24
BA-en-4003-2005_TUE30
3.2.3 Power supply TCON01
If no 24 V DC internal works connection is available, use the TCON01
power supply. The power supply is designed for mounting on standard
rails NS35 and is capable of supplying two Terracompact II TCO030 units.
3.3 Supply voltage
Depending on design, the units are intended for connection to 24 V direct
voltage or 115 V / 230 V alternating voltage. The supply voltage is shown
on the type plate. Subsequent changes cannot be made.
If a TCO30 or TCB030 is supplied wiht 24 V, make sure that the supply
(24 V) is ungrounded. If required, the negative connection can be con-
nected with PAL.
3.4 Cable specification
Cable into Ex zone:
three-core 3 x 1.5 mm
2
core colors blue, brown, green/yellow, light blue-sheathed,
oil and gasoline resistant.
Attention!
If the ground cable is subjected to tensile stress in the application (e.g. if
KG/BN_ (ground cable) or KG/BS_(helix ground cable) is used), the cable
must be secured additionally with an external strain relief (e.g. a strap
clip).
Fig. 12:
Terminal
assignment,
power supply
TCON01
Z00
1
45
y
+
–
PE
L
N
45
24V
118
Содержание Terrabox TCB030
Страница 2: ...2 BA en 4003 2005_TUE30 ...
Страница 36: ...36 BA en 4003 2005_TUE30 Fig 16 Dimension power supply TCON01 Deep 107 mm Z00145y PE L N 45 24V 118 ...
Страница 42: ......
Страница 43: ......