background image

5

 

© 2018 Emerson Climate Technologies, Inc.

 

AEX-XXXX 

PRELIMINARY 

AE8-1384 R6

 

 

 

NOTICE

 

CAUTION

 

WARNING

 

M2-M1: 

Normally open control circuit contacts; M2-M1 

should be wired in series with the compressor contactor.

 

A (+), GND, B (-)

: RS485 communications.

 

Temperature Plug

: See 

Figure 3 

for identification of the

 

PTC, NTC, and common connections.

 

When multiple CoreSense Communications modules are 
networked, a shielded, twisted pair cable such as Belden

 

#8761 (22 AWG) should be used for the communication

 

wiring.

 

 

 

The RS485 is polarity sensitive. When “daisy 
chaining” modules the A (+) must connect to other 
A (+) terminals and B (-) must connect to other B (-) 
terminals.

 

 

Dielectric (Hipot) Testing

 

 

 

Use caution with high voltage and never hipot when 
compressor is in a vacuum.

 

U.L.  sets  the  requirement  for  dielectric  strength  testing 
and should  be consulted for the appropriate voltage and 
leakage values. Emerson Climate Technologies does not 
recommend  hipot  testing  at  voltages  higher  than  1,000 
VAC.

 

 

OPERATION

 

 

 

The CoreSense Communications module is a 
recognized safety device and must be used with all 
compressors that have TE* electrical codes.

 

 

A solid  green LED indicates the module is  powered and 
operation is normal. A solid red LED indicates an internal 
problem  with  the  module.  See  the 

Troubleshooting

 

section of this bulletin for more information on what to do if 
the red LED is solid.

 

 

CoreSense Communications communicates 

Warning 

codes via a green flashing LED. Warning codes do not 
result in a trip or lockout condition. 

Alert

 codes are 

communicated via a red flashing LED. Alert codes

 

will result in a trip condition and possibly a lockout 
condition.

 

Warning Codes (Green LED Flash Code)

 

Code 1 - Loss of Communication

 

The module will flash the green 

Warning 

LED one 

time indicating the module has not communicated 
with the master controller for longer than 5 minutes. 
Once communication is reinitiated, the 

Warning 

will 

be cleared.

 

Code 2 - Reserved For Future Use 

Code 3 - Short Cycling

 

The module will flash the green 

Warning 

LED three times 

indicating the compressor has short cycled more than 48 
times in 24 hours. A short cycle is defined as compressor 
runtime  of  less  than  3  minutes.  The 

Warning 

will  be 

activated  when  the  “Short  Cycling”  dipswitch  (#10)  is 
“off” or in the “down” position. When fewer than 48 short 
cycles are accumulated  in  24  hours the 

Warning 

code 

will be cleared.

 

Code 4 - Open/Shorted Scroll Thermistor

 

The module will flash the green 

Warning 

LED four  times 

indicating  the  scroll  NTC  thermistor  has  a  resistance 
value  that  indicates  an  open/shorted  thermistor  (see 

Table  2

).  The 

Warning 

will  be  cleared  when  the 

resistance value is in the normal range.

 

 

Alert/Lockout Codes (Red LED Flash Code)

 

Code 1 - Motor High Temperature

 

The  module  will  flash  the  red 

Alert 

LED  one  time 

indicating  the  motor  PTC  circuit  has  exceeded  4.5K 
Ohms  ±  25%.  A  code  1 

Alert 

will  open  the  M2-M1 

contacts.  The 

Alert 

will  reset  after  30  minutes  and  the 

M2-M1 contacts will close if the resistance of the motor 
PTC  circuit  is  below  2.75K  Ohms.  Five  consecutive 
Code  1 

Alerts 

will  lockout  the  compressor.  Once  the 

module has locked out the compressor, a power cycle or 
Modbus reset command will be required for the lockout 
to be cleared.

 

Code 2 - Open/Shorted Motor Thermistor

 

The module will flash the red 

Alert 

LED two times 

indicating the motor PTC thermistor circuit has a 
resistance value that indicates an open/shorted 
thermistor chain (see 

Table 2

). A Code 2 Alert will 

open the M2-M1 contacts.  The 

Alert 

will reset after 

30 minutes and the M2-M1 contacts will close if the 
resistance of the motor PTC circuit is back in the 
normal range. The module will lockout the compressor 
if the trip condition exists for longer than 6 hours

 

WARNING

 

CAUTION

 

NOTICE

 

Содержание AE8-1384 R6

Страница 1: ...ion 4 Product Specifications 4 Installation Mounting 4 Terminal Description and Basic Field Wiring 4 Dielectric Hipot Testing 5 Operation Warning Codes 5 Alert Lockout Codes 5 Resetting Alert Codes 6 Section Page Commissioning Communications 6 DIP Switch Configuration 7 Jumper Setting 7 PC Interface Software 7 Service Field Service 8 Troubleshooting 8 Tables Module Part Numbers 9 Module Specificat...

Страница 2: ...etained throughout the lifetime of the compressor You are strongly advised to follow these safety instructions Safety Icon Explanation DANGER indicates a hazardous situation which if not avoided will result in death or WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol indicates a hazardous situation which ...

Страница 3: ...t electrically locking out the system Use only approved refrigerants and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury WARNING BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system comp...

Страница 4: ...ended to be used as field retrofits for other motor protection modules that may have been previously used with Copeland Scroll compressors The motor and scroll thermistor circuits are configured differently for Copeland Scroll with CoreSense Communications and are not compatible with motor protection modules that were previously used Copeland Scroll compressors equipped with CoreSense Communicatio...

Страница 5: ...e module has not communicated with the master controller for longer than 5 minutes Once communication is reinitiated the Warning will be cleared Code 2 Reserved For Future Use Code 3 Short Cycling The module will flash the green Warning LED three times indicating the compressor has short cycled more than 48 times in 24 hours A short cycle is defined as compressor runtime of less than 3 minutes The...

Страница 6: ...compressor after one Code 7 Alert A power cycle or Modbus reset command will be required to clear the lockout Code 8 Reserved for Future Use Code 9 Module Low Voltage The module will flash the red Alert LED nine times indicating low module voltage see Table 2 on the T2 T1 terminals for more than 5 seconds A Code9 Alert will open the M2 M1 contacts The Alert will reset after 5 minutes and the M2 M1...

Страница 7: ... CoreSense Communications module that is daisy chained and connected to a master controller must have a unique node address as determined by the DIP switch settings 2 Switch 6 defines the communication baud rate for the CoreSense Communications module If the switch is off the baud rate is 19200 If the switch is on the baud rate is 9600 The baud rate of each CoreSense Communications module should b...

Страница 8: ... Copeland Scrolls with one exception the scroll thermistor is a negative temperature coefficient NTC type thermistor This means that as the dis charge temperature increases the resistance of the thermistor decreases The motor has positive temperature coefficient PTC type thermistors as the motor temperature increases so does the resistance of the thermistor chain To measure the resistance of the P...

Страница 9: ...ption 5 VA 5 VA M1 M2 Contact Rating 2 5A Max 2 5A Max Motor Temperature Trip Resistance 4 5KΩ 25 4 5KΩ 25 Open Motor Thermistor Trip Resistance 220KΩ 220KΩ Shorted Motor Thermistor Trip Resistance 40Ω 40Ω Temperature Reset Resistance 2 75KΩ 2 75KΩ Scroll Temperature Trip Resistance 2 4KΩ 2 4KΩ Open Scroll Thermistor Trip Resistance 370KΩ 370KΩ Shorted Scroll Thermistor Trip Resistance 1KΩ 1KΩ Scr...

Страница 10: ...4 320 ASSET Model Number 18 36 332 CoreSense Module Serial Number 11 22 33D Division Name 29 58 35A Product Code 9 18 363 Product Name 7 14 36A Product type 1 2 36B Endian Convention 1 2 36C Dip switch Setting 2 2 Unused 18 bytes 380 Alarm Code 1 2 0 Normal Operation 1 Loss of Communication to E2 2 Open OR Short Spare Thermister Warning 3 Open OR Short Scroll Thermister Warning 4 Short Cycle Warni...

Страница 11: ...us OK 1 Not OK 0 0x0100 Pilot Voltage Status OK 1 Not OK 0 385 Scroll Temperature Value 2 2 Scroll High Temp Sensor Value Range 0 C to 655 36 C 387 Spare Temperature Value 2 2 Spare Temp Sensor Value Range 0 C to 655 36 C 389 Pilot Voltage Value 2 2 Pilot Voltage Value Range 0 to 655 36 V Unused 117 bytes 400 Ten most recent alarms with time stamp 40 60 428 Compressor run history with cumulative c...

Страница 12: ...er Location 17 34 115 Customer Name 17 34 126 Compressor Model Number Modified 18 36 138 Compressor serial number 12 24 144 Application code 3 6 147 Temperature code 4 8 14B Refrigerant code 7 14 152 Functional Configuration 2 2 154 Compressor run time to count as short cycle 1 2 155 Scroll High Temp Trip 2 2 157 Scroll High Temp Reset 2 2 15A Future Use 1 2 15B Future Use 2 2 15D Future Use 2 2 1...

Страница 13: ...code 3 6 147 Temperature code 4 8 14B Refrigerant code 7 14 152 Functional Configuration 2 2 154 Compressor run time to count as short cycle 1 2 Range 1 min to 6 min 3 155 Scroll High Temp Trip 2 2 Range 110 deg C to 150 deg C 140 157 Scroll High Temp Reset 2 2 Note Reset set point value should be always Trip set point value 30 deg C 15A Future Use 1 2 15B Future Use 2 2 15D Future Use 2 2 15F No ...

Страница 14: ...Information Solid Green Normal Operation Module is powered and operation is normal N A N A Solid Red Module Malfunction Module has internal fault N A 1 Reset module by removing power from T2 T1 2 Replace module Warning LED Flash Green Flash Code 1 Loss of Communication Module and master controller have lost communications with each other for more than 5 minutes When communications are confirmed 1 ...

Страница 15: ... Red Flash Code 4 Scroll High Temperature Ω 2 4K Lockout if the number of Alerts exceeds the number configured by the user in 24 hours Interrupt power to T2 T1 or perform Modbus reset command 1 Check system charge and superheat 2 Check system operating conditions 3 Check for abnormally low suction pressure Red Flash Code 5 Future Use N A N A N A Red Flash Code 6 Missing Phase Missing phase After 5...

Страница 16: ...TE DEBERÁN RESPETAR LAS APROBACIONES DE LA AGENCIA REGLAMENTARIA PARA EL PRODUCTO FINAL PROTECCIÓNCONTRACICLOSCORTOS ACTIVADO DESACTIVADO VEALAPLACADE DATOS 02 14 052 2895 00 WARNING PRECAUCIÓN WARNING PRECAUCIÓN WARNING PRECAUCIÓN WARNING PRECAUCIÓN WARNING PRECAUCIÓN NORMAL NORMAL TYPE TIPO TRIP DISPARO TYPE TIPO EVENT EVENTO ALERT CODE RED CODIGO DE ALERTA ROJO SOLID SOLIDO 1 2 3 4 5 6 7 8 9 1 ...

Страница 17: ...Y AE8 1384 R6 Figure 2 CoreSense Communications Module View A Terminal identification is from the end of the plug View A Figure 3 Thermistor Circuit Cable Scroll NTC Thermistor black wire Motor PTC Thermistor red wire Common Connection blue wire Spare Connection ...

Страница 18: ...nologies Inc AEX XXXX PRELIMINARY AE8 1384 R6 0 11 1 12 2 13 3 14 4 15 5 16 6 17 7 18 8 19 9 20 10 21 Switch 1 2 3 4 5 On Off 22 23 24 25 26 27 28 29 30 31 Figure 4 Modbus Addressing Switch 1 2 3 4 5 Switch 1 2 3 4 5 On Off On Off ...

Страница 19: ... services described herein or their use or applicability Emerson Climate Technologies Inc reserves the right to modify the designs or specifications of such products at any time without notice Emerson Climate Technologies Inc does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any Emerson Climate Technologies...

Отзывы: