22
User Guide •
Smartpack S Controller
About Power System Configuration
350030.013, 1v0-2012-06
5 - Logs and Reports options
The options in this logical group collect and present the system log, battery log,
report of active alarms, etc.
The logs and reports are organized in following groups:
• Active Alarm Log
• Event Log
• Battery Test Log
• Inventory Report
Active Alarms Log
You can browse through the stored system alarm messages (or alarm log). The
controller’s alarm log may store up to 1000 chronological events. Each log entry
contains event text, event action, time and date. When the log is full, the oldest
value is overwritten. The log is stored in EEPROM.
Example of alarm log in
Smartpack S
Controller’s submenu:
Logs/Report > Active Alarms
#
Description
Value
Limit
Alarm Group
Output
Note
BatteryTemp 1.1
42
30
----
---
SymmVolt 1.1
12,91
1,50
Alarm Group 15
----
RectifierError
1
1
Minot Alarm
-----
------
------
Event Log
The Event Log is a record of system related events automatically registered by the
system controller.
Example of Event Log in
Smartpack S
Controller’s submenu:
Logs/Report > Event Log
#
Date and Time
Description
Event
Note
yyyy.mm.dd hh:mm:ss
RectifierError
MinorAl:On
yyyy.mm.dd hh:mm:ss
SymmVolt 1.4
MajorAl:On
yyyy.mm.dd hh:mm:ss
LVD close
Info:On
yyyy.mm.dd hh:mm:ss
Door alarm
MajorAl:Off
yyyy.mm.dd hh:mm:ss
OutdoorTemp 81.1
Info:Off
----
You can also save the Even Log to a storage media -- read about
– or use
WebPower
or
PowerSuite
to delete, print and
save the log to a file in your computer.
Battery Test Log
The Battery Test Log is displayed in a results table; each row of data represents a
battery test. Also, the battery quality, calculated by completed battery tests, and
other test parameters are displayed.