Emergi-Lite®
Tel: (888) 552-6467
Fax: (800) 316-4515
www.emergi-lite.com
10/16 750.1355 Rev. B
1/2
EL-2MRS Emergency Lighting Unit
EL-2MRS Emergency Lighting Unit
Self-powered Halogen Light Unit
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always
be followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1.
All servicing should be performed by qualified service personnel.
2.
All unused wires must be insulated to prevent shorting.
3.
Do not use outdoors.
4.
Do not let power supply cords touch hot surfaces.
5.
Do not mount near gas or electric heaters.
6.
Use caution when handling batteries. Battery acid can cause burns to the skin
and eyes. If acid is spilled on the skin or eyes, flush affected area with fresh
water and contact a physician immediately.
7.
Avoid possible shorting.
8.
Equipment should be mounted in locations and at heights where it will not
readily be subjected to tampering by unauthorized personnel.
9.
The use of accessory equipment not recommended by the manufacturer may
cause an unsafe condition.
10. Do not use this equipment for other than intended use.
11. When relamping, only use lamps specified in the fixture.
12. Allow battery to charge for 24 hours before first use.
SAVE THESE
INSTRUCTIONS
Installation Instructions
1. Turn of AC power.
2. Using a flat head screwdriver, insert the blade into the slot and gently
pry off the front cover (see figure 1).
Wall & Ceiling Mount
1. Remove battery from back plate.
2. Remove the appropriate knockouts in the back plate to mount to a
standard junction box.
3. Feed unit wires through the center hole of the back plate.
4. Make the proper connections (see figure 4):
a. For 120VAC, connect the black wire (120Vac) and white wire
(neutral) to the building utility.
b. For 277277VAC, connect the orange wire (277Vac) and white wire
(neutral) to the building utility.
c. Feed wires back into the junction box.
5. Mount and secure the back plate to the junction box.
6. Reattach the battery to the back plate and connect the battery ensuring
the red wire is connected to the positive terminal.
7. Snap top cover to back plate.
IMPORTANT:
Install product no higher than the maximum
mounting height of 10 feet from the floor.
WARNING:
Risk of Shock.
Disconnect Power before Installation.
Figure 2
1.
Manual battery test switch
2.
Red LED (indicates normal operation)
Figure 1
BACK PLATE
SLOT
CREW(8#32*1”)
RANSFORMER
OUSING
WHITE(NEUT
JUNC
BLACK
(FOR 120VAC CO
LAMP ASSEMBLY
Figure 3
Wire
Back plate
Center hole
Screw
Transformer
Housing
Lamp assembly
Black (120Vac)
Junction box
White (neutral)
connector
Orange (277Vac)
BLACK
WHITE
ORANGE
GREEN
G
R
W
277VAC 120VAC
INPUT INPUT
WIRING
G
R
EEN GROUND
WHI
T
E
BL
ACK
Figure 4
ORA
N
G
E