INTRODUCTION

 

Overview

 

Co

reSense™  Communications  is  a  breakthrough 

innovation  for  20  to  40    ton  Copeland 

Scroll™  air 

conditioning 

compressors. 

The 

CoreSense 

Communications  module,  installed  in  the  compressor 
electrical box, provides advanced diagnostics, protection, 
and 

communications 

that 

enhance 

compressor 

performance and reliability.

 

 

Features

 

CoreSense Communications has the following key    

features: 

1.  Motor temperature protection

 

2.  Scroll high temperature protection

 

3.  Missing phase protection

 

4.  Reverse phase protection

 

5.  Low control circuit voltage protection

 

6.  Short cycling detection and alert

 

7.  Communication to system controller through 

RS485/Modbus

 

8.  Storage of operational history, runtime information, 

fault counters, etc.

 

9.  Display of status, warning, and alert information 

via LEDs

 

CoreSense  Communications  provides  compressor  and 
system protection through its proprietary lockout feature. 
Depending on the severity and frequency of the fault that 
caused the trip condition, the CoreSense Communications 
module can lockout the compressor contactor to prevent 
damage to the compressor and system components. Less 
severe fault conditions resulting in an occasional trip will 
not result in a lockout condition.

 

 

Flashing  red  and  green  LEDs  communicate 

Status, 

Warning, 

and 

Alert 

codes to the service technician and 

the master controller.

 

 

Application Usage

 

 

 

CoreSense Communications modules are not 
interchangeable with any other brand of motor 
protection module that may have been previously 
used with Copeland Scroll compressors.

 

 

CoreSense Communications modules are not intended 
to be used as field retrofits for other motor protection 
modules that may have been previously used with 
Copeland Scroll compressors. The motor and scroll

 

thermistor circuits are configured differently for Copeland 
Scroll  with  CoreSense  Communications  and  are  not 
compatible  with  motor  protection  modules  that  were 
previously used.

 

Copeland  Scroll  compressors  equipped  with  CoreSense 
Communications will have an 

E

” in the electrical code. An 

example is the 40-ton scroll, ZP485KCE-T

E

D.

 

 

Module Part Numbers

 

OEM  and  service  compressors  will  have  the  CoreSense 
Communications  module  installed  in  the  compressor 
electrical  box.  Individually  packaged  modules  are 
available  to  the  aftermarket  for  component  replacement. 
Part numbers for OEM and service applications are listed 
in 

Table 1

 at the end of this bulletin.

 

 

Agency Recognition

 

CoreSense Communications carries the following agency 
recognitions:

 

U.L. file E253322, Volume 7, Software Class B 
CB Test Certificate

 

 

Product Specifications

 

CoreSense specifications are  shown  in  

Table  2.  

Many 

of the electrical specifications are the same as previously 
used electronic motor protection modules.

 

 

INSTALLATION

 

 

Mounting

 

As  mentioned  above,  CoreSense  Communications  will 
be shipped already installed in the compressor electrical 
box.  Two holding  tabs  secure  the  module  in  the  box.  To 
remove the module depress the holding tabs and remove 
the module.

 

 

 

Always  disconnect  and  lockout  the  power  supply 
before removing the compressor electrical box cover 
for servicing.

 

 

Terminal Description and Basic Field Wiring

 

Figure 2 

at the end of this bulletin shows the CoreSense 

Communications  module. 

Figures  1a

  and 

1b

  are  the 

terminal  box  wiring  diagrams.  An  explanation  of  the 
terminal designations follows:

 

T2-T1

: Module power supply, 24 or 120/240 VAC.

 

L1-L2-L3

: Phase inputs corresponding to compressor 

input power L1-L2-L3.

 

WARNING

 

WARNING

 

Содержание AE8-1384 R6

Страница 1: ...ion 4 Product Specifications 4 Installation Mounting 4 Terminal Description and Basic Field Wiring 4 Dielectric Hipot Testing 5 Operation Warning Codes 5 Alert Lockout Codes 5 Resetting Alert Codes 6 Section Page Commissioning Communications 6 DIP Switch Configuration 7 Jumper Setting 7 PC Interface Software 7 Service Field Service 8 Troubleshooting 8 Tables Module Part Numbers 9 Module Specificat...

Страница 2: ...etained throughout the lifetime of the compressor You are strongly advised to follow these safety instructions Safety Icon Explanation DANGER indicates a hazardous situation which if not avoided will result in death or WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol indicates a hazardous situation which ...

Страница 3: ...t electrically locking out the system Use only approved refrigerants and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury WARNING BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system comp...

Страница 4: ...ended to be used as field retrofits for other motor protection modules that may have been previously used with Copeland Scroll compressors The motor and scroll thermistor circuits are configured differently for Copeland Scroll with CoreSense Communications and are not compatible with motor protection modules that were previously used Copeland Scroll compressors equipped with CoreSense Communicatio...

Страница 5: ...e module has not communicated with the master controller for longer than 5 minutes Once communication is reinitiated the Warning will be cleared Code 2 Reserved For Future Use Code 3 Short Cycling The module will flash the green Warning LED three times indicating the compressor has short cycled more than 48 times in 24 hours A short cycle is defined as compressor runtime of less than 3 minutes The...

Страница 6: ...compressor after one Code 7 Alert A power cycle or Modbus reset command will be required to clear the lockout Code 8 Reserved for Future Use Code 9 Module Low Voltage The module will flash the red Alert LED nine times indicating low module voltage see Table 2 on the T2 T1 terminals for more than 5 seconds A Code9 Alert will open the M2 M1 contacts The Alert will reset after 5 minutes and the M2 M1...

Страница 7: ... CoreSense Communications module that is daisy chained and connected to a master controller must have a unique node address as determined by the DIP switch settings 2 Switch 6 defines the communication baud rate for the CoreSense Communications module If the switch is off the baud rate is 19200 If the switch is on the baud rate is 9600 The baud rate of each CoreSense Communications module should b...

Страница 8: ... Copeland Scrolls with one exception the scroll thermistor is a negative temperature coefficient NTC type thermistor This means that as the dis charge temperature increases the resistance of the thermistor decreases The motor has positive temperature coefficient PTC type thermistors as the motor temperature increases so does the resistance of the thermistor chain To measure the resistance of the P...

Страница 9: ...ption 5 VA 5 VA M1 M2 Contact Rating 2 5A Max 2 5A Max Motor Temperature Trip Resistance 4 5KΩ 25 4 5KΩ 25 Open Motor Thermistor Trip Resistance 220KΩ 220KΩ Shorted Motor Thermistor Trip Resistance 40Ω 40Ω Temperature Reset Resistance 2 75KΩ 2 75KΩ Scroll Temperature Trip Resistance 2 4KΩ 2 4KΩ Open Scroll Thermistor Trip Resistance 370KΩ 370KΩ Shorted Scroll Thermistor Trip Resistance 1KΩ 1KΩ Scr...

Страница 10: ...4 320 ASSET Model Number 18 36 332 CoreSense Module Serial Number 11 22 33D Division Name 29 58 35A Product Code 9 18 363 Product Name 7 14 36A Product type 1 2 36B Endian Convention 1 2 36C Dip switch Setting 2 2 Unused 18 bytes 380 Alarm Code 1 2 0 Normal Operation 1 Loss of Communication to E2 2 Open OR Short Spare Thermister Warning 3 Open OR Short Scroll Thermister Warning 4 Short Cycle Warni...

Страница 11: ...us OK 1 Not OK 0 0x0100 Pilot Voltage Status OK 1 Not OK 0 385 Scroll Temperature Value 2 2 Scroll High Temp Sensor Value Range 0 C to 655 36 C 387 Spare Temperature Value 2 2 Spare Temp Sensor Value Range 0 C to 655 36 C 389 Pilot Voltage Value 2 2 Pilot Voltage Value Range 0 to 655 36 V Unused 117 bytes 400 Ten most recent alarms with time stamp 40 60 428 Compressor run history with cumulative c...

Страница 12: ...er Location 17 34 115 Customer Name 17 34 126 Compressor Model Number Modified 18 36 138 Compressor serial number 12 24 144 Application code 3 6 147 Temperature code 4 8 14B Refrigerant code 7 14 152 Functional Configuration 2 2 154 Compressor run time to count as short cycle 1 2 155 Scroll High Temp Trip 2 2 157 Scroll High Temp Reset 2 2 15A Future Use 1 2 15B Future Use 2 2 15D Future Use 2 2 1...

Страница 13: ...code 3 6 147 Temperature code 4 8 14B Refrigerant code 7 14 152 Functional Configuration 2 2 154 Compressor run time to count as short cycle 1 2 Range 1 min to 6 min 3 155 Scroll High Temp Trip 2 2 Range 110 deg C to 150 deg C 140 157 Scroll High Temp Reset 2 2 Note Reset set point value should be always Trip set point value 30 deg C 15A Future Use 1 2 15B Future Use 2 2 15D Future Use 2 2 15F No ...

Страница 14: ...Information Solid Green Normal Operation Module is powered and operation is normal N A N A Solid Red Module Malfunction Module has internal fault N A 1 Reset module by removing power from T2 T1 2 Replace module Warning LED Flash Green Flash Code 1 Loss of Communication Module and master controller have lost communications with each other for more than 5 minutes When communications are confirmed 1 ...

Страница 15: ... Red Flash Code 4 Scroll High Temperature Ω 2 4K Lockout if the number of Alerts exceeds the number configured by the user in 24 hours Interrupt power to T2 T1 or perform Modbus reset command 1 Check system charge and superheat 2 Check system operating conditions 3 Check for abnormally low suction pressure Red Flash Code 5 Future Use N A N A N A Red Flash Code 6 Missing Phase Missing phase After 5...

Страница 16: ...TE DEBERÁN RESPETAR LAS APROBACIONES DE LA AGENCIA REGLAMENTARIA PARA EL PRODUCTO FINAL PROTECCIÓNCONTRACICLOSCORTOS ACTIVADO DESACTIVADO VEALAPLACADE DATOS 02 14 052 2895 00 WARNING PRECAUCIÓN WARNING PRECAUCIÓN WARNING PRECAUCIÓN WARNING PRECAUCIÓN WARNING PRECAUCIÓN NORMAL NORMAL TYPE TIPO TRIP DISPARO TYPE TIPO EVENT EVENTO ALERT CODE RED CODIGO DE ALERTA ROJO SOLID SOLIDO 1 2 3 4 5 6 7 8 9 1 ...

Страница 17: ...Y AE8 1384 R6 Figure 2 CoreSense Communications Module View A Terminal identification is from the end of the plug View A Figure 3 Thermistor Circuit Cable Scroll NTC Thermistor black wire Motor PTC Thermistor red wire Common Connection blue wire Spare Connection ...

Страница 18: ...nologies Inc AEX XXXX PRELIMINARY AE8 1384 R6 0 11 1 12 2 13 3 14 4 15 5 16 6 17 7 18 8 19 9 20 10 21 Switch 1 2 3 4 5 On Off 22 23 24 25 26 27 28 29 30 31 Figure 4 Modbus Addressing Switch 1 2 3 4 5 Switch 1 2 3 4 5 On Off On Off ...

Страница 19: ... services described herein or their use or applicability Emerson Climate Technologies Inc reserves the right to modify the designs or specifications of such products at any time without notice Emerson Climate Technologies Inc does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any Emerson Climate Technologies...

Отзывы: