User’s Guide for MB-350U-C-(485M) 

Ver. 1.1

 

ELT SENSOR 

Содержание MB-350U-C

Страница 1: ...User s Guide for MB 350U C 485M Ver 1 1 ELT SENSOR ...

Страница 2: ... 2 Installation 3 Front Panel Display 4 Level LED CO2 CO 5 Specifications 6 Calibration 7 Cautions 1 Connection with PC 2 Monitoring 3 CO2 Level Setting Change III RS 485 Protocol Sending only Option 1 H W Interface 2 Mod Bus Protocol 1 4 CO Level Setting Change ...

Страница 3: ...DC 12V Adaptor 3 Manual 4 USB Cable 2 Installation Connect power jack to main body Requiring 2 minutes stabilizing time USB cable is available for connection to Computer and ELT_WSD program enables alarm range setting and measured data save on Computer 2 ...

Страница 4: ...e 2 RH typical 0 99 RH Power Supply DC 12V 1A AC DC adaptor CO2 CO Level LED display Red Orange Green LEDs for CO2 CO each Alarming On Off switch Sounds Melody can be settable on off with 3 seconds press Operating Condition 0 50 0 95 Storage Temp 30 70 Dimension main body 135 0 x 90 0 x 28 0 mm W H D Certificate CE ROHS 3 Front Panel Display MB 350U C 485M Model 4 Level LED display CO CO 3 CO2 Ver...

Страница 5: ...error 2 Do not disassemble modify or repair the products 3 Avoid shock vibration direct sun light 6 Calibration None Factory calibration operation mode for Green house and other Agricultural usage M CO2 Manual calibration for 10 minutes in fresh air or 400ppm Standard CO2 gas MCDL A CO2 Automatic calibration mode ACDL Monthly auto calibration For HVAC ventilation usage 4 Co CO 0 ppm Manual calibra...

Страница 6: ...0 interface of PC Execute ELT_WSD_MB 350 exe with mini USB cable connected between PC and MB 350 of which 12V Power 12V AC DC Adapter should be provided ELT_WSD emulation Program II 1 Connection with PC Select model B 530H MB 350 Press RESCAN button and auto select USB Serial Port COM xx 5 1 2 ...

Страница 7: ... LogFile CSV saved to sub directory of ELTWSD_EK100 prg mark v on Time stamp menu add time for further analysis 6 c0996t 262h40e0000o000764 c 0996 t 262 h40 e0000 o0007 64 CO2 996ppm temp 26 2 C humidity 40 e option not available VOC 0000 V Model CO 0007ppm 64 Checksum 4 5 v 3 v ...

Страница 8: ...u Type in ppm value for CO2 Level the default values are L0 1000 ppm L1 1400ppm L2 2500ppm 1 2 3 Low High Very High GREEN L0 ORANGE L1 RED Click Box Send Command so that changed Alarm Level L0 L1 to be fixed CF L2 Sound Alarm range is deactivated 3 CO2 Level Setting Change 7 ...

Страница 9: ... changed Alarm Level L0 L1 to be fixed 4 CO Level Setting Change 8 Beep Sound Warning MB 350U C 485M sounds different type of Beep depending on CO value measured every 40 seconds CO val HI GH L2 CO2 value Red Continuous BEEP L1 CO2 val L2 Red Discrete Beep 2sec Beep 2sec pause MI DDLE L0 CO2 val L1 Orange Discrete Beep 1sec Beep 1sec pause LO W CO2 value L0 Green No sound 1 2 3 Beep can be disable...

Страница 10: ...5 Modbus 2 485B 3 GND A Pin Connection 3 pin Connector CN1 RS 485Modbus Protocol Option II 9 B Communication Specification RS 485 2 Wire half duplex Parameter Description Baud rate 9 600BPS Option 19 200 BPS Data Bit 8 Bits Parity Bit None Stop Bit 1 ...

Страница 11: ... PPM 0x0051 Temperature 2 Byte Integer Temperature Ex 255 255 10 25 5 0x0052 Humidity 2 Byte WORD Humidity Ex 75 75 0x0053 CO 2 Byte WORD PPM CO Ex 25 25 PPM 2 2 Supported Function Code Currently supported only code 03 and exception response Error code 0x83 or other CODE 0X80 Exception code Description 01 Exception of Function code 02 Exception of Starting Address 03 Exception of Quantity of Regis...

Страница 12: ...Thanks for Reading Contact Charlie Wang Lucy Kim TEL 82 32 719 8055 sales eltsensor co kr 11 ...