CMi4110 User’s Manual English v1.3
CMi4110 User’s Manual English v1.3
page | 19 (27)
[2018-06]
V1.3
3
Meter
date/time
6 bytes
(including
DIF/VIF)
M-Bus Type F
Meter date and time (YY-MM-DD HH:MM)
Mapped to OBIS 9.36
046Dxxxxxxxx
Bit 31-28 = Year-high*
Bit 27-24 = Month
Bit 23-21 = Year-low*
Bit 20-16 = Day
Bit 15 = Summer time flag**
Bit 14-13 = Century
Bit 12-8 = Hour
Bit 7 = Error flag
Bit 6 = Reserved for future use***
Bit 5-0 = Minute
*The year is read by combining the year-
high and year-low field. For example,
year-high = 0010 and year-low = 010 =>
year = 0010010
**0 = standard time, 1= daylight-saving
time
***0 = timestamp is valid, 1 = timestamp
is
not
valid
4
Accumulated
energy at
24:00
6
Bytes
(including
DIF/VIF)
BCD8
M-Bus Type A
Energy consumption (MWh, kWh, MJ,
GJ)
Mapped to OBIS 6.8
4C06xxxxxxxx = MWh, 3 decimals = kWh
4C07xxxxxxxx = MWh, 2 decimals
4CFB00xxxxxxxx = MWh, 1 decimal
4CFB01xxxxxxxx = MWh, 0 decimals
4C0Exxxxxxxx = GJ, 3 decimals
4C0Fxxxxxxxx = GJ, 2 decimals
4CFB08xxxxxxxx = GJ, 1 decimal
4CFB09xxxxxxxx = GJ, 0 decimals
4
Error flags
5 bytes
(including
DIF/VIF)
Uint16
M-Bus Type C
Error and warning flags
02FD17xxxx =Error and warning flags
Table 11: DIB fields, message type scheduled
– daily redundant
Scheduled-extended
The data message of message format
Scheduled mode-extended
contains all the meter data included in
the
Standard
telegram. In addition to these, a timestamp from the meter (meter date/time) is included in
each telegram.