommended output cable sizes assume that the motor maximum
current matches that of the drive. Where a motor of reduced rating is
used the cable rating may be chosen to match that of the motor. To
ensure that the motor and cable are protected against overload, the
drive must be programmed with the correct motor rated current.
N
UL listing is dependent on the use of the correct type of UL-listed fuse,
and applies when symmetrical short-circuit current does not exceed
100kA. See Chapter 14
on page 264 for sizing
information.
A fuse or other protection must be included in all live connections to the
AC supply.
An MCB (miniature circuit breaker) or MCCB (moulded-case circuit-
breaker) with type C may be used in place of fuses on sizes 1 to 3 under
the following conditions:
•
The fault-clearing capacity must be sufficient for the installation
•
For frame sizes 2 and 3, the drive must be mounted in an enclosure
which meets the requirements for a fire enclosure (For details
regarding fire enclosures see section 3.2.6
on page 264 for UL listing
requirements.
Fuse types
The fuse voltage rating must be suitable for the drive supply voltage.
Ground connections
The drive must be connected to the system ground of the AC supply.
The ground wiring must conform to local regulations and codes of
practice.
4.7.1 Main AC supply contactor
The recommended AC supply contactor type for sizes 1 to 6 is AC1.
Model
Typical input
current
Maximum
input current
Fuse option 1
Fuse option 2
semiconductor fuse in series
with HRC fuse or breaker
Cable size
IEC class
gR
North
America:
Ferraz HSJ
HRC
IEC class gG
UL class J
Semi-
conductor
IEC class aR
EN60204
UL508C
A
A
A
A
A
A
Input
mm
2
Output
mm
2
Input
AWG
Output
AWG
BA4201
62.1
68.9
100
90
90
160
25
25
3
3
BA4202
72.1
78.1
100
100
100
160
35
35
3
3
BA4203
94.5
99.9
125
125
125
200
70
70
1
1
BA5201
116
142
200
175
160
200
95
95
2/0
2/0
BA5202
137
165
250
225
200
250
120
120
4/0
4/0
BA4401
61.2
62.3
80
80
80
160
25
25
3
3
BA4402
76.3
79.6
110
110
100
200
35
35
2
2
BA4403
94.1
97.2
125
125
125
200
70
70
1
1
BA5401
126
131
200
175
160
200
95
95
2/0
2/0
BA5402
152
156
250
225
200
250
120
120
4/0
4/0
BA6401
224
241
315
300
250
315
2 x 70
2 x 70
2 x 2/0
2 x 2/0
BA6402
247
266
315
300
300
350
2 x 95
2 x 95
2 x 4/0
2 x 4/0
BA4601
23
26.5
63
60
32
125
4
4
10
10
BA4602
26.1
28.8
63
60
40
125
6
6
8
8
BA4603
32.9
35.1
63
60
50
125
10
10
8
8
BA4604
39
41
63
60
50
125
16
16
6
6
BA4605
46.2
47.9
63
60
63
125
16
16
6
6
BA4606
55.2
56.9
80
60
63
125
25
25
4
4
BA5601
75.5
82.6
125
100
90
160
35
35
2
2
BA5602
89.1
94.8
125
100
125
160
50
50
1
1
BA6601
128
138
200
200
200
200
2 x 50
2 x 50
2 x 1
2 x 1
BA6602
144
156
200
200
200
200
2 x 50
2 x 50
2 x 1
2 x 1