background image

6

 

© 2018 Emerson Climate Technologies, Inc.

 

AEX-XXXX 

PRELIMINARY 

AE8-1384 R6

 

 

 

Once  the  module  has  locked  out  the  compressor,  a 
power cycle or Modbus reset command will be required 
to clear the lockout.

 

 

Code 3 - Short Cycling

 

The  module  will  flash  the  red 

Alert 

LED  three  times 

indicating  the  compressor  is  locked  out  due  to  short 
cycling.  A  Code  3 

Alert 

will  open  the  M2-M1  contacts. 

Code  3  will  be  enabled  when  the  “Short  Cycling” 
dipswitch  (#10)  is  “on”  or  in  the  “up”  position  and  the 
compressor  has  exceeded  the  number  of  short  cycles 
configured  by  the  user  in  a  24  hour  period.  Once  the 
module  has  locked  out  the  compressor,  a  power  cycle 
or Modbus reset command will be required to clear the 
lockout.

 

 

Code 4 - Scroll High Temperature

 

The  module  will  flash  the  red 

Alert

  LED  four  times 

indicating the scroll NTC circuit is less than 2.4K Ohms. 
A  Code  4 

Alert

  will  open  the  M2-M1  contacts.  The 

Alert 

will  reset  after  30  minutes  and  the  M2-M1 

contacts  will  close  if  the  resistance  of  the  scroll  NTC 
circuit  is  higher  than  5.1K  Ohms.  The  module  will 
lockout the compressor if the number of Code 4 

Alerts

 

exceeds  the  user  configurable  number  of  Code  4 
events  within  a  24  hour  period.  Once  the  module  has 
locked  out  the  compressor,  a  power  cycle  or  Modbus 
reset command will be required to clear the lockout. 

 

Code 5 - Reserved for Future Use 

Code 6 - Missing Phase

 

The  module  will  flash  the  red 

Alert

  LED  six  times 

indicating  a  missing  phase  in  one  of  the  three  leads  to 
the  compressor.  A  Code  6 

Alert

  will  open  the  M2-M1 

contacts.  The 

Alert

  will  reset  after  5  minutes  and  the 

M2-M1 contacts will close if the missing phase condition 
is not present.

 

 

Code 7 - Reverse Phase

 

The  module  will  flash  the  red 

Alert

  LED  seven  times 

indicating  a  reverse  phase  in  two  of  the  three  leads     
to  the  compressor.  A  Code  7 

Alert

  will  open  the  M2- 

M1  contacts.  The  module  will  lockout  the  compressor 
after one Code 7

 Alert

. A power cycle or Modbus reset 

command will be required to clear the lockout.

 

 

Code 8 - Reserved for Future Use

 

Code 9 - Module Low Voltage

 

The  module  will  flash  the  red 

Alert 

LED  nine  times 

indicating low module  voltage (see 

Table 2

) on the T2- 

T1  terminals  for  more  than  5  seconds.  A  Code9 

Alert 

will open the M2-M1 contacts. The 

Alert 

will reset after 

5 minutes and the M2-M1 contacts will close if the T2-T1 
voltage is above the reset value in 

Table 2

.

 

 

Please see 

Table 6 

for a summary of 

Warning 

and 

Alert

 

codes and troubleshooting information.

 

Resetting Alert Codes

 

Resetting 

Alert 

codes can be accomplished in two different 

ways. First, 

Alert 

codes can be reset manually by cycling 

power to the module (disconnect T2 or T1 for 5 seconds). 
The second way to reset 

Alert 

codes is to send a Modbus 

reset command from the master controller.

 

Power Up Delay

 

When  CoreSense  Communications  is  cycled  off,  there   
is a thirteen to fifteen second delay before the module is 
active.

 

If the fault that initiated the 

Alert 

code is absent after one 

of  the  above  resets  is  performed,  the 

Alert 

code  will  be 

cleared and CoreSense will allow normal operation. If the 
fault  is  still  present  after  the  reset  is  performed  the  fault 
code  will  continue  to  be  displayed  via  the  green  or  red 
flashing LED.

 

COMMISSIONING

 

Communications

 

Programming knowledge and a familiarity with 
Modbus will be required by the system designer 
to use the communications features of CoreSense 
Communications. CoreSense Communications

 

has opto-isolated RS485 for the physical layer. The 
communication protocol is Standard Modbus and 
Emerson Modbus. CoreSense Communications will 
act as the Modbus slave, while the master will be 
implemented in a system controller, PC software, or 
any other equivalent external device. Use of the 
communications feature of CoreSense 
Communications allows the master access to much of

 

the data that resides in the CoreSense Communications 
module. Emerson Modbus has  six message 
categories:

 

1.  Device ID Messages

 

2.  CoreSense Status Messages

 

Содержание AE8-1384 R6

Страница 1: ...ion 4 Product Specifications 4 Installation Mounting 4 Terminal Description and Basic Field Wiring 4 Dielectric Hipot Testing 5 Operation Warning Codes 5 Alert Lockout Codes 5 Resetting Alert Codes 6 Section Page Commissioning Communications 6 DIP Switch Configuration 7 Jumper Setting 7 PC Interface Software 7 Service Field Service 8 Troubleshooting 8 Tables Module Part Numbers 9 Module Specificat...

Страница 2: ...etained throughout the lifetime of the compressor You are strongly advised to follow these safety instructions Safety Icon Explanation DANGER indicates a hazardous situation which if not avoided will result in death or WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol indicates a hazardous situation which ...

Страница 3: ...t electrically locking out the system Use only approved refrigerants and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury WARNING BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system comp...

Страница 4: ...ended to be used as field retrofits for other motor protection modules that may have been previously used with Copeland Scroll compressors The motor and scroll thermistor circuits are configured differently for Copeland Scroll with CoreSense Communications and are not compatible with motor protection modules that were previously used Copeland Scroll compressors equipped with CoreSense Communicatio...

Страница 5: ...e module has not communicated with the master controller for longer than 5 minutes Once communication is reinitiated the Warning will be cleared Code 2 Reserved For Future Use Code 3 Short Cycling The module will flash the green Warning LED three times indicating the compressor has short cycled more than 48 times in 24 hours A short cycle is defined as compressor runtime of less than 3 minutes The...

Страница 6: ...compressor after one Code 7 Alert A power cycle or Modbus reset command will be required to clear the lockout Code 8 Reserved for Future Use Code 9 Module Low Voltage The module will flash the red Alert LED nine times indicating low module voltage see Table 2 on the T2 T1 terminals for more than 5 seconds A Code9 Alert will open the M2 M1 contacts The Alert will reset after 5 minutes and the M2 M1...

Страница 7: ... CoreSense Communications module that is daisy chained and connected to a master controller must have a unique node address as determined by the DIP switch settings 2 Switch 6 defines the communication baud rate for the CoreSense Communications module If the switch is off the baud rate is 19200 If the switch is on the baud rate is 9600 The baud rate of each CoreSense Communications module should b...

Страница 8: ... Copeland Scrolls with one exception the scroll thermistor is a negative temperature coefficient NTC type thermistor This means that as the dis charge temperature increases the resistance of the thermistor decreases The motor has positive temperature coefficient PTC type thermistors as the motor temperature increases so does the resistance of the thermistor chain To measure the resistance of the P...

Страница 9: ...ption 5 VA 5 VA M1 M2 Contact Rating 2 5A Max 2 5A Max Motor Temperature Trip Resistance 4 5KΩ 25 4 5KΩ 25 Open Motor Thermistor Trip Resistance 220KΩ 220KΩ Shorted Motor Thermistor Trip Resistance 40Ω 40Ω Temperature Reset Resistance 2 75KΩ 2 75KΩ Scroll Temperature Trip Resistance 2 4KΩ 2 4KΩ Open Scroll Thermistor Trip Resistance 370KΩ 370KΩ Shorted Scroll Thermistor Trip Resistance 1KΩ 1KΩ Scr...

Страница 10: ...4 320 ASSET Model Number 18 36 332 CoreSense Module Serial Number 11 22 33D Division Name 29 58 35A Product Code 9 18 363 Product Name 7 14 36A Product type 1 2 36B Endian Convention 1 2 36C Dip switch Setting 2 2 Unused 18 bytes 380 Alarm Code 1 2 0 Normal Operation 1 Loss of Communication to E2 2 Open OR Short Spare Thermister Warning 3 Open OR Short Scroll Thermister Warning 4 Short Cycle Warni...

Страница 11: ...us OK 1 Not OK 0 0x0100 Pilot Voltage Status OK 1 Not OK 0 385 Scroll Temperature Value 2 2 Scroll High Temp Sensor Value Range 0 C to 655 36 C 387 Spare Temperature Value 2 2 Spare Temp Sensor Value Range 0 C to 655 36 C 389 Pilot Voltage Value 2 2 Pilot Voltage Value Range 0 to 655 36 V Unused 117 bytes 400 Ten most recent alarms with time stamp 40 60 428 Compressor run history with cumulative c...

Страница 12: ...er Location 17 34 115 Customer Name 17 34 126 Compressor Model Number Modified 18 36 138 Compressor serial number 12 24 144 Application code 3 6 147 Temperature code 4 8 14B Refrigerant code 7 14 152 Functional Configuration 2 2 154 Compressor run time to count as short cycle 1 2 155 Scroll High Temp Trip 2 2 157 Scroll High Temp Reset 2 2 15A Future Use 1 2 15B Future Use 2 2 15D Future Use 2 2 1...

Страница 13: ...code 3 6 147 Temperature code 4 8 14B Refrigerant code 7 14 152 Functional Configuration 2 2 154 Compressor run time to count as short cycle 1 2 Range 1 min to 6 min 3 155 Scroll High Temp Trip 2 2 Range 110 deg C to 150 deg C 140 157 Scroll High Temp Reset 2 2 Note Reset set point value should be always Trip set point value 30 deg C 15A Future Use 1 2 15B Future Use 2 2 15D Future Use 2 2 15F No ...

Страница 14: ...Information Solid Green Normal Operation Module is powered and operation is normal N A N A Solid Red Module Malfunction Module has internal fault N A 1 Reset module by removing power from T2 T1 2 Replace module Warning LED Flash Green Flash Code 1 Loss of Communication Module and master controller have lost communications with each other for more than 5 minutes When communications are confirmed 1 ...

Страница 15: ... Red Flash Code 4 Scroll High Temperature Ω 2 4K Lockout if the number of Alerts exceeds the number configured by the user in 24 hours Interrupt power to T2 T1 or perform Modbus reset command 1 Check system charge and superheat 2 Check system operating conditions 3 Check for abnormally low suction pressure Red Flash Code 5 Future Use N A N A N A Red Flash Code 6 Missing Phase Missing phase After 5...

Страница 16: ...TE DEBERÁN RESPETAR LAS APROBACIONES DE LA AGENCIA REGLAMENTARIA PARA EL PRODUCTO FINAL PROTECCIÓNCONTRACICLOSCORTOS ACTIVADO DESACTIVADO VEALAPLACADE DATOS 02 14 052 2895 00 WARNING PRECAUCIÓN WARNING PRECAUCIÓN WARNING PRECAUCIÓN WARNING PRECAUCIÓN WARNING PRECAUCIÓN NORMAL NORMAL TYPE TIPO TRIP DISPARO TYPE TIPO EVENT EVENTO ALERT CODE RED CODIGO DE ALERTA ROJO SOLID SOLIDO 1 2 3 4 5 6 7 8 9 1 ...

Страница 17: ...Y AE8 1384 R6 Figure 2 CoreSense Communications Module View A Terminal identification is from the end of the plug View A Figure 3 Thermistor Circuit Cable Scroll NTC Thermistor black wire Motor PTC Thermistor red wire Common Connection blue wire Spare Connection ...

Страница 18: ...nologies Inc AEX XXXX PRELIMINARY AE8 1384 R6 0 11 1 12 2 13 3 14 4 15 5 16 6 17 7 18 8 19 9 20 10 21 Switch 1 2 3 4 5 On Off 22 23 24 25 26 27 28 29 30 31 Figure 4 Modbus Addressing Switch 1 2 3 4 5 Switch 1 2 3 4 5 On Off On Off ...

Страница 19: ... services described herein or their use or applicability Emerson Climate Technologies Inc reserves the right to modify the designs or specifications of such products at any time without notice Emerson Climate Technologies Inc does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any Emerson Climate Technologies...

Отзывы: