background image

®

Emergi-Lite®

Tel: (888) 552-6467 

Fax: (800) 316-4515

www.emergi-lite.com

11/17 750.0024 Rev. A

1/2

HP Series Remote Heads for Hazardous Locations

HP Series Remote Heads for Hazardous Locations

Class 

I

 Division 2, Class 

II

, Division 2 Groups F & G, Class 

III

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always 
be followed including the following:   

READ AND FOLLOW ALL SAFETY 
INSTRUCTIONS

1.

All servicing should be performed by qualified service personnel.

2.

Do not mount near gas or electric heaters.

3.

Equipment should be mounted in locations and at heights where it will 
not readily be subjected to tampering by unauthorized personnel.

4.

The use of accessory equipment not recommended by the 
manufacturer may cause an unsafe condition.

5.

Do not use this equipment for other than intended use.

SAVE THESE

 

INSTRUCTIONS

Installation Instructions

1. Remove the cover from the back box (See figure 1). 

2. Select the entry point on the back box for the conduit and open one of 

the knockouts (top or side).

3. Install the conduit fitting rated for Class 1 Div2 (provided).

4. For daisy-chain (input/output) wiring: open a second knockout and 

install the conduit fitting rated for Class 1 Div2 (provided).

Wall or Ceiling mount

 Install the unit to the wall or ceiling with 4 screws (not included).

  

  

Column mount (option)  

a. The universal mounting bracket is an accessory ordered separately 

(See figure 2).

b. The bracket can be installed using steel banding for routing around 

the column. Standard banding (not provided) must be maximum    
3/4-in in width.  The bracket can also be mounted on a Superstrut® 
metal framing (1 5/8-in channel series) using 1/4-in bolts (not 
provided). Holes are placed at 9-in apart horizontally.

c. Install the bracket, observing the indicator: TOP. 

d. Screw the unit onto the bracket with the 4 screws, washers and 

nuts included  in the bracket kit.

5. Route the wires from the wire conduit(s) through the conduit fitting(s)  

and into the back box.

WARNING:

Risk of Electrical Shock.

Disconnect Power before Installation.

Figure 1

Lamps

Cover

Back box

Conduit hub
entries(3)

Hook

Figure 2

Maximum mounting height 

as per UL924 standards

.

LED Lamp wattage

Maximum mounting height

6 - Watts

30 Feet

10 - Watts

50 Feet

15 - Watts

60 Feet

WARNING:

THE COLUMN MUST BE 

ANCHORED TO THE FLOOR 

AND CEILING.

Отзывы: