Installation
Operating instructions RHF
63
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
7.3 Specified mounting position
A vertical assembling is specified. The terminals must be placed at the bottom.
When assembling the device within an electrical enclosure it must be ensured, that
the dissipation heat in the electrical enclosure is discharged adequately. The air
temperature of 45°C in direct proximity of the device must not be exceeded. The
air input- and air outlet on the up- and bottom side of the device (as far as availa-
ble) must not be buried by installation material as cable ducts or other devices.
When mounting external of a cabinet it is recommended to use the mounting
plates (accessories) and mounting rails .
Stop!
If these mounting instructions are not observed, this can lead to a thermal overcharge of
the filter module.
Caution!
If these mounting instructions and the connection instructions (chapter 9.2) are not ob-
served, this can lead to a thermal overcharge of the filter module and under circum-
stances to a production of smoke and/or a burning.
STOP