background image

CPHE_65008__R05 

Replacement for 04

 

 

Operating Instructions

Pressure Regulator

CPHE and ACP

Description and Technical Data: 

Regulators are used to avoid permanent on/off 
cycling of compressor or to keep evaporating 
temperatures above certain levels 

 

Can be installed in any position. 

 

Intended for use with CFC, HCFC, HFC 

 

Adjustable from:   CPHE -0,4 to 5 bar 

 

 

 

ACP: 0 to 5 bar 

 

Factory setting:  

CPHE: 1,4 bar 

 

 

 

ACP: 2,7 bar 

 

Max. allowable pressure PS:   CPHE: 35 bar 

 

 

 

ACP 31 bar 

 

Medium temperature range TS: -40°C to 120°C 

 

Ambient temperature range:   -40 to 50°C 

 

Transport temperature range:  -40 to 70°C 

 

Marking:  

 

 

 

   

Safety Instructions:

 

 

 

Read installation instructions thoroughly. 

Failure to comply can result in device failure, 
system damage or personal injury. 

 

It is intended for use by persons having the 
appropriate knowledge and skill. Before 
attempting to install the regulator, make sure 
pressure in system is brought to and remains at 
atmospheric pressure.  

 

Do not release any refrigerant into the 
atmosphere. 

 

Do not use any other fluid media without prior 
approval of Alco Controls. Use of fluid not 
listed could result in change of Hazard 

Category of the product and consequently 
change of conformity assessment requirement 
for product in accordance with European 

Pressure Equipement Directive 97/23/EC. 

 

In a severely contaminated system, avoid 
breathing acid vapours and avoid contact with 
skin from contaminated refrigerant / lubricants. 
Failure to do so could result in skin injury. 

 

CPHE and ACP are not released for use with 
flammable refrigerants such as hydrocarbon 
refrigerants and ammonia. 

 

The CPH(E) regulator’s power assembly and 
cage assembly must be removed before 
soldering. 

Installation and Mounting: 

Two typical installation applications are possible: 
Hot Gas Bypass to the evaporator inlet (with up to 
100% of capacity control) per Fig. 1 
Hot Gas Bypass to the suction line (max. 40% of 
capacity control  

because of oil return 

capability) per Fig. 2 

 

Pressure regulators can be installed in any position. 

 

Direction of flow must match arrow on body. 

 

Before brazing clean tubing. 

 

CPHE:

 Remove power assembly and cage before 

brazing. 

 

ACP:

 Do not disassemble valve before brazing. 

 

Use wet rags or chill blocks when brazing to 
prevent valve damage.

Do not

Direct flame away from valve body (Fig. 3). 
Use an inert gas such as nitrogen to pass through 
the valve to prevent

 

The use of appropriate brazing material is required 
(soft solder is not allowed).

 

Never use 

 

Internal parts must be protected from foreign 
material and moisture. ALCO filter
liquid line and ALCO filter use in suction line is 
recommended.

 

Install the external equalizer line to the compressor 
suction line alw
pressure regulators. NEVER join the equalizer line 
with another control except of the Liquid Injection 
Valve.

Setting:

If desired set point differs from factory setting, 
follow the procedure for setting before any 
installatio
below
The function of the CPHE and ACP series regulators 
is to prevent the suction pressure from falling below 
a predetermined set point, thereby balancing the 
system. Therefore, the first step after installation is 
to determine this set point for the minimum suction 
pressure allowable for your application. To do so, 
follow this procedure:

 

Start the system and determine if it is operating 
properly. Install a gauge on the compressor suction 
line and measure the suction
system has stabilized. To make sure, that hot gas is 
not bypassed de

 

Remove the seal cap (1) and turn the power 
assembly adjusting stem (2) full 
COUNTERCLOCKWISE.

 

Reduce the evaporator load until the sucti
pressure lowers to the point at which bypass is 
desired.

 

Energize hot gas solenoid to enable gas flow.

 

Turn the power assembly adjusting stem on top of 
the regulator in a CLOCKWISE direction until 
bypass occurs and suction pressure does not fall 
below t
CLOCKWISE turn of the adjusting stem will 
increase the pressure setting; a 
COUNTERCLOCKWISE turn will decrease it. 
Adjustments should be made in small increments, 
allowing the system to stabilize after each turn.

Do not

regulator (only CPHE). This screw should only be 
used when working in a vacuum temperature range

 

Vary evaporator load to test at various conditions 
that the suction pressure does not fall below the 
predetermined set point

 

CPHE: Replace the seal cap (1) on the adjusting 
stem (Fig 4).

 

ACP: replace plastic cap

!

Replacement for 04 

Date: 20.06.2013 

DWG Nr.: CPH EZ 005000/PCN  863003

Operating Instructions 

Pressure Regulator 

CPHE and ACP 

GB

 

Emerson Climate Technologies GmbH

Holzhauser Str. 180  -  D-13509 Berlin

Germany 

www.emersonclimate.eu

 

 

Use wet rags or chill blocks when brazing to 
prevent valve damage. 

 

Do not

 

exceed max. body temperature of 120°C.

 

Direct flame away from valve body (Fig. 3).  
Use an inert gas such as nitrogen to pass through 
the valve to prevent copper oxide formation. 
The use of appropriate brazing material is required 
(soft solder is not allowed).

 

Never use oxygen or flammable gases. 

 

Internal parts must be protected from foreign 
material and moisture. ALCO filter-drier use in 
liquid line and ALCO filter use in suction line is 
recommended. 
Install the external equalizer line to the compressor 
suction line always downstream from evaporator 
pressure regulators. NEVER join the equalizer line 
with another control except of the Liquid Injection 
Valve. 

Setting: 

If desired set point differs from factory setting, 
follow the procedure for setting before any 
installation and/or refer to the Adjustment Table 
below: 
The function of the CPHE and ACP series regulators 
is to prevent the suction pressure from falling below 
a predetermined set point, thereby balancing the 
system. Therefore, the first step after installation is 
to determine this set point for the minimum suction 
pressure allowable for your application. To do so, 
follow this procedure: 

Start the system and determine if it is operating 
properly. Install a gauge on the compressor suction 
line and measure the suction pressure after the 
system has stabilized. To make sure, that hot gas is 
not bypassed de-energize the hot gas solenoid. 
Remove the seal cap (1) and turn the power 
assembly adjusting stem (2) full 
COUNTERCLOCKWISE. 
Reduce the evaporator load until the suction 
pressure lowers to the point at which bypass is 
desired. 
Energize hot gas solenoid to enable gas flow. 
Turn the power assembly adjusting stem on top of 
the regulator in a CLOCKWISE direction until 
bypass occurs and suction pressure does not fall 
below the predetermined set point. A 
CLOCKWISE turn of the adjusting stem will 
increase the pressure setting; a 
COUNTERCLOCKWISE turn will decrease it. 
Adjustments should be made in small increments, 
allowing the system to stabilize after each turn. 

Do not

 turn adjustment screw on the side of the 

regulator (only CPHE). This screw should only be 
used when working in a vacuum temperature range 

Vary evaporator load to test at various conditions 
that the suction pressure does not fall below the 
predetermined set point. 
CPHE: Replace the seal cap (1) on the adjusting 
stem (Fig 4). 
ACP: replace plastic cap 

NOTES: 

 

On multiple evaporator systems, do not pipe hot 
gas to more than one evaporator. Use separate 
bypass regulators or consult the ALCO 
Applications Engineering De

 

If the compressor is located above the evaporator, 
bypass should be piped to the evaporator to insure 
proper oil return during low load bypass 
conditions. 

 

On a long piping run, bypass to the evaporator, 
insulate the bypass to prevent condensate. 

Condensate can lead to unstable conditions and 

or flooding of the compressor.

Solenoid Connections

 

If a compressor discharge line thermostat is used, 
it is recommended that the solenoid 
series with the thermostat.

 

Voltage and frequency of the c
to the power source. Connect leads to the power 
source.    
(NEVER wire on the load side of the motor 
starter.) 

Note 1: For installation of a Liquid Injection Valve 
(e.g. L-series), refer to ALCO’s catalog for selection 
and see the Superheat Table below.
Note 2: If a liquid-injection solenoid valve is used, 
the electrical connections should be in parallel with 
the hot gas solenoid valve.

Leakage test: 

 

After completion of installation, a pressure test 
must be carried out as follows:

 

- According to EN378 for systems which must 
comply with European pressure equipment 
directive 97/23/EC.

 

- To maximum working pressure of system for 
other applications.

Warning: 

 

Failure to do so could result in loss of refrigerant 
and personal injury.

 

The pressure test must be conducted by skilled 
persons with due respect regarding the danger 
related to pressure.

Service: 

 

Before any service shut down system and 
disconnect from power source.

 

Fully depressurize regulator. After reducing 
pressure to atmospheric
be opened, internal parts removed, cleaned and 
replaced, per Fig.4. Install parts in reverse 
sequence  as removed.

 

Replace gaskets 4, 6 and 7 before reassembling the 
regulator. 

 

Tighten capscrews evenly to torque specification 
35 Nm. 

DWG Nr.: CPH EZ 005000/PCN  863003 

Emerson Climate Technologies GmbH 

13509 Berlin 

 

 

On multiple evaporator systems, do not pipe hot 
gas to more than one evaporator. Use separate 
bypass regulators or consult the ALCO 
Applications Engineering Department. 
If the compressor is located above the evaporator, 
bypass should be piped to the evaporator to insure 
proper oil return during low load bypass 

On a long piping run, bypass to the evaporator, 
insulate the bypass to prevent condensate. 

Condensate can lead to unstable conditions and 

or flooding of the compressor.

 

Solenoid Connections 

If a compressor discharge line thermostat is used, 
it is recommended that the solenoid is wired in 
series with the thermostat. 
Voltage and frequency of the coil must correspond 
to the power source. Connect leads to the power 

(NEVER wire on the load side of the motor 

Note 1: For installation of a Liquid Injection Valve 

series), refer to ALCO’s catalog for selection 

eat Table below. 
injection solenoid valve is used, 

the electrical connections should be in parallel with 
the hot gas solenoid valve. 

After completion of installation, a pressure test 
must be carried out as follows: 

According to EN378 for systems which must 

comply with European pressure equipment 

97/23/EC. 

To maximum working pressure of system for 

other applications. 

Failure to do so could result in loss of refrigerant 
and personal injury. 

ressure test must be conducted by skilled 

persons with due respect regarding the danger 
related to pressure. 

Before any service shut down system and 
disconnect from power source.

 

Fully depressurize regulator. After reducing 
pressure to atmospheric only CPHE regulator may 
be opened, internal parts removed, cleaned and 
replaced, per Fig.4. Install parts in reverse 
sequence  as removed. 
Replace gaskets 4, 6 and 7 before reassembling the 

Tighten capscrews evenly to torque specification 

Библиотека СОК  

Содержание ACP

Страница 1: ... Valve Setting If desired set point differs from factory setting follow the procedure for setting before any installation and or refer to the Adjustment Table below The function of the CPHE and ACP series regulators is to prevent the suction pressure from falling below a predetermined set point thereby balancing the system Therefore the first step after installation is to determine this set point ...

Страница 2: ...onse by repositioning Regulator and cylinder unloaders have control interaction Differential should be increased between the controls by lowering the regulator s set point Regulator will not provide pressure control Pressure adjusting stem is set at a point so high that suction pressure never reaches the set point Re adjust the regulator acc to operating instructions External equalizer line upstre...

Страница 3: ...ch niemals mit dem anderer Geräte verbinden außer mit Nacheinspritzventil Einstellung Eine Änderung der Werkseinstellung nur unter Einhaltung folgender Schritte anhand der nachfolgenden Einstelltabelle vornehmen Heißgas Bypassregler werden verwendet um ein Absinken der Verdampfungstemperatur unter einen bestimmten Wert zu verhindern Als erstes ist dieser Einstellwert zu bestimmen Dies geschieht wi...

Страница 4: ...korrigieren Regler und Zylinderabschaltung des Verdichters beeinflussen sich gegenseitig Druckdifferenz zwischen Zylinderabschaltung und Reglereinstellung vergrößern Regler tiefer einstellen Keine Regelung Reglereinstellung ist so hoch gewählt daß der Einstelldruck nicht erreicht werden kann Einstellung gemäß Betriebsanleitung vornehmen Externer Druckausgleich vor dem Verdampferdruckregler angesch...

Страница 5: ...ýjimkou souvisejícího vstřikovacího ventilu Cílem regulátoru je udržovat tlak nad bezpečnou úrovní pro daný typ zařízení je proto nutné vyvážit systém úvodní kontrola zjistí zda je nastavený tlak pro soustavu vhodný Kontrola se provede následovně Spustit zařízení s připojeným manometrem do sání kompresoru Tlak se po ustálení provozu měří při uzavřeném obtoku horkých par elektromagnetický ventil v ...

Страница 6: ...ěním Navzájem se ovlivňuje ovládání regulátoru a odlehčovač přepouštěč pístu Je potřeba zvětšit rozdíl tlaků mezi ovládacími prvky snížením bodu nastavení požadované hodnoty regulátoru Regulátor neprovádí regulaci tlaku Dřík nastavení tlaku je nastaven tak vysoko že sací tlak nikdy nedosahuje požadovanou hodnotu Změňte nastavení regulátoru podle návodu k obsluze Umístění potrubí vnějšího vyrovnáva...

Страница 7: ...го выравнивания на всасывающей линии компрессора всегда после регулятора давления в испарителе НИКОГДА не объединяйте линию выравнивания с другими приборами за исключением ТРВ впрыска Уставки Если необходимо изменить заводскую уставку следует провести процедуру настройки перед установкой регулятора в соответствии с таблицей настроек см ниже Задачей регуляторов CPHE и ACP является предотвращение по...

Страница 8: ... для ТРВ впрыска K Код заправки R134a R22 R407C R404A R507 CL 15 13 22 GL 15 30 25 30 UL 30 45 40 Рекомендации по обслуживанию Событие Возможная причина Действия по устранению Утечка через регулятор В регулятор попала грязь Очистить седло регулятора Неустойчивая работа большие колебания контролируемого давления Переразмеренный регулятор Смотрите таблицу выбора в каталоге Наложение работы регулятор...

Страница 9: ...ent for 04 Date 20 06 2013 DWG Nr CPH EZ 005000 PCN 863003 CPHE ACP Emerson Climate Technologies GmbH Holzhauser Str 180 D 13509 Berlin Germany www emersonclimate eu Fig 3 ACP Fig 4 DWG Nr CPH EZ 005000 PCN 863003 Emerson Climate Technologies GmbH Berlin Fig 3 ACP max 120 C ...

Отзывы: