User Guide •
Smartpack S Controller
The Smartpack S Controller
350030.013, 1v0-2012-06
Configuration
By the default,
Smartpack S
-based power systems are shipped from factory with
the controllers correctly installed and configured inside the power system.
CAN Bus Addressing
The power system’s master controller dynamically software-assigns ID numbers to
rectifiers. The master controller registers the rectifiers’ ID numbers — or CAN bus
address (01, 02…) — together with their Serial Numbers (software assignment).
Other control units make use of DIP switches for configuring their unique CAN bus
ID number (hardware assignment).
The
Smartpack S
controller’s ID numbers (1, 2…14) are assigned by DIP switches on
the controller’s top, refer to chapter
"Location of Connector, Communication Ports"
A maximum of 14
Smartpack S
controllers may be connected to the CAN bus.
Table 1. Smartpack S controller’s DIP switch addressing
Smartpack S
Controller**
ID # DIP Switch Position
1 — 2 — 3 — 4
1st Controller
1
OFF—OFF—OFF—OFF
2nd Controller
2
ON
—OFF—OFF—OFF
3
rd
Controller
3
OFF— ON—OFF—OFF
4
th
Controller
4
ON
— ON—OFF—OFF
5
th
Controller
5
OFF—OFF—ON —OFF
6
th
Controller
6
ON
—OFF— ON—OFF
7
th
Controller
7
OFF—ON— ON —OFF
8
th
Controller
8
ON
— ON— ON—OFF
9
th
Controller
9
OFF—OFF—OFF—ON
10
th
Controller
10
ON
—OFF—OFF—ON
11
th
Controller
11
OFF—ON —OFF—ON
12
th
Controller
12
ON
—ON —OFF—ON
13
th
Controller
13
OFF—OFF—ON —ON
14
th
Controller
14
ON
—OFF— ON —ON
Note:
The controller’s ID # corresponds to the DIP switch’s binary value plus 1
** The DIP switch positions above applies to all controllers, except for
Smartpack2 Master
and Compack controllers, which have unchangeable ID#
11 and 1 respectively
Smartpack S controller's
DIP switch configuration
ID <1>
(All Switches OFF)