Where input line reactors are not required to meet IEC 61000-3-12 (EN 12015) line reactors may still be required due to power supply quality issues,
poor phase balance, severe disturbances etc in this case refer to section 4.11
Supplies requiring Input line reactors
2.12 EMC compliance (general standards)
This is a summary of the EMC performance of the drive. For full details, refer to the
EMC Data Sheet
which can be obtained from the supplier of the
drive.
Table 2-16 Immunity compliance
1
Surge immunity of control circuits
on page 103 for control ports for possible requirements regarding grounding and external
surge protection
Emission
The drive contains an in-built filter for basic emission control. An additional optional external filter provides further reduction of emission. The
requirements of the following standards are met, depending on the motor cable length and switching frequency.
05500030
19
2.2
1.5
05500040
13
3.0
2.2
05500069
7
5.1
4.0
06500100
4.0
8.4
5.5
06500150
4.0
12.3
7.5
06500190
2.0
15.8
11.0
06500230
2.0
19.1
15.0
06500290
1.5
22.6
22.0
06500350
1.0
29.5
30.0
07500440
1.0
33.8
37.0
07500550
1.0
38.6
45.0
Standard
Type of immunity
Test specification
Application
Level
IEC61000-4-2 EN61000-4-2
Electrostatic discharge
6 kV contact discharge
8 kV air discharge
Module enclosure
Level 3
(industrial)
IEC61000-4-3
EN61000-4-3
Radio frequency radiated field
10 V/m prior to modulation
80 - 1000 MHz
80 % AM (1 kHz) modulation
Module enclosure
Level 3
(industrial)
IEC61000-4-4
EN61000-4-4
Fast transient burst
5/50 ns 2 kV transient at 5 kHz repetition
frequency via coupling clamp
Control lines
Level 4
(industrial harsh)
5/50 ns 2 kV transient at 5 kHz repetition
frequency by direct injection
Power lines
Level 3
(industrial)
IEC61000-4-5
EN61000-4-5
Surges
Common mode 4 kV
1.2/50
μ
s waveshape
AC supply lines:
line to ground
Level 4
Differential mode
2 kV
1.2/50
μ
s waveshape
AC supply lines:
line to line
Level 3
Lines to ground
Signal ports to ground
1
Level 2
IEC61000-4-6
EN61000-4-6
Conducted radio frequency
10V prior to modulation
0.15 - 80 MHz
80 % AM (1 kHz) modulation
Control and power lines
Level 3
(industrial)
IEC61000-4-11
EN61000-4-11
Voltage dips and interruptions
-30 % 10 ms
+60 % 100 ms
-60 % 1 s
<-95 % 5 s
AC power ports
IEC61000-6-1
EN61000-6-1:2007
Generic immunity standard for the residential, commercial and light -
industrial environment
Complies
IEC61000-6-2
EN61000-6-2:2005
Generic immunity standard for the industrial environment
Complies
IEC61800-3
EN61800-3:2004
Product standard for adjustable speed power drive systems (immunity
requirements)
Meets immunity requirements for first and second
environments
Drive model
AC Input Line reactor
Inductance
mH
Current rating
A
Input power
kW
NOTE