Wall-Mounted Dewpoint Sensor 

Product Information Sheet

 

210-2002

    

   Input Status Screen

 

Figure 1 - Sensor and Input Board Wiring

 

Overview 

The 210-2002 is a Vaporstat™ wall-mounted 
dewpoint sensor. The sensor is designed for 
measuring indoor or outside dewpoint or absolute 
humidity level.  
 

Sensor Wiring 

 

1. For wiring the dewpoint sensor to a CPC 

input board, use Belden #8761 shielded two-
conductor cable or equivalent. 
 

2. Connect the BLACK and WHITE wires to the 

screw terminals on the sensor’s connector as 
shown in 

Figure 1 (connect BLACK to Signal 

Ground and WHITE to 0-5V Output). Clip the 
SHIELD wire. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

3. Connect the SHIELD and BLACK wires to the 

0V terminal of the input board. Connect the 
WHITE wire to the SIG terminal of the input 
board. 
 

4. Connect 24VAC (a separate 120VAC/24VAC 

transformer must be used P/N 640-0039) to 
the power terminal on the dewpoint sensor 
back plate using the BLACK and WHITE wires. 
(This 24VAC transformer must only be used 
to power this dewpoint sensor. Do not use 

this transformer to power additional 
devices.) 

 

5. Locate the input dip switch for the sensor 

point, and set to the OFF position (LEFT for 
MultiFlex, DOWN for 16AI). Refer to the input 
board’s user manual for locations of the 
input dip switches. 

Controller Setup 

 
NOTE:  DO NOT set this sensor up with a sensor type 

of “Dewpoint”; that setting is only for CPC 
Dewpoint Probes (P/N 203-1902). This 
dewpoint sensor MUST be set up as a linear

 

 

sensor type. 

E2/Einstein 

 

1. After logging  into the   controller,   press                                    

6

 + 

 to open the Input Status screen or 

press the 

I

 key, 

 (System 

Configuration), 

 (Input Summary). (If 

using an Einstein, press F8(ACTIONS) from 
the  Home screen.  Press Y (System  Setup).   
Press 6 (Input and Output Point Setup).  
Press 1 (Input  Summary) to open the Input 
Summary screen.) 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Wall-Mounted Dewpoint Sensor 

Product Information Sheet

 

47

Содержание 210-2002

Страница 1: ...sed P N 640 0039 to the power terminal on the dewpoint sensor back plate using the BLACK and WHITE wires This 24VAC transformer must only be used to power this dewpoint sensor Do not use this transformer to power additional devices 5 Locate the input dip switch for the sensor point and set to the OFF position LEFT for MultiFlex DOWN for 16AI Refer to the input board s user manual for locations of ...

Страница 2: ...log The Analog Input screen will display 4 Once on the Analog Input screen move the cursor to the Sensor Type field press LOOK UP and set to Linear If using an Einstein press F7 LOOK UP and set to Linear 5 Move cursor to Select Eng Units and press LOOK UP Set this field to DF for Degrees Fahrenheit If using an Einstein press F7 LOOK UP and set to DF 6 Then set the following sensor properties Set t...

Страница 3: ...en select 2 Setup 4 From the Select Sensor screen choose the sensor you wish to set up 5 Once you select a sensor the Sensor Setup screen opens Enter a name for the sensor in the Name field for example DEWPOINT and set the Type field to Linear by using the scroll keys or pressing the red button the L button 6 Press 0 to go back to the Sensor Control screen Select 3 Setpoints and then choose the se...

Страница 4: ...o the bottom port on the flowmeter 2 Attach the long hose to the top port on the flowmeter 3 To ensure the meter is kept in the vertical position secure the flowmeter to the side of the gas bottle using the supplied tie wrap 4 Remove the protective cap from the nitrogen bottle and attach the gas regulator 5 Attach the open end of the bottom hose located on the flowmeter to the gas regulator Slide ...

Страница 5: ... minutes during which time the green LED below the display will flash Once calibration is completed the sensor will revert to its normal display mode Calibration Layout Refer to the calibration topic of the manufacturer s manual for the sensor s zero calibration layout Contact your CPC sales representative for calibration kit P N 210 2005 purchasing information EmersonTM Emerson Consider It Solved...

Отзывы: